|
Safety and Buildings Plumbing
Information Q&A
New June 2, 2008: Comm 82.38(3) - 6/1/08
Where can the fire test and
draindown from a standpipe discharge?
Comm 82.41(3) -
6/1/08 What are the cross connection control
requirements for an emergency eye wash located on a hose?
Comm 84.10(2)
- 6/1/08 How would a health care treatment device
that includes a reuse system be classified for the purposes of product
or plan review requirements?
Comm 82.40(8)(e)2 -
6/1/08 Is there anywhere in the plumbing system
where a stop and waste-type control valve may be installed underground?
Comm 82.31(13)(b) -
6/1/08 May only one water closet be included in
a horizontal wet vent where there are two lavatories and two bathtubs
or showers?
Use "find" (Control
+ F) to
locate a key word or code section.
All attachments are PDF files. Explanation of File
Formats
Link to Wisconsin Uniform Plumbing
Code Online.
Code
or statute reference - Date of Posting
State Stats.
145.01.10 9/25/98
Is a plumbing license required to pre-fab plumbing?
Yes, with one exception. When a plumbing
system has
received product approval, the piping system may be pre-fabbed by
assembly workers who are not licensed individuals. Otherwise, a license
is required to construct a plumbing system.
145.01.10 11/24/00
Are water lines to soda dispensers considered plumbing?
Yes, if the line carries drinking water, it's
considered plumbing.
145.01.10 11/24/00
Is a license required to install pipe liners? No.
Pipe liners are considered a repair at this time.
145.02.2
6/1/06
May a city require
installation of an RP valve at the water service point of entry to the
building? Only in sewage treatment facilities,
marinas, wharves, or docks, as
listed in Comm 82.41(3)(c).
145.02.2
12/1/00
Can a sanitary district have more stringent requirements
than the code? Yes, in some instances. There
is specific statutory
authority in 200.11(3)
of the statutes that allows a commissioner of a sanitary district to
require preliminary treatment prior to discharging into the sanitary
district's system. This is not the plumbing inspector or sewage
treatment plant operator. The department will require documentation
that the action will provide additional treatment over the plumbing
code minimums.
145.06
6/1/06
What part of a dialysis
system is considered plumbing and who can
install the system? The entire dialysis system
is considered to be part of the
plumbing within a health care facility. A fully-licensed plumber
(apprentice, JP or MP) may install the entire system. A
restricted-appliance plumber may install the plumbing from an existing
pipe and
through the last water treatment device. A fully-licensed plumber must
install the piping from the last treatment device to the dialysis
stations.
145.06
(7/25/05)
May a homeowner install plumbing in a portion of their
home intended to
be used by the public? For example, if a shampoo sink or
public restroom is to be installed for an in-home beauty
salon?
No,
the homeowner may
only install plumbing in a one-family dwelling. The portion
of the building in this example is public and a licensed individual
would be required.
145.06 3/13/98
An MP is not required to own a business. A
master plumber may work for another and be in charge
of plumbing installations. It is not required that the master own a
share of the business.
145.06 7/12/00
Who is the "responsible master"? The
responsible master is any master that agrees to be
responsible for the installation of plumbing. There is no distance
restriction on the master from the installation.
145.07 6/11/01
Does a degree in engineering technology qualify someone
to take the MP exam? No. The statutes require
that a degree in "engineering"
is necessary to write the MP exam. This degree must include courses
related to plumbing (see Comm 5.91 (3)) or be a degree in civil
engineering or mechanical engineering.
145.11
5/10/07
What
advertising requires the master plumber license number?
The
law says the MP number must be on items that are Printed material
designed for public distribution (PMDFPD). Of the
following, what meets this definition? Business cards -
PMDFPD, yes. One business card on the wall of the plumbing
shop and not distributed, no MP number required. Pencils/pens
with advertisement - PMDFPD, yes UNLESS the pencils are not designed
for public distribution, then, no. For instance, you buy one pen for
use in your office. Yellow page ad - PMDFPD, yes. Business
page listing – The single or double-line phone book entry is
a point for information transfer, not advertising. This
listing does not require the MP license number. Paint on
plumbing truck Not printed material, not publicly
distributed. No. This advertising doesn't leave the property,
it stays on the truck. Billboard off the
business property PMDFPD, Yes the MP license is required on distributed
billboards. Business signs. No, these signs are
informational for customers to find the shop.
145.11 11/15/06 What
"advertising"
literature needs the MP number? Trucks and
equipment do not
need to carry the MP license. Phone books (when listed as "plumbing or
plumber") require the MP number. An unlicensed person advertising to
clean drains and perform minor repair work may advertise under the
heading of plumbing contractor, but their advertisement must delineate
the type of statute-compliant work they perform. Any
advertising requires the MP number.
145.14
5/10/07
May Restricted
Service Master Plumbers install exterior grease interceptors?
May they submit the plans for those projects? Yes,
a RSMP may install an exterior grease interceptor and they may also
sign the plans for projects where they will be the responsible master.
145.14
2/6/07
When is a water
supply system considered to be existing, so that a restricted appliance
could install a device or appliance? An
existing water supply system exists when the fully-licensed individual
(or occupant of a single family residence) has installed the piping
from the meter or control valve of a pressure tank to the point past
where the water treatment device is to be installed.
Administrative Code
Comm 5.07 3/8/99
What to do if one doesn't have the continuing education
required for
renewal. See the attached
document.
Comm
5.92.3
5/15/01
Can a journeyman write a restricted master exam?
Yes, if the 1000-hour requirement is met. See
the attached
petition report.
Comm
5.94.3
3/18/98
Is there a time limit to get the 1000 hours work for JPRA
exam? Yes, the 1000 hours of work required to
write the JPRA
exam must be completed during a continuous year. The credential must be
renewed after the 2 year expiration. For renewal see Comm 5.07(2). See
related petition.
Comm
81.01(38)
5/26/98 The plumbing code definition of one building.
Two
buildings become one when they touch or share a
roofline. Individual units separated by a "division wall" and having
individual sewers or water services can become separate buildings. For
more information, see the description attached.
Comm
81.01(176)
(11/24/04)
What is the definition of “process piping?"
The process piping
is a system
that conveys process water. Process water is potable water that has
been altered or modified by the addition of a product, chemical or
ingredient such that it has been degraded to where it would cause a
nuisance, be aesthetically objectionable, or could cause minor damage.
Drinking the water would not constitute a health hazard.
For example: Water is potable to the point where the first ingredient
is added to the water for brewing beer. From that point on the system
is process piping.
Comm 81.01(176)
6/6/00
When is a depression in the floor considered plumbing?
When a grated trench is installed in a
building it is
considered a plumbing fixture and must be properly drained and disposed
of as in 82.10 (8). The only exception to this is when the depression
or pit is a containment device for hazardous waste.
Comm
82.01(176)
3/1/05
When is the piping within a kiosk not considered to be
under the authority of Comm 82? A kiosk that
is mobile (one
that has wheels) would not be considered a building and the piping
inside would not be required to compy with the plumbing code.
Comm
81.01(179)
2/6/07
Is there a definition for a storm
plumbing system? No, however storm plumbing
system means
piping, appliances and devices
that convey, hold infiltrate, or treat storm water from building runoff. This includes all piping
connected to piping
conveying runoff from buildings. The
portion of the storm plumbing system under the authority of the
Wisconsin
Uniform Plumbing Code is that portion conveying storm water to the
municipal
system or discharging to grade.
Comm
82.20
6/1/06
Must plans be submitted
for plumbing review for the piping receiving
the discharge from a detention basin draining one acre or more?
When on private property, the piping is
considered
plumbing and
plan review is required.
Comm
82.20(1)
7/22/05
Does
a pressurized private interceptor main sewer plan need to be submitted
for plan review? Sometimes. If the dfu
load on the piping would require a
gravity
flow pipe size of greater than four inches, the plan needs to be
submitted to the department or an appropriate agent city.
Comm
82.20(1)
11/18/97
Municipality can require plan review beyond code
An agent municipality can require plan review
for fewer
than 16 plumbing fixtures. There is no requirement for the department
to see the ordinance drafted for this requirement, however an ordinance
is required.
Comm 82.20(1)
3/13/98
Bed and Breakfast plumbing review requirements. Bed
and breakfasts only require plumbing plan review
when new construction is involved. An existing building converted to a
bed and breakfast does not require plan review if it meets the
statutory definition (254.61) of bed and breakfast. A new building is
considered a hotel or motel even if it's licensed as a bed and
breakfast. /p>
Comm 82.20(1)
4/7/98
Replacement grease interceptor plan review All
grease interceptor installations require plan
review.
Comm
82.20(1) 5/10/07
May a POWTS designer sign plans for an
exterior grease interceptor? No,
Currently the state Department of Regulation and Licensing only permits
the POWTS designer to design septic tanks for private sewage disposal
systems, drain fields designed to serve such septic tanks and sewer
service from the septic tank or sewer extensions from the mains to
immediate inside or proposed inside foundation wall of the building.
Comm
82.20(1)
(11/24/04)
Plan review requirements for
multiple dwellings See Table 82.20-2 which
states "For the purposes of plan submittal,
public buildings do not include zero-lot line row houses where each
living unit is served by an individual water service and an individual
building sewer." For clarification, these individual connections (water
and sewer) are to the public sanitary sewer or public water main, or to
a private interceptor main sewer and/or private water main. The
building may be defined as a row house, apartment or condominium, but
the individual plumbing system requirement must be met. For the
interpretation of this section, the private interceptor main sewer and
private water main extends to the most upstream building served. So all
buildings are treated identically.
Because of their individual connections each row house would be
required to have one full sized drain and vent stack.
Comm
82.20(1)
9/25/98
May pre-fab systems be assembled prior to plan
approval? Yes, if they are not installed.
82.20 (1) (a) requires that
"Written approval for the plans shall be obtained prior to installation
of the work."
Comm
82.20(1)
7/28/03
When is registration or plan review needed for CCC
devices?
1. Plan review for testable CCC devices is required
when the installation is in health care or related facilties. For all
other installations, registration of testable CCC devices with the
division is required.
2. When replacing an existing assembly with the exact same model number
and size? NO, but on the next test report a letter from the plumber
should be sent with the report stating it has been changed.
3. When replacing an existing assembly with the same ASSE # but a
smaller size? NO, not when dealing with non-potable water but the
letter from the plumber stating it as been changed should still be
sent. When dealing with potable water, it would be up to the reviewer
through a phone conversation with the submitting party.
4. When replacing an existing assembly with the same ASSE # but a
larger size? NO, not when dealing with either potable or non-potable
water.
5. When moving an existing assembly vertically but on the same floor? NO
6. When moving an existing assembly to a different floor? YES, always.
7. When moving an existing assembly horizontally? This is where things
get a little sticky. A good rule of thumb may be to use a 10-foot
diameter sphere. If the assembly is to be moved ten feet from its
original location, then YES. If not, then NO. There would be some slack
given even if it would be moved out of the sphere, it would be
determined by a plan reviewer from a conversation with the plumber.
Comm
82.20(1)
8/10/00
Can a municipality force a homeowner to connect to public
sewer & water? Yes, by ordinance. See attached
copy of statute 281.45, the enabling language.
Comm
82.20(1)
5/20/99
Plan submittal/inspection of Native American Land
See attached
File
Comm
82.20(1)(b)
1/4/99
Approval for private water mains Which
water mains get approval from Commerce or DNR?
This memo gives different situations describing when a water main will
be approved by DNR and which ones will be approved by Commerce or a
Agent Municipality. Attached.
Comm
82.20(1)(b) 10/4/05
Does the
installation of a
two-inch diameter pressurized private interceptor main sewer require
plan review? Sometimes.
If the pressurized private interceptor main sewer is carrying more than
250 drainage fixture units (so that a gravity flow pipe serving the
same flow would be required to be greater than four inches in diameter)
plan review is required. Also, if a gravity flow private
interceptor
main sewer of more than four inches in diameter discharges
into a sump,
and then the downstream pressurized sewer must be included in the plan
submittal.
Comm
82.20-1 6/1/04
Referring to Table 82.20-1, number 2., what type of
buildings would be owned by a metropolitan or sanitary sewer district?
Basically this refers to treatment plants,
however if
the sanitary sewer districts owned other buildings those buildings
would need plumbing plan submittal to Commerce (and approval) prior to
construction.
Comm 82.20-2
6/1/04
Do I need to submit storm private interceptor main
sewers? What is a storm private interceptor main sewer? All
piping designed to serve as a private interceptor
main sewer greater than 4" in diameter (when sized for gravity) must be
submitted. This includes storm. A storm private interceptor main sewer
is serving the runoff or piping from two or more buildings.
Comm 82.20-2
6/1/04
Are plans required to be submitted for a building that
contains a single-family dwelling and a commercial establishment?
Yes, if the fixture count of the total
building
includes 16 or more fixtures
Comm
82.21(2)(a) 5/10/07
How
do you know if a cross connection
control device may remain in service if it is not code compliant now,
but may have been code compliant when it was installed? A
cross connection control device may remain if it was code compliant at
the time of installation unless the cross connection device is failing
and causing a backflow incident or is being replaced. The attached
table (PDF file) has the known dates of when cross connection
control devices of various types were code compliant.
Comm
82.21(3)
6/6/00
What needs replacement in existing installations?
Attached
is a document that will help an inspector know what needs to be
replaced if found on inspection of an existing installation.
Comm 82.30(1)
6/01/04
If showers are installed on pool decks, can the drains
serving those showers be considered deck drains or must those drains be
sanitary drains? The shower drains used to
wash chlorine off pool patrons should be
considered as deck drains unless the showers are provided with soap and
are to be used as sanitary washing facilities. If the showers are
provided with soap, the drains should discharge to sanitary.
Comm
82.30(1) 6/1/04
Are floor drains sanitary fixtures? Floor
drains are sanitary fixtures, however area drain
inlets are very similar to floor drains. Table 82.38-1 designates the
discharge points for floor drains. Some floor drains, like those
located in well pump houses may discharge to grade.
Comm
82.30(3)
2/5/02
What is the dfu value of a garage catch basin? According
to the Table 82.30-1, the drainage fixture
unit value of a floor drain is 4. Since a garage catch basin is a
modified floor drain, the dfu value of a garage catch basin is also 4.
Regardless of the number of fixtures or trenches connected to the
garage catch basin, the dfu value is 4.
Comm
82.30(3)
1/26/01
How is the dfu value calculated for a pumped discharge? Because
the pumped discharge could continue for an
extended length of time, the continuous flow calculation is used to
calculate the dfu value for a pumped discharge. This is two gpm/dfu.
Comm
82.30(3)
8/16/98
Can a 3-inch receptor have a dfu of less than 4?
Refrigerated food case only and with an
approved
petition. Yes, a petition has been granted to allow a 3-inch receptor
to have a dfu value of less than 4. See the report #1,
report #2.
Petition #88-00190-P
Comm
82.30(3)
7/28/03
Is an automatic clothes washer a wall outlet fixture? Yes.
Even if the trap for the fixture drain is
installed below the floor, an automatic clothes washer is considered a
wall outlet fixture.
Comm
82.30(4)
(11/24/04)
Does the requirement for a minimum diameter piping of
2” underground apply to pressurized piping?
No.
(b)
refers to underground gravity “drain” piping. The
pipe you’re referring to is designed according to Comm
82.30(10)(b)3.a. and b.
Comm
82.30(4)
7/28/03
Can a municipality can dictate the size of a Private
Interceptor Main
Sewer? A municipality can dictate the size of
PIMS. The
requirement must be by ordinance. The department does not need to
review the ordinance.
Comm
82.30(4)
2/25/04
Can a laundry tray which is being used as a lavatory
serve as the 1-dfu fixture for a wet vent?
No. If a fixture is sold as a laundry tray, the fixture
unit value is 2, regardless of usage.
Comm
82.30(4)
2/25/04
Is a laundry tray a service sink for dfu value? No.
A service sink is a specific fixture that is labeled
as a service sink by the manufacturer. A customer may use a laundry
tray as a service sink, but that doesn't affect the fixture units.
Comm
82.30(5 ) 5/24/02
Can a building drain be installed at less than 1/8" per
foot? Not according to code language, however
a petition for
variance has been approved to allow the installation of a building
drain at a pitch of 1/16 inch per foot. The computed velocity for a 4"
and 6" building drain was in excess of the 2.0 feet per second minimum.
See petition.
Comm
82.30(8)
When is a tee a heel-inlet fitting? A tee on
its back can meet the radius requirement for a
floor outlet water closet discharging to a horizontal line. It is not
considered a "heel inlet" fitting, as the manufacturers don't list it
as a heel inlet fitting in their catalogues.
Comm
82.30(11)
- 5/29/06 Does
a crawl
space
need a floor drain is a water heater is
installed in the crawl space? No. The
code only requires the drain where a plumbing fixture
is located on a “floor” which is entirely below
grade. The definition of a floor is an area on which a person
stands. Since a crawl space does not meet that definition, a
floor drain is not required by code when a water heater is installed in
the crawl space. Remember, a receptor is still required for
the T&P relief valve.
Comm
82.30(11)
(11/24/04)
Is a petition required from Commerce if DNR has issued a
variance to a well setback? Are Commerce staff and agents required to
enforce the well setbacks stated in NR 811 and 812? If
DNR has issued a variance, a Commerce variance is not required.
Commerce staff and agents are required to enforce well setbacks as they
are referenced in the code.
Comm
82.30(11)
11/18/97
A municipality can dictate the type of saddle fittings.
A municipality can dictate the type of saddle
fittings.
The requirement must be by ordinance. The department is not required to
review the ordinance, but the saddle is required to be approved. See
84.30.
Comm
82.31
02/22/06
Are there limitations to
the installation of air admittance
valves? Yes, the attached
document lists the currently-approved devices and
their limitations.
Comm
82.31(3)
11/17/97
The discharge of dfu fixtures into a circuit vent.
Can three one-dfu fixtures discharge upstream
of a
circuit vent connection? No, the connection of more than two one-dfu
fixtures to the circuited vented drain line must be downstream of the
circuit vent connection. The wording is "may discharge into a
horizontal drain served by a circuit vent." Therefore, only two one-dfu
fixtures can be connected to the circuit vent.
Comm
82.31(3)
11/19/97
Are air admittance valves approved in Wisconsin?
The approval of specific air admittance valves
is
included in the Product Register. The first was effective on January 1,
2001.
Comm
82.31(4)(b)4.
6/1/04
May a floor outlet fixture vent connect to the vent stack
at a point 38" above the floor in which the floor outlet fixture is
located? Yes, only wall outlet fixture vents
are required to
extend above the next higher floor level prior to connecting to the
vent stack.
Comm
82.31(11)
7/28/03
Can a dishwsher standpipe connect to a horizontal common
vent? No. A dishwasher standpipe can not
connect to a drain
vented by a horizontal common vent. The code language prohibits this
connection by saying ""fixture drains from two traps serving a kitchen
sink with or without a dishwasher" The traps must serve a kitchen sink
for the installation to include the horizontal common vent.
Comm
82.31(13)
11/17/97
Horiz wet vent - tub/shower and lav must share drain
Using the horizontal wet vent, the lavatory
and tub or
shower must share a common horizontal drain between their connection
and the water closet connection.
Comm
82.31(13)(b) - 4/1/08
May only one water closet be included in
a horizontal wet vent where there are two lavatories and two bathtubs
or showers? Yes. The only limitation
of the horizontal wet vent is that more than two water closets may not
be included on the vent.
Comm
82.31(14)
07/28/03
Calculating loads for circuit vents and relief vents
What is the dfu load when a relief and circuit
vent
join? The dfu load returns to the total served by both vents at that
point that the two join together. For example, if there are 24 dfus on
a circuit vented line, the relief vent has 24 dfus and the circuit vent
has 24 dfus, there are only 24 dfus when the two connect.
Comm
82.31(16)6/1/06
What’s required
for the vent terminating through an
exterior wall to be "approved by the department"?
For this section, "approved by the department" means
meeting the
requirements listed in the code for vent terminals and terminating
a through-the-wall vent no less than five feet below a
building overhang.
Comm
82.31(16)(d)
and (e) 0/4/05
How far must a
vent
that extends through a building wall terminate below a building
overhang? The
department approval will permit the vent termination a minimum of five
feet below
a building overhang.
Comm
82.32
11/17/97
Do material changes require re-submittal of plans?
Sometimes. When the materials are changing to
a more
restrictive material, like from Type L copper to PEX, a revision will
be necessary. If you are replacing type K with type L (and all
installation requirements are met) a revision may not be necessary. If
a conventional installation is replaced with a "home run" system, yes.
Comm
82.32(3)(a)
2/25/04
May a garbage disposal be installed on a breakroom sink?
Yes. There are no requirements prohibiting
the
installation of a garbage disposal on a breakroom sink.
Comm
82.33(1)
12/23/03
Is an
emergency eyewash required to be discharged via
indirect waste to the plumbing system?
An
emergency eyewash may be permitted to directly
connect to the sanitary system if the outlets from the water supply
system are above the bowl of the eyewash (an air gap is created). For
biologically or chemically isolated laboratories, contact S&B plumbing staff
for more information. Comm
82.33(7)
8/8/01
Topic What is the air gap separation distance in a drain
system?
The code compliant separation distance is stated in
82.33 (7). For piping of one-inch or less in diameter, the air gap is
twice the diameter of the indirect waste piping. For piping greater
than one-inch in diameter the code compliant separation is 2 inches.
Comm
82.33(8)
3/13/98
Sizing for local wastes serving T&P valves
How do you size a local waste serving T&P
relief valves? The receptor size dictates the dfu value for sizing the
local waste piping. Comm Table 82.30-1 is used for sizing the piping
based on the dfu value.
Comm
82.33(8)
3/13/98
Denied petition for lavatory drain tailpiece
A petition was denied on 7/17/92 for a local waste
piping serving as a receptor for condensate waste to discharge to a
lavatory drain by means of a branch tailpiece. Petitioners statements
included that no other place existed to discharge the condensate, that
the air conditioner was located about 10 feet from the bathroom area
and that these units are used only 2 to 3 months per year. Connecting
the condensate to the trap is logical because the trap is always being
used. The petition was denied because the intent of the code could not
be met.
Comm
82.33(8)
7/28/03
Where is the air-gap when using a funnel receptor?
When a funnel is used in connection with a floor drain
grate, the
air-gap for the indirect waste is measured as the distance between the
end of the direct waste pipe and the rim of the funnel.
Comm
82.33(8 ) 7/28/03
May an ice machine discharge into a branch tailpiece?
A branch tailpiece serving a sink is not an approved
receptor for the discharge from an ice machine. A petition for variance
was approved for the installation. See attached.
Comm
82.33(9)
April 9, 2004
Is a floor drain required in an elevator pit?
The Wisconsin plumbing code does not require the
installation of a drain in the elevator pit, but the ASME standard
A17.1-96 does. The rule requiring the drain can be found in Rule 106.1b
(3).
Comm
82.33(9)
7/28/03
Must an eye wash discharge to sanitary?
No. An emergency eye wash may discharge to the sanitary
drain system or the chemical waste system. If the eye wash discharges
to the chemical system, it need not be considered for sizing the
dilution or neutralizing basin. See 82.33(1), dated 12/23/03, for more
information.
Comm
82.33(9)
2/27/01
Does the drain receiving elevator drain discharge require
a vent?
No. The elevator drain discharge is considered
stormwater. Only clearwater interior drains require venting.
Comm
82.33(9)(g)
10/4/05
Must a sink in a
refrigerated food storage room discharge through an
indirect waste to the drainage system?
Yes.
The code states that “Drains serving
refrigerated food storage rooms,
compartments or display cases shall discharge to the sanitary drain
system
through indirect waste piping.”
Comm
82.34(3)
7/28/03
Where should kennel wastes discharge?
Interior wastes shall discharge to sanitary and
exterior wastes may discharge to surface. No special catch basin is
required. Kennel wastes may discharge to surface if the drain doesn't
discharge to a drainage ditch or waterway and the drain doesn't
discharge to high groundwater area. The groundwater designation is
dependent on soil texture, structure and depth to creviced bedrock. For
more information contact DNR, 608-266-7715. See attached.
Comm
82.34(4)
(7/22/05) When
hose bibbs are installed in a garage and the wastewater is discharged
to a drain, is a catch basin required?
If the garage is intended to be used as a vehicle wash, a garage catch
basin or car wash interceptor would be required.
Comm
82.32(4)(b) 6/1/06
Is a pedestal pedicure spa
considered a pedestal fixture?
Yes. A pedestal pedicure spa may be installed in accordance with the
pedestal fixture requirement for vertical distance from the fixture
outlet to the trap.
Comm
82.33(9)(c)1
6/1/06
May a 1.5-inch receptor
for a residential clothes washer be increased in diameter above the
trap inlet in order to terminate less than 32 inches above the floor?
No. The entire standpipe must be two inches in diameter in order for
the receptor to terminate less than 32 inches above the
floor. A two inches diameter standpipe that terminates
between 26 inches and 48 inches above the floor must have a two-inch
trap and fixture drain installed downstream of the standpipe.
Comm
82.34(3)
7/28/03
Where should kennel wastes
discharge?
Shampooing or bathing of animals:
To POWTS, if designed for
discharge
To Sanitary sewer (Pretreatment - filter to remove hair)
Interior kennel area
floor
drains(sediment bucket or catch
basin):
To POWTS, if designed for discharge (Pretreatment - filter
to remove
hair)
To a DNR-approved rain garden (Pretreatment - filter to remove
hair)
To a Sanitary
sewer (Pretreatment - filter to remove hair)
Exterior kennel area floor drains(sediment bucket or catch
basin):
To Grade
To Sanitary sewer or POWTS only where permitted by local authority
and kennel is covered.
For more information, contact DNR, 608-266-7715.
Comm
82.34(4)
4/2/04
May a single trench drain be installed to serve several
rooms?
No, trench drains (or any other type of fixture) must be
located so that the fixture is easily accessible for cleaning, meets
the trap-compartment requirements and complies with the basic plumbing
requirements. Since trench drains are required to connect individually
to the catch basin with a return bend, unless they're designed as floor
drains with individual traps, S&B considers it hazardous to run
trenches through walls.
Comm
82.34(4)
11/19/97
Exterior grease interceptor approval requirements
Pre-fab exterior grease interceptors require product
approval.
Comm
82.34(5) 5/10/07
If
a three-compartment sink has food waste grinders installed on
two of the compartments and the third compartment is a sanitizing
compartment, may the entire sink bypass the grease interceptor?
No.
The code specifically allows the discharge from a food waste grinder,
the discharge from a sanitizing compartment or both the option of
bypassing a grease interceptor, not two food waste grinders in one
three-compartment sink.
Comm
82.34(5)
7/28/03
Are there circumstances where grease interceptors do not
need to be
installed?
Under conditions where grease will not be significantly
generated, the department may allow a designer to install fixtures
without a grease interceptor. See the attached
letter for an example of the department's correspondence.
Comm
82.34(5)
4/4/01
What are plumbing requirements for bed and breakfasts?
Plan review is required for bed and breakfasts when the
number of fixtures exceeds the plan review requirement for public
buildings. Three or more tenants requires pressure balance shower
valves. Less than 9 rooms is considered to produce insignificant grease
and will not be required to discharge kitchen wastes through a grease
interceptor.
Comm
82.34(5 ) 6/29/01
Is a grease interceptor required for an "auto fry"?
An auto fry is defined as an enclosed, ventless, self
contained individual-serving deep fryer. A grease interceptor is not
required where only one auto fry is installed.
Comm
82.34(5)
7/30/01
Where are grease interceptors required?
Day Care: Licensed for more than
9 children.
Restaurants: Only exception is when food is served
on paper plates and spatula is only utensil for frying food.
Elderly housing: Main kitchen. Community room if
more than one-compartment sink is installed.
Church: Two compartment sink or larger.
Fire Stations: Nine or more station employees
requires grease interceptor. Break rooms: When
more than 2 compartment sink is installed and more than a stove and
dishwasher.
Camp: Same as church. More than two compartment
requires interceptor. CBRF: 9 or more residents
requires interceptor.
Town Hall: Two or more compartments requires
grease interceptor.
Fast food: Pizza machine = No, hot dog machine =
No, Meat slicer = Yes, Presliced meats = No, Meatball, chicken
bar-b-que, soups = Yes.
Grocery store meat department: Requires
interceptor.
Bakery: requires grease interceptor.
Schools: Home Economics room=No. Main kitchen =
Yes.
Prison: Same as school.
Custard, ice cream stand: No grease interceptor
required for only ice cream or custard.
Comm
82.34(8)
(11/24/04)
Can the runoff from an area under a fueling canopy be
discharged to the sanitary sewer if the remainder of the site is
discharged to the storm?
Yes, however an oil and flammable liquids separator is required to
serve the discharge from under the canopy.
Comm
82.34(11)
(11/24/04)
Is a variance required for a meat processing plant
discharge to bypass an interceptor if the DNR has issued a WPDES permit
to land spread the waste including the blood and other byproducts?
No. Since the code states the reason for the requirement, i.e.
“to prevent the discharge of feathers, entrails, blood and
other materials” and the waste is not being
“discharged,” but is being collected and land
spread, a variance would not be required in this instance.
Comm
82.35(3)
(7/22/05)
Can
the opening created by removing a water closet serve as a cleanout for
a branch on two floor levels?
Yes, the water closet opening can serve as a cleanout for the branch
until the branch connects with another branch to create a main.
Comm
82.35(3)
(7/22/05)
Are
cleanouts required to serve pump discharge or pressurized sewer piping?
No.
Cleanouts are not required. See 82.35 (1) where the scope of
the
subchapter is “the installation of cleanouts and manholes for
all drain
piping.”
Comm
82.35(3)
11/18/97
A municipality can require sampling manholes.
A municipality can require installation of sampling
manholes. The requirement must be by ordinance. The department is not
required to review the ordinance.
Comm
82.35(3)
6/6/00
Where are cleanouts required on drains and sewers?
Are the risers included in the measurements between
cleanouts on building sewers and drainage piping inside a building? No.
The measurements are taken horizontally between cleanouts.
Comm
82.35(3)
6/6/00
Where are cleanouts required on circuit vented lines?
The attached
drawings show the required installation of cleanouts on circuit vented
lines.
Comm
82.35(3)
6/6/00
When is a manhole a cleanout?
Terminology can be confusing as to when a manhole,
catch basin, area drain inlet, etc can be used as a cleanout. The attached
drawings will help the inspector or plan reviewer evaluate an
installation.
Comm
82.35(3)
7/28/03
Can a roof drain serve as a cleanout?
Yes. A roof drain can serve as a cleanout for
horizontal piping below the floor.
Comm
82.35(3)
6/6/00
Can you use a water closet for a cleanout?
Can a water closet be used as a cleanout at the
junction of the building drain and building sewer? No. The only
cleanout requirement where a removable fixture trap can replace a
cleanout is the "branches" requirement.
Comm
82.35(3)
7/28/03
When are cleanouts required for sewer offsets?
The installation of an 8" or larger sanitary sewer requires
additional
manholes at every change in direction of 45 degrees or more. The
installation of two 1/16 bend fittings with piping between is not
considered to be a change in direction of 45 degrees or more. An
installation of street fittings to create a fitting are to be
considered one fitting. Storm sewers 12 inches or larger in diameter
are required to comply with this requirement. However, storm inlets
with an inside diameter of at least 36 inches can serve the purpose of
a manhole. Private interceptor main sewers 6 inches or larger in
diameter are required to include a manhole at every change of
direction. This change of direction is not specific to any offset
measurement.
Comm
82.35(3)
11/19/02
Is a manhole required for a vertical change of direction?
No. The code's intent is to have the manhole and cleanout
requirements
for sewers and private interceptor main sewers apply to horizontal
changes in direction, not changes in elevation. This applies to the
requirements in 82.35 where cleanouts, manholes or storm inlets are
required for changes in direction of 45 degrees or more and also where
the code requires for a manhole where there is a change of direction.
Comm
82.35(3)(d)
2/6/07
May a cleanout
for a private interceptor
main sewer be located inside one of the buildings?
No,
the cleanout for a private interceptor main sewer is required to be an
“exterior” cleanout.
Comm
82.36(3) and Comm 60.30
8/7/07
What does the
department require for the thickness of
a subsurface stormwater detention system or detention basin liner?
There
are three options that the department deems acceptable for a
subsurfqace stormwater dentention system or detention basin liner:
1. Clay liner
2. High Density Polyethylene Liner (HDPE)
3. Polyethylene Pond Liner (PPL) The
specifications for the liners are here, PDF file.
Comm
82.36(6)(c)
3/1/05
In previous versions of the code, a reduction in size in
the direction of flow was permitted only within a manhole; Does the
code have such a requirement?
Yes. Comm 82.36(6)(c)1 requires that fittings and connections comply
with 82.30 (8) and (9). Paren. 9 only allows any additional obstruction
of flow where permitted by the department. The department will only
allow that reduction in a storm system within a manhole.
Comm
82.36(8)
3/16/04
If a foundation drain and accompanying sump pit are
installed, must the
pump also be installed at that time?
There are two conditions that require the pump to be
installed at the time the foundation drain and sump is installed: 1.
Natural conditions that would create a need for the pump and, 2. A
municipality that requires the installation of a pump at the time of
sump installation. See the Uniform Dwelling Code, Comm 21-25, for
more information.
Comm
82.36(13)
(7/22/05)
What
does a stormwater system operation and maintenance (O&M) plan
look like?
No two O&M plans are identical, as all O&M plans are
specific
to the installation. One typical statement contained in an
O&M plan might be that inlets should be inspected twice a year
and
debris removed. Another might say, no standing water should
be
permitted in the system to prevent mosquito larvae habitat.
Any
defects in the pavement or grass areas that allow standing water for
more than 48 hours will be repaired.
Comm
82.38
6/1/06
Where may decorative
fountain drains and fountain overflow drains
discharge?
Decorative fountain drains may discharge to the storm system.
They may
also discharge to grade where no nuisance is created, and where not
prohibited by local government or the Department of Natural Resources.
Fountains located inside buildings may also discharge to the
sanitary
system if the discharge does not exceed 50 gallons per day.
Comm
82.38
11/19/97
Fixtures discharge to surface or drain subsurface.
Most fixtures and wastewater discharge points are
listed in Table 82.38. Holy water uses are not listed and the
department allows discharge of holy water via piping systems to grade,
subsurface, sanitary systems or storm drains.
Comm
82.38
8/06/03
Where can greenhouse wastewater discharge? Final
decision for discharge to storm or sanitary will
be given by DNR. Interior clearwater piping shall be trapped, vented,
and installed by a licensed individual.
Comm
82.38
11/24/00
Where should a zambonie discharge? Either
storm or sanitary. If ice is to be melted and
discharged through the interceptor, to storm. If the catch basin is to
be used for other purposes, the discharge should be to sanitary.
Comm
82.38(3)
12/23/03
What are the allowable discharge points for a loading
dock? A loading dock is treated as a parking
lot. Enclosed
loading dock discharge points comply with Table 82.38-1 #6. Open
loading dock discharge is considered stormwater and would be discharged
as permitted in Table 82.38-1 #10.
Comm
82.38(3)
12/23/03
What's the definition of "open parking lot"? The
plumbing code is using the building code definition
of "open" for parking lots. Requirements for openings are located in
406.3.3.1 of the Wisconsin
Enrolled Commercial Building Code.
Comm
82.38-1
6/1/04
Row number 8 allows a municipal well pump house floor
drain and sink to discharge to grade, unless prohibited by local
municipality and where no nuisance is created. Would an emergency
shower in this facility and a chlorine storage floor drain in this
facility also be allowed to discharge to grade? Yes.
The fixtures located in this facility that are
listed in this question may also discharge to grade.
Comm
82.38(3) 4/1/08
Where
can the fire test and draindown from a standpipe discharge? Water
discharged during a fire test is considered clear water unless there
are chemical additives and it may discharge as row 10 in Table
82.38-1 allows. This includes a provate oniste wastewater
treatment system that’s designed to receive the discharge,
municipal sanitary sewer, municipal storm sewer, ground surface (unless
prohibited by local and when no nuisance is created) or subsurface
dispersal (which would require plan review and approval for a
commercial building).
Comm
82.40(2)
11/17/97
Can 5/8" PEX carry more than two fixtures? Yes,
as long as the wsfu fits the sizing chart for that
material.
Comm
82.40(3)
02/5/02
Is tempered water required for emergency fixtures?
Tempered water to emergency fixtures is not
required by
the plumbing code. An OSHA consultant may require the installation of
tempered water because the standard for emergency fixtures refers to
tempered water.
Comm
82.40(4)
11/19/97
Requirement for building control valves. See
diagram attached.
There must be one building control valve that is located within 3 feet
from the point where the water service enters the interior building
(either where it penetrates the floor or wall). This means one building
control valve.
Comm 82.40(5) 5/10/07
When are water heaters required to be set
at 125 degrees? Manufacturers are required, by
statute, to be set water heaters at 125 degrees Fahrenheit when they
are sold for individual use in a dwelling unit in Wisconsin.
See 134.81, Stats.
Landlords who rent for
residential tenancy must set the thermostat of the water heater that
serves that individual tenancy at 125 degrees or at the minimum setting
of the water heater. See 704.06, Stats. Water heater
thermostat settings. A landlord of premises which are subject to a
residential tenancy and served by a water heater serving only that
premises shall set the thermostat of that water heater at no higher
than 125 degrees Fahrenheit before any new tenant occupies that
premises or at the minimum setting of that water heater if the minimum
setting is higher than 125 degrees Fahrenheit. There are no
requirements for residential water heater temperatures in the plumbing
code.
Comm
82.40(5)
5/29/06
Can a
T&P relief
valve discharge to a floor that doesn’t have a floor drain?
No, an approved receptor would be required if
there is no floor drain.
Comm 82.40(5)
5/29/06
Does an existing water
heater
replacement require that the installer update the receptor for the
T&P relief valve to current code compliance? No,
not unless a health hazard is created by leaving the existing
installation
Comm
82.40(5)
11/17/97
Required pressure for a T&P relief valve
What pressure rating is required for a
T&P
relief valve? The T&P relief valve pressure rating may not be
higher than the tank working pressure rating.
Comm
82.40(5)
8/06/03
T&P relief discharge in replacement projects
Can the T&P relief discharge through
the floor
in a replacement installation? Replacement may be the same as original
installation. No changes are necessary.
Comm
82.40(5)
8/6/98
T&P valve sizing local waste The
drawings in the appendix illustrate local waste
installations. Plumbing will use the receptor dfu values to size the
local waste.
Comm
82.40(5)
12/11/98
How are drain pans used as T&P valve receptors
installed? Pans placed under water heaters in
case of drips are
not considered plumbing and should not be connected to the plumbing
system. If a water heater T&P relief valve discharges into this
pan, it is now considered a receptor and installed accordingly.
Comm
82.40(5)
5/2/00
Is insulation required for all recirculation systems?
No, not when the recirculation system is used
to heat
the home in emergency situations and is activated by a thermostat or
when the recirculation is not a continuous system, but activated by
demand.
Comm
82.40(7)
11/17/97
Velocity restrictions in mobile home park Can
a water supply system to a mobile home park exceed
8 feet per second? Yes, because the code doesn't restrict velocity in a
supply system except in the water distribution system. (Watch
manufacturer's requirements.)
Comm
82.40(7)
11/19/97
Turf sprinkler in water calculations Is
the demand for the turf sprinkler required to be
included on the water calc worksheet? No.
Comm
82.40(7)
9/1/00
What needs to be added to the demand to size a
multipurpose piping system? On a single family
dwelling, none. On a duplex, 5 gpm
to the service. The calculations are performed per NFPA 13D and per
Comm 82.40 (7). Whichever causes the larger piping system is the
controlling water sizing.
Comm
82.40(7)
9/1/00
What gpm are required for emergency fixtures? Unless
further information is provided by the designer
of the system, the following gpm rates may be applied to sizing
calculations: Eye wash - .4 gpm, Face wash - 3 gpm; Drench hose - 3
gpm; Drench shower - 20 gpm.
Comm
82.40(7)
4/4/01
Tempered water and water supply fixture units. What
are the water supply fixture units that can be
calculated when designing a water distribution system using tempering
valves? The total water supply fixture units for a fixture are used in
the calculations downstream and upstream of the tempering valve.
Comm
82.40(7)
1/2/03
What pressure is required for emergency fixtures?
An emergency fixture requires 30 psig. This
minimum
pressure is used in the water calculation worksheet if an emergency
fixture is included in the water distribution system.
Comm
82.40(7)
1/2/03
What flow is required for combination emergency fixtures?
The demand for each of the units in a combination emergency
fixture
unit must be combined in the water sizing for a distribution system
that includes combination emergency fixtures, such as combination eye
wash and emergency shower. For example, the eye wash demand is .4 gpm
and the shower demand is 20 gpm so the combination fixture has a demand
of 20.4 gpm.
Comm
82.40(7)
2/5/02
How many emergency fixtures must be included in the water
sizing? If there are multiple emergency
fixtures located in
building or facility, the designer and owner must make the decision as
to how many emergency fixtures could be used simultaneously. The water
sizing should be completed based on that decision. The plumbing review
would include at least one emergency fixture included in the gpm demand
of the system.
Comm
82.40(7)
2/5/02
May fire residual pressure be used for water system
sizing? No The plumbing code requires that
the minimum
pressure in the street be used for water distribution sizing
calculations. In most cases, a municipality will provide a static
pressure and a normal residual operating pressure. The normal residual
pressure is the pressure that is appropriate to use in the water
distribution sizing.
Comm
82.40(8)
- 11/17/97
Internal bypass valve application Can
an integral bypass serve a softener or iron filter?
Most of the time. The filter or softener must be able to be removed for
service and the valve remaining on the system.
Comm
82.40(8)
- 4/20/98
When does a replacement wall hydrant need to meet code?
When replacing a hose bibb, it's only
necessary to
bring the replacement to the requirements in Comm 82.40(8)(a), when
you're cutting the pipe or disconnecting the hydrant inside the
building. Cross connection control is required to be applied to the
hose connection.
Comm 82.40(8)(e)2 - 4/1/08
Is there anywhere in the plumbing system
where a stop and waste-type control valve may be installed underground?
There
is no definition for a control valve in the code or statute, so the
interpretation of where a stop and waste-type control valve may be
installed is based on the probability of incidence and the historical
precedence of the plumbing trade. One installation of
below-ground bleed type devices has been for fire hydrants which are
emergency fixtures and have less of a probability of groundwater impact
or serving as a drinking water source for the public.
Similarly, a large diameter hydrant (2" or greater outlet) that serves
a wastewater treatment plant on the protected non-potable distribution
piping has the same low probability for serving as a public drinking
water source or increasing the risk of contamination near the
wastewater treatment plant.
Comm
82.41
- 5/10/07
Backflow
protection for pressure washers (without break tanks including air
gaps) Pressure
washers may be hard piped or connected with a garden hose to the water
supply system. ALL pressure washers installed permanently
must be connected to the water distribution system with approved water
distribution materials (see chapter 84.30). Following
is an explanation of the minimum acceptable backflow
protection. Portable Pressure Washer - Hose connection vacuum
breaker or backflow preventer (ASSE 1011 or 1052) connected to hose
bibb serving washer. (Non-continuous use, not permanently connected to
the water supply). Permanently installed pressure
washer - RP (ASSE 1013) installed in water supply.
Comm
82.41 May 10, 2007
Booster
Pumps and backflow protection Booster pumps are
generally hard piped to the water supply and then use a hose at the
outlet end of the pump. ALL booster pumps installed
permanently must be connected to the water distribution system with
approved water distribution materials (see chapter 84.30).
Booster pumps must be provided with an automatic low pressure cut-off
switch to protect the booster pump in the case of loss of supply
pressure when the booster pump is serving plumbing fixtures, appliances
or pieces of equipment. All booster pump installations must
take into account the pump’s affect on the plumbing water
distribution system. Following are acceptable backflow
protection options for booster pump installations: Inlet side
of booster pump (continuous use) - RP (ASSE 1013)
installed in water supply. Outlet side of booster
pump - > 150 to 350 psig. RP (ASSE 1013) installed in
the water distribution system downstream of the pump. In this
case the pump materials in contact with the water must be water
distribution approved materials. - > 350 psig There
are no backflow preventers manufactured to withstand these pressures at
this time.
Comm
82.41
9/18/03
What are the cross connection
protection requirements for
chemical dispensing systems for janitorial use?
See attached article (PDF
file) Comm 82.41
9/26/03
Are there requirements for installing the
"Strahman" steam/water mixing valves? Yes,
see this memo for more information, PDF file,
Word 97
file.
Comm 82.41(3) 4/1/08
What are the cross connection control
requirements for an emergency eye wash located on a hose? If
the emergency eye wash can be submerged in a sink, a low hazard cross
connection control device would be required to serve the eye
wash. This determination is based on the probability of
incidence. If the emergency eye wash is located where it is
not likely to be submerged in wastewater (stand alone system) then no
cross connection control device is required.
Comm
82.41(3)
(11/24/04)
When does cross connection control need to be modified to
be code compliant when remodeling or repairing a plumbing system?
If the piping system is being cut to remove or
repair the backflow
prevention device or assembly the cross connection control must be made
code compliant to the code in effect at the time of the repair. If a
union is installed that would allow removal of the device or assembly
without cutting the piping system, the existing device or assembly may
be returned to service.
Comm
82.41(3)
3/2/99
How is CCC installed on a carbonator? See
the attached
illustration for one type. See part two for another situation.
Comm
82.41(3)
5/2/00
Can a chiller water supply also serve fire protection?
Yes. However, backflow protection must be
installed to
serve the degree of hazard that is caused by the installation, as
always.
Comm
82.41(3)
8/1/00
Can a whirlpool and a pool be served by a single rp
valve? No. Each pool, wading pool or whirlpool
must be served
by separate reduced pressure backflow prevention valves or air gaps. A
pool may be filled by a hydrant that has a hose connection backflow
preventer attached.
Comm
82.41(3)
8/06/03
What backflow protection is required on a dental mold
grinder? The dental mold grinder requires
either an internal air
gap in the device or a device that provides protection in accordance
with Comm Tables 82.41-1 and 82.41.2.
Comm
82.41(3)
5/15/01
Do all fixtures in a mortuary need separate cross
connection control? Yes. The Department of
Regulation and Licensing
requires that all fixtures be installed in mortuaries with individual
cross connection control. Examples could be embalming machines and
aspirators.
Comm
82.41(3)
10/19/0
Can a city require additional cross connection control?
Is it in compliance with Chapter 145, stats., if a city adopts an
ordinance that requires containment in buildings other than those
described in Comm 82.41(3) (c), Wis. Adm. Code (sewerage treatment
facilities or marinas, wharves and docks)?
No. At this time there are no provisions in the code or statutes that
would permit local ordinances that supercede the uniform plumbing code
requirements for containment. Section 145.02 (2) states that "The
department shall have general supervision of all such plumbing and
shall after public hearing prescribe, publish and enforce reasonable
standards therefore which shall be uniform and of statewide concern so
far as practicable." The definition of "practicable" is "capable of
being effected, done or executed; feasible." In several cases the
plumbing code has specific allowances for cities to adopt ordinances or
enforce requirements in excess of the plumbing code. Comm 82.41(3) has
no such permission.
Comm
82.41(3)
5/2/00
Variance permitted monitoring water supply in lieu of CCC.
Petition for variance attached. Conditions noted on sample letter.
Comm
82.41(3)
8/8/01
Can a fire truck fill be located in a fire protection
system? Yes. A fire truck fill in a fire
department may be
located in a fire protection system. This decision was made by the fire
protection program. The backflow protection assigned to the sprinkler
system will be considered adequate for the fire truck fill.
Comm
82.41(3)
1/2/03
Is a non-reservoir type hydrant permitted? Yes,
for existing installations. Hydrants will not be
required to be removed if the water supply to the hydrant is protected
with a cross connection control device such as an ASSE 1012 and a hose
connection vacuum breaker. New installations require the installation
of a reservoir type hydrant.
Comm
82.41(3 ) 1/2/03
Does a pipe that travels through a fountain require a CCC
device? A water supply that travels through a
contaminated area
is not automatically required to have a cross connection control device
installed to serve that distribution line, if the termination of the
water supply is above the flood level rim of the fountain and if the
water distribution material is resistant to corrosion. See Comm
84.30(4).
Comm
82.41(3)(c)
2/25/04
Is it code-compliant for one cross connection control
device or assembly to serve multiple humidifiers?
No. However, an air gap within a humidifier may provide
adequate
backflow protection.
Comm
82.41(4)(a)
6/1/06
May a small diameter tube
from a chemical dispenser be inserted into a flush valve tube so as
that the end of the small tube would be the highest point of injection
or aspiration? No. The point of penetration into
the flush valve tube is considered
the point of aspiration.
Comm
82.41(4)
(7/22/05)
At
what level must a pipe applied atmospheric vacuum breaker be installed
when an aspiration device is located downstream of the vacuum breaker?
The pipe applied atmospheric vacuum breaker must
be installed so that
the critical level indicator is at least 6 inches above the connection
of the aspiration or injection device.
Comm
82.41(4)
10/23/98
Atmospheric vacuum breakers above urinals. The
atmospheric vacuum breaker is required to be
installed on water distribution serving urinals.
The minimum height of the atmospheric vacuum breaker is 6 inches above
the flood level rim of the urinal bowl (for wall mount) and the floor
level (for stall type).
Comm
82.41(5)(h)
2/25/04
What kind of "wild head" is permitted downstream of an
atmospheric vacuum breaker serving a turf sprinkler system? The
wild head must be sold as a turf sprinkler or a hole
may be drilled in a pipe to serve as a wild head when the orifice is as
large as a turf sprinkler orifice. The sprinkler may not include an
automatic shut off. Comm
82.50
6/1/04
Are
there other requirements for laboratories? Yes,
there are other requirements for laboratories. See
the Center for Disease Control (CDC) website for more information. http://www.cdc.gov/od/ohs/pdffiles/4th%20BMBL.pdf
The document is 265 pages long.
Comm 82.50(2)
7/10/2006
May psychiatric units have
faucets
installed that are equipped with spouts and actions other than those
listed in the code section or Table 82.50-1? Yes,
there are other options for environmental suicide prevention
approved via the attached
alternate approval.
Comm
82.50(3)
11/14/03
Article in
WCCR concerning hot water distribution systems in health
care.
Comm
82.50(12)
11/19/02
Is a 5-inch spout height required for public lavatories?
No. The public restroom may have standard
lavatory
faucets. Only those faucets listed in Table 82.50-1 that require the
gooseneck spouts must have the 5-inch clearance.
Comm
82.60(2)
4/26/02
What are the requirements for no-hub hangers? No-hub
pipe needs to be supported within 24 inches on
each side of a joint unless there's an alignment retaining shield. An
alignment retaining shield includes a no-hub coupling. Otherwise, cast
iron pipe needs to be supported every length of pipe, horizontally, and
every 15 feet vertically. As of 3/4/02, the Tyler Pipe company requires
that their pipe be installed with supports as required in the CISPI
standard. See attached letter.
Comm
82.70(3)
2/25/04
Does a laundry reuse plumbing treatment system need to
comply with Table 82.70? Yes, the recycled
water serving the laundry must comply
with Table 82.70. This does not apply to residential suds savers, as a
suds saver is not a plumbing treatment system.
Comm
84.10(1)
10/4/05
May
air admittance valves be installed to serve chemical waste systems?
No. If
chemical
resistant piping is installed to
serve a fixture, an air admittance valve is not permitted as a vent
termination.
Comm 84.10(2) 4/1/08
How would a health care treatment device
that includes a reuse system be classified for the purposes of product
or plan review requirements? Devices or systems
that incorporate hydrotherapy for health care and a water reuse system
are classified as health care plumbing appliances. All health
care plumbing appliances are required to be submitted for product
approval as listed in Table 84.10.
Comm 84.11
7/2/07
Do
all chemical dispensing systems require to be listed by an acceptable
listing agency as meeting ASSE Standard 1055 or receive a written
product approval from Dept. of Commerce? No.
There are currently three ways to determine if a specific chemical
dispensing system can be installed in Wisconsin. 1) It meets
ASSE Standard 1055(1) 2) It has received written alternate
product approval from the department, or 3) It has received
written alternate system approval from the department. Note
(1) ASSE Standard 1055 only applies to those devices
classified
as chemical dispensing systems having self-contained means of backflow
protection.
Since there are many chemical dispensing
systems that
do not have a self-contained means of backflow protection, the
department decided to require that type of chemical dispensing system
to receive an alternate plumbing product approval in accordance with
Comm. 84.11 and Comm. Table 82.41-2.
The
Department has
issued an Alternate Plumbing System Approval regarding chemical
dispensing systems that are not covered by ASSE Standard 1055.
The
alternate approval includes the following stipulations that must be
followed.
Stipulation
#1 – Chemical dispensing systems that are not in compliant
with
ASSE Standard 1055, may be installed when the installation includes an
acceptable cross connection method or assembly in accordance with Comm.
82.41 (3) Table 82.41-1 of the Wisconsin Administrative Code.
Stipulation
#2 - The installation of the cross connection method or assembly must
comply with s. Comm. 82.41 (5) of the Wisconsin Administrative Code.
Comm
84.30(4)
11/18/97
A municipality can dictate materials upstream of the lot
line. The requirement must be by ordinance.
The department
must review the ordinance.
Comm
84.30(4)
6/6/00
Is piping in a marina water distribution or service?
The materials downstream of an reduced
pressure
backflow prevention valve are water service materials. The velocity
would not be required to be maintained at 8 fps. Where the installation
is downstream of a building control valve, the code requires the water
distribution
Comm
84.30(4)
8/8/00
Do pipe repair kits need product approval? No.
See attached
letter on the requirements they must meet.
Comm
84.30(4)(e)310/4/05
May a lavatory be served
by a
distribution system of materials listed in Table 84.30-11? No,
not unless the
materials are listed in 84.30-8 or have received an alternate
approval. <>84.20 (3) (a) 2 allows lavatory
faucets to
discharge
up to three
g.p.m., and materials listed in Table 84.30-11 are restricted to
fixture
outlets of one g.p.m. or less.
Comm
84.30(5)
6/9/99
When can you use pipe saddles? See
attached
document.
Comm
84.30(5)(d)
5/10/05
How does one get approval for using pipe saddles
for other uses then those specified in Comm 84.30(5)(d)? When
an installation is proposed for using pipe saddles for above
ground drain or vent pipe and tubing, the following conditions must be
met: Pipe saddles shall be installed in accordance with the
instructions of the saddle manufacturer. A saddle for drain piping
shall have a radius in accordance with Comm 82.30(8)(a). The material
of the saddle shall be compatible with the materials of the pipes that
are to be connected to the saddle. The hole in the pipe, which is to
receive the saddle, shall be drilled or cored to match the saddle
outlet. The manufacturer of the saddle shall provide straps or clamps,
which wrap around the pipe and saddle. Proper hangers or bedding shall
be provided to maintain alignment between the opening in the pipe and
the saddle. A saddle used in a pressurized piping system shall meet the
applicable code requirements for temperature and pressure ratings. This
determination is considered department approval.
Links
--
County
Web sites ||
City/Town/Village Web sites || State Portal ||
Licensing and Permitting || Build Your
Business
Email
this page's manager, Todd Taylor, ttaylor@commerce.state.wi.us
or 608-267-3606
The Department of
Commerce Safety
and Buildings Division is
an equal opportunity service provider and employer. If you need
assistance to access services or need material in an alternate format,
please contact us, 608-266-3151, TTY 608-264-8777, or ttaylor@commerce.state.wi.us
|