|
|
Safety and Buildings Division Comm 14 Code Advisory Committee Meeting Summaries Meeting summaries are subject to review at a subsequent meeting Tuesday, May 19, 2009, 9 a.m. to 2:30 p.m., Tommy G. Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, WI Council member attendance: John Ashley - Present; Gregg Cleveland, Chair, Present; Tod Doebler - Present; Marty King - Present; John Periard - Absent; and Jim Stormer (Todd Blaser, Alternate) - Excused. Department of Commerce staff: Bob DuPont, Joe Hertel, Greg Jones, Terry Nolen and Sam Rockweiler
Guests: Matthew Mertens, North Shore Fire Department, and Russ Saunders, National Fire Protection Association Gregg Cleveland opened the meeting with a round of introductions, and the Council accepted the
Department update
Bob noted that under the statewide smoking ban that was enacted on
May 18, the Department may need to develop new rules for No Smoking
signs.
Registration of construction projects and fire sprinkler inspections
- Bob explained that the Department’s contractor-registration program
has become popular, and has generated interest in likewise requiring
individual construction projects to be registered with the Department.
Registering the projects could contribute toward developing a more
robust statewide inspection program, such as for energy conservation. Bob noted the Department tracks the required periodic inspections for about 98% of the elevators and boilers in the State, because those appliances can become unsafe – and tracks the required periodic inspections of cross-connection-prevention valves in water distribution systems, because those valves provide protection from potentially unsafe conditions. However, although annual inspections are required for automatic fire sprinkler systems that likewise provide protection from potentially unsafe conditions, those inspections currently are not tracked, but could be, beginning with registering the inspections during construction. Gregg asked whether the registration would include a fee, and Bob
indicated there could be an annual filing fee. Marty King commented
that providing the information to the Department could be beneficial,
but some complaints could arise from the building owners who would have
to report the information. There was interest in determining the
reaction of sprinkler contractors to the concept. Gregg noted the
requirement could be a disincentive to provide sprinklers, but the
gathered data could have educational value. According to Bob, the data
could increase belief in the reliability of sprinkler systems. Gregg
noted the data could have other benefits, such as for the water-use
fees administered by the Public Service Commission – and for the
sprinkler-system tracking that is required at some local levels, which
out-of-state testing companies sometimes do not comply with. Marty
noted the database could also track deficiencies, and Bob said the
Department’s response if a required inspection does not occur could be
to send either a notice to the owner or an inspector to the site. Marty
suggested requiring inspectors to attach an inspection tag to the
sprinkler riser, and suggested enabling local governmental units to
search and download information from the database. Gregg asked whether
the required periodic testing of fire alarms could be tracked as well,
but Marty noted the alarm installers and testers are not registered, as
sprinkler installers and testers are. Gregg suggested surveying fire departments to determine how many fire sprinkler systems currently exist. Greg Jones noted the Department has data showing which newer buildings have sprinkler systems, and Bob said that data shows about 18,000 buildings have been built since 1997 with sprinklers. Tod Doebler noted additional buildings may have been built since then with sprinklers that have been required only by local ordinances. Matthew Mertens indicated the tracking could be helpful because little tracking occurs locally, and turnover of local fire inspection staff is frequent. Matthew asked what the Department would do with the data, and Bob explained the primary response would be to follow up on deficiencies. Joe Hertel added that fire sprinkler testers could query the database for missing inspections. It was noted that in many cases sprinklers are not maintained in vacant buildings. Matthew noted the fire sprinkler tester often is also the tester of the cross-connection-prevention valves. Craig Hubbell noted concern that fee payers would subsidize any
violators, and suggested minimizing the fee along with fining the
violators. Joe noted the Department does not have citation authority,
but Bob explained that late fees could be assessed. Terry Nolen
explained that Department staff also have authority to issue stop-use
orders. Tod suggested annually notifying the owner of the need for the
inspection, as occurs with annual renewal of permits for underground
storage tanks. Gregg asked whether a portion of the fee should be sent
to the local level, and Marty and Craig preferred to not do so and to
instead keep the fee low. Gregg suggested obtaining input from the sprinkler industry, and avoiding actions that would increase opposition to sprinklers. Russ Saunders reported that several states are considering proposed legislation for restricting requirements to install sprinklers. Some of that legislation is gaining support, and some of it is being defeated.
Fire-incident reporting - In reference to the
proposed rule changes for fire-incident reporting that were sent to the
Council in advance of the meeting, Bob explained that the legislative
intent was likely not met by the preceding draft text which defined the
Department, as referenced in section 101.141 (3) of the Statutes, as
being the fire chief. Bob explained that the legislative intent for
statutorily authorizing corrections to fire-incident reports was
directed at the Department rather than fire chiefs. Gregg opposed the
newly proposed text that would require the Department to only involve
the fire chief when making changes to a fire department’s report,
because the Department could then make changes that the fire chief
disagreed with. Gregg noted the on-line National Fire Incident
Reporting System (NFIRS) that is to be used for filing the reports has
an audit feature which screens out the errors the Department has
previously corrected on paper-based reports. Joe and Terry agreed the
statutory reference to correcting the reports is largely an outdated
throw back to those previous corrections. Sam suggested revising the
proposed text to require the Department to obtain consent from the
chief of a fire department prior to correcting or updating a NFIRS
report from that department.
A motion was made by Craig Hubbell, seconded by Marty King, and
passed unanimously to require the Department to obtain consent from the
chief of a fire department prior to correcting or updating a
fire-incident report from that department under section 101.141 of the
Statutes.
Gregg asked whether private fire departments that contract with a municipality are subject to the reporting requirements in section 101.141 of the Statutes, and asked what role mutual-aid fire departments have for reporting a fire they respond to. Terry noted the NFIRS reports are designed for any type of fire department that responds to a fire. Bob explained the Department has authority under chapter 227 of the Statutes to require reports from private fire departments, and to allow mutual-aid fire departments to file the reports. There was agreement to revise the draft rules to more clearly convey this requirement and allowance.
Proposed Q&As
Community-based residential facilities - Sam
explained that the proposed Q&A for community-based residential
facilities which was sent to the Council in advance of the meeting
addresses a requirement by the Department of Health Services that
became effective on April 1, 2009, to have annual fire prevention
inspections. The Q&A clarifies that the fire inspections conducted
under Comm 14 typically will satisfy the DHS requirement. It was noted
that the Q&A refers to a CBRF as serving 5 or more adult-care
residents, which is consistent with the corresponding Statutes, rather
than 9 or more as was referenced in previous codes. The Council
accepted the Q&A as proposed.
Child day-care facilities - Sam explained that the
proposed Q&A for child-care facilities which was sent to the
Council in advance of the meeting clarifies that fire prevention
inspections are required for a public or private day-care center for 8
or fewer children which is not in a one- or two-family dwelling. The
Council accepted the Q&A as proposed.
Design and construction - Sam explained that the
proposed, revised Q&A for design and construction which was sent to
the Council in advance of the meeting included a hotel-construction
example that was intended to illustrate some of the NFPA®
1 requirements which are considered to be design and construction
requirements and therefore do not apply in Wisconsin. Sam noted that
additional examples could be added as they become available. Gregg recommended redrafting the Q&A to focus it more on the NFPA 1 requirements that address the design of a building and therefore do not apply in Wisconsin. With that focus, the example would not need to exclude the building-component requirements in NFPA 1 which address fire prevention during construction, such as temporary wiring, fire sprinkler protection and building-separation walls. Russ Saunders commented that in some other states it is common to look at the requirements in both NFPA 1 and the International Building Code® during plan review, and refocusing the Q&A more on the design of the building rather than the act of construction could be helpful. Russ noted that some states have statutes or reciprocal agreements that address the authority, procedures and roles of the building and fire inspection programs. There was agreement the Q&A should be redrafted as Gregg recommended.
Unresolved issues from fire departments
General - Sam distributed a table of unresolved fire department issues that Terry developed and then updated to reflect the discussions at the March 17 Council meeting. The update included adding yellow shading to identify the issues that may be resolvable only through changes in either Comm 14 or in other Comm codes, such as Comm 60 to 66; however, some of the cells in the table that are entirely shaded may be partially resolvable without code changes. The update also included adding three new columns to designate the code-change issues, the issues that may be resolvable through a Q&A, and issues that may be resolvable through Council consensus and documentation in progress reports. Gregg cited discussions he has had with counterparts in other sates,
which concluded that each issue should be addressed either in the
building code or in the fire prevention code, but not in both. As an
example, it was noted that requirements for tents should not be applied
from both codes. Gregg also noted that when defining terms, they should
not be mixed between both codes – and where there is conflict, the most
stringent rule should apply. Terry noted that having fire service personnel submit future issues on a code-change proposal form through the Department’s Web site could be helpful by documenting the background of the issue. As an example, Terry referenced the Council’s conclusion at the previous meeting to retain the current local flexibility for addressing abandoned buildings under section 66.0413 of the Statutes, rather than recommend a corresponding code change – but further follow-up research on the issue indicates the background is that many small fire departments do not have enough municipal resources or support to adequately address those buildings under the current code text. Those departments want the preceding Comm 14 text restored for dealing with dilapidated buildings.
Flammable and combustible liquids and gases - In
reference to the entries on page 8 of the table relating to chapters
Comm 10 and 40, Terry indicated there is interest in expanding the
scope and application of Comm 14 to have it match the generally broader
scope and application of the respective statutory authority. Bob
explained that the overriding, enabling chapter 101 of the Statutes has
a long history of applying primarily to public buildings and places of
employment, and was relatively recently expanded to also apply to one-
and two-family dwellings. Joe noted NFPA 1 sections 63.6 and 63.7
simply reference NFPA 55 for gaseous and liquefied hydrogen systems,
and asked whether Comm 40 needs revision to be consistent with that
reference. There was interest in considering whether Comm 40 could be
replaced by corresponding requirements in NFPA 1 and Comm 14. Bob
suggested considering that change and having the Comm 40 Council report
to the Comm 14 Council during the next code-update cycle, in 2012. If
Comm 40 is eventually replaced by requirements in Comm 14 and NFPA 1,
the scope of Comm 14 could be expanded to extend beyond public
buildings and places of employment, for the topic areas currently
addressed in Comm 40. Bob noted that during the current update of Comm
14 and Comm 60 to 66, there may be an option to simultaneously update
Comm 40 – as Comm 7 and 9 were updated during the previous update of
Comm 14 and Comm 60 to 66, for fireworks and explosives. Terry noted
that in 2001 one of the objectives of adopting a model building code
and a model fire code was to enable repealing some of the existing
Department codes. The rationale was that adopting NFPA 1 would allow
updating these included requirements in unison on a regular basis – and
the NFPA requirements are at least equivalent to, and in many cases
more detailed than, the fire safety requirements contained in the
current editions of the corresponding Wisconsin Administrative Code
chapters. Bob agreed to report back to the Council at its next meeting,
on the feasibility of simultaneously updating Comm 40.
Referenced standards - In reference to the entries
on page 8 of the table relating to referenced standards, Terry noted
the background on the issue is some staff are concluding that Comm
14.01 (2) (a) 3. and NFPA 1:1.3.2.2 are in conflict with each other,
and that the building and fire codes and some local ordinances are
applying them differently. The Council saw no conflict between the two
rules. Marty commented that the topic should be addressed in more
detail through training, which could include discussion of using
manufacturer recommendations where the code is silent. The Council
agreed that neither a code change nor a Q&A is currently needed for
the topic.
Inspection frequency - In reference to the entries
on page 9 of the table relating to inspection frequencies, Terry noted
the background of the issue is whether the list of uses that can be
inspected once per year instead of twice should be expanded, such as by
providing latitude to make case-by-case exceptions for the example uses
listed on page 9. Gregg noted reluctance to expand the list other than
for case-by-case exceptions, and explained that some events should be
inspected each time they occur. The Council agreed that the current
rule text in section Comm 14.01 (11) (b) 4. that directs fire chiefs in
first class cities on how to establish their inspection frequency could
likewise be applied to fire chiefs elsewhere who are responsible for
the fire inspections of the uses listed on page 9 – which include
seasonal occupancies; temporary-occupancy uses, such as farm structures
temporarily used for winter storage, horse stables or riding arenas;
home-occupation accessory buildings used as businesses; seldom or
infrequently occupied buildings; and unoccupied buildings. It was noted
that a code change would be needed for applying this criteria beyond
first class cities. Terry noted concerns with auditing under this
concept if the fire chief does not declare the inspection frequency and
corresponding buildings in advance, or have a list of buildings to be
inspected and their inspection frequency. Terry noted the other background of the inspection frequency issue is whether providing extra public fire education services should be given a percentage credit to allow performing fewer than the required number of fire inspections, as was permitted in 1988. The Council agreed it should not, and Gregg noted this conclusion should be emphasized in training. Sam noted Comm 14 defines substantial compliance as meaning “an ample amount of the required activity was performed through a concerted effort aimed at total compliance.” Gregg stated, as a member of the subcommittee that developed the definition of “substantial compliance,” that the subcommittee’s intent was to apply the term to all the required 2% eligibility elements as a whole, rather than individually to each element. Terry indicated that applying substantial compliance to all the 2% eligibility elements “as a whole” is completely different than applying it to each of the eligibility elements separately, as was initially presented to the fire service and is currently being applied by each fire prevention coordinator. Terry noted that under the “as a whole” concept, a fire department could do everything but fire inspections, and still pass the audit. Craig asked whether the Coordinators are each addressing the topic in the same manner. Bob agreed they should be and suggested that a corresponding Q&A could be developed which could emphasize the “effort” aspect from the definition of substantial compliance. Next meeting The next meeting was generally scheduled for late July to early
August, to coincide with reviewing the outcome of the public hearing
for updating Comm 14 to be consistent with recent statutory changes for
fire-incident reporting and mobile kitchens. Tuesday, March 17, 2009, 9 a.m. to 2:30 p.m., Tommy G. Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, WI Council member attendance: John Ashley - Present; Gregg Cleveland – Chair - Present; Tod Doebler - Present; Marty King - Present; John Periard - Absent; and Jim Stormer (Todd Blaser, Alternate) - Present. Department of Commerce staff: Bob DuPont, Joe Hertel, Terry Nolen and Sam Rockweiler Guests: Matthew Mertens, North Shore Fire Department Gregg Cleveland opened the meeting with a review of the draft progress report for the preceding, February 25, 2009, Council meeting. Todd Blaser noted the member attendance should show he was present instead of absent, and the Council accepted the progress report as so revised.Q&As for adult-care and child-care facilities Adult care facilities - Sam Rockweiler explained that the draft Q&A for adult-care facilities which was sent to the Council in advance of the meeting essentially consisted of the draft table the Council discussed at the previous meeting, for summarizing how fire inspectors should apply the Department’s construction and fire prevention codes to adult care in one- or two-family dwellings, in adult family homes, and in community-based residential facilities – for both converted and non-converted buildings. Posting the table as a Q&A on the Department’s Web site, and distributing a notice of it through the Safety and Buildings Division LISTSERV® should then result in distributing the notice through Gregg’s LISTSERV e-mail list for fire chiefs and Tod Doebler’s LISTSERV list for fire inspectors. Terry Nolen asked whether the column headings of Non-Converted Building and Converted Building should instead read New Building and Existing Building, and Marty King and Gregg preferred referring to whether the buildings are converted, in combination with the corresponding footnotes. Gregg emphasized that with the adoption in 2002 of NFPA® 1 and the International Code Council® codes, fire inspectors need to think more thoroughly about their work, and they need better training for it, which the Q&A should be helpful with. It was noted that only about 10% of fire department inspection personnel attend continuing education sponsored by the Department, because the attendance is currently not a code requirement. The Council agreed the Q&A should be posted as drafted. Child care facilities - Sam explained that the draft Q&A for child-care facilities which was sent to the Council in advance of the meeting primarily consisted of the summary of input from the Department of Children and Families (DCF) that the Council discussed at the previous meeting, for resolving questions and concerns about fire department inspections for child-care facilities. Sam and Terry explained that in developing the Q&A, they reviewed documentation from 1989 which addressed (1) Department-level plans then for changing the statutory definitions of public building and places of employment to exclude day care centers for 8 or fewer children, and (2) a Department-level Memorandum of Understanding indicating the Department would not apply the commercial building code to those facilities. However, that statutory change did not occur, and consequently the current commercial building code and fire prevention code do apply to any day care center for 8 or fewer children which is not in a one- or two-family dwelling. Marty commented that the Memorandum of Understanding apparently was inconsistent with the Statutes, and Marty and Gregg agreed the statutory definition should not be changed now, as was planned in 1989. There was agreement to inform DCF and Jim Smith of this outcome, and Bob DuPont agreed to do so. Terry suggested emphasizing in the Q&A that fire inspections are exempted only where the child-care facility is in a one- or two-family dwelling. Matthew Mertens suggested noting in the Q&A that a foster home is allowed to have up to six children if they are siblings. The Council agreed that the Q&A should be posted now – and that another Q&A or other clarification should be developed for day care centers which are not in a one- or two-family dwelling and which are for 8 or fewer children. It was noted that licenses for foster-care facilities may change to address temporary-capacity numbers. Department update Budget bill - Gregg asked Bob to explain a proposal in the State’s biennial budget bill that would transfer money to the State’s general fund, from the two-percent fire dues appropriation. Bob indicated the Department of Administration notified the Department of this intended transfer after the Council’s previous meeting. Bob added that the budget bill may be written to include the term “notwithstanding” in order to override the text in section 20.143 (3) (La) of the Statutes which authorizes the Department to apply this appropriation only to administrative expenses, which the Department has defined in section Comm 14.03 (1) (a). Bob also noted the Department may be able to avoid cutting expenditures across-the-board, and thereby avoid substantial reductions in the fire prevention program. He agreed to look further into the two-percent transfer and the across-the-board reductions. Existing buildings - Gregg noted there is uncertainty about where to obtain antecedent building code requirements that may still apply to buildings constructed years ago, such as for a school built in the 1950’s with asbestos that now must be removed. Bob said that although the Department has an archive of all previous versions of the building codes, those versions are not posted on-line, like the current codes. However, the building owner is still responsible for complying with them. Gregg emphasized a need to do more for these building owners, and agreed with Marty that the two-percent dues funds should not be used for posting the archives on-line because that should be a building code activity rather than a fire prevention code activity. Bob noted Department staff are available to assist with individual projects for these buildings, but the design responsibility rests with the building owner. Terry commented that in the past, the Department had provided a five-volume set of the archived codes to fire departments for $200. Bob agreed to look into whether scanning and posting online the previous five-volume set, which extended from 1914 to about 1980, would be practical. It was noted that having online access to archived codes could be beneficial for any involved party, including an owner, designer, architect, or school district. It was noted that the adopted NFPA standards are archived and online through NFPA but at a cost to the consumer. Craig asked whether that effort would resolve Gregg’s concern. Gregg recommended also posting a Q&A that describes the corresponding process, and automating the process so that everyone has access to the information. Bob asked whether the Q&A should address maintenance and change of use, and Gregg said the more situations that are explained, the more helpful the results would be. Terry noted the Q&A could have links to other sources of information. Statewide electrical inspections, and credentials for electrical inspectors - Bob reported that the Department’s rules for statewide electrical inspections and credentials for electrical inspectors are expected to become effective in 2009, and have a deadline in 2013 for obtaining the credentials. Under 2007 Wisconsin Act 63, local governmental units cannot add additional local requirements between the 2009 effective date and the 2013 deadline, and any corresponding local requirements will sunset on the 2013 deadline. Mobile kitchens, and fire-incident reporting - Bob noted that staff are finalizing the public hearing documents for updating Comm 14 to make it consistent with requirements enacted in 2007 Wisconsin Acts 75 and 173 that specify (1) the information that all fire departments must report to the U.S. Fire Administration for all fires which involve buildings, and (2) the maximum size and usage for a mobile kitchen that is allowed to not have an exhaust hood and corresponding automatic fire suppression system. Registration of building contractors - Bob reported that an emergency rule became effective on March 2 that requires registration of various types of building contractors who are not already credentialed by the department under other administrative rules. Bob explained that the registration will help the Department communicate with and educate building contractors throughout the state – and will enhance the Department’s ability to coordinate protections for workers, with other agencies such as the Department of Workforce Development. Self-certification for fire dues - Bob reported that self-certification postcards for the fire dues have been sent to fire chiefs, but the only available clerical staff is on extended medical leave, so there may be some delays in subsequent letters and fire dues payments to local units. Terry asked whether the payments will be reduced by any provisions in the budget bill, and Bob said they would not. Terry asked whether next year’s self-certification is still on-track for being processed through the Internet, and Bob said it is, and that local units will be informed soon that the required form for the certification will be available only through the corresponding Department Web site. It was noted that a demo may be available for the Wisconsin State Fire Chiefs Association conference in June. There may also be a test link demo available online as well. Fire incident reports - Bob reported that one training session for the National Fire Incident Reporting System is planned in each of the Division’s five fire prevention districts, and a video of the training will be available in the summer, as the reporting begins. Marty noted that a US Fire Administration Web site references a NFIRS course for further information, and future federal funding could be linked to being registered through that Web site and participating in a corresponding on-line survey. It was questioned whether NFIRS reporting would automatically roll over to the USFA fire department census information. Surplus computers - Todd Blaser asked whether a previous preliminary proposal to transfer surplus State computers to local governmental units is still an option, and Bob said it is not, because there is no ability to limit State surplus material to a particular group. Unresolved issues from fire departments In reference to the table of unresolved fire department issues that was developed by Terry and sent to the Council in advance of the meeting, Terry explained that (1) a new column was added for indicating which Department codes apply to each issue; (2) the issues were newly grouped into topical areas; and (3) issues which have been resolved through Q&As have been recorded. Sam suggested prioritizing the issues into three categories: (I) issues that are likely to be resolved only through changes in either Comm 14 or in other Comm codes, such as Comm 60 to 66; (II) issues that are likely to be resolved through a Q&A; and (III) issues that may be resolved through Council discussions and documentation in progress reports. The issues in category I could then be addressed first, in order to increase their potential for being adequately addressed before the projected end-of-2009 deadline for developing a public Hearing draft for adopting the 2009 edition of NFPA 1. Reformatting - As an example of the issues in category I, Bob cited the entry on page 4 of the table, under chapter 1, relating to reorganizing the Comm 14 modifications to NFPA 1 – which matches up with a preceding Council agreement to reformat section Comm 14.01 to better fit any corresponding NFPA 1 sections. Definitions - Next up could be addressing additional definitions in Comm 14, as referenced on pages 11 and 12 of the table. Terry noted that the occupancies which are listed in Comm 14.01 (11) (b) 5. a. to s. for once-per-year inspections, and the temporary use which is addressed in Comm 14.01 (2) (f), were carried over from the commercial building code and may have different meanings in NFPA 1 and Comm 14. It was recommended to apply the NFPA 1 definitions to these terms wherever possible. Gregg suggested looking at whether any of the listed occupancies should be renamed to match up with the NFPA 1 definitions, and Terry agreed to do the initial review. Gregg recommended then looking at whether any other terms in Comm 14 should be changed to better match the terminology in NFPA 1. A motion was made by Marty King and seconded by Todd Blaser to make the terminology in Comm 14 consistent with the terminology in NFPA 1, wherever possible, beginning with section Comm 14.01 (11) (b) 5. It was noted that Comm 14.01 (11) (b) 5. m. addresses vacant or unoccupied buildings, and NFPA 1 chapter 10 requires the owner of a vacant building to remove all combustible materials. Marty indicated these buildings are considered abandoned when that owner cannot be readily identified, and abandoned buildings should be treated the same as vacant buildings. However, local governmental units sometimes define “abandoned” differently for different purposes, and those differences will likely continue. It was also noted that “seasonal or periodic occupancies” as addressed in Comm 14.01 (11) (b) 5. s., are expected to be further defined in the rules the Department is currently developing for fire incident reporting under 2007 Wisconsin Act 75. The motion as made by Marty and seconded by Todd passed unanimously. Scope - Terry noted that the entries on pages 4 and 5 of the table relating to scope include reference to Comm 14 generally being limited to public buildings and places of employment, whereas the fire prevention criteria in section 101.14 (1) of the Statutes extend beyond that limit. There was interest in adding an informational Note near the beginning of Comm 14 for describing the fire prevention authority that the Department and fire departments have beyond public buildings and places of employment, which could be similar to the language for this topic in the 1918 Wisconsin Fire Code. In addition, a purpose section could be added that addresses fire prevention inspections beyond public buildings and places of employment, and the current reference in Comm 14.01 (11) (b) 9. to this inspection authority could be moved up to the scope criteria in Comm 14.01 (1). There also was interest in adding rule text for applying NFPA 1 in these inspections, and interest in updating the Comm 14.01 (1) Note and Comm 14.001 (1) text addressing NFPA 1. A motion was made by Todd Blaser, seconded by Marty King and passed unanimously to proceed with addressing the Comm 14 scope as just discussed. Temporary use and temporary buildings - Terry commented that “temporary use” as applied in Comm 14 differs from how it is applied in the commercial building code, both in terms of code language and code application. He cited as an example a non-regulated agricultural building that was converted to a regulated mercantile building for retail sales of Christmas and holiday items. The building is open to the public every year during November and December, and then stores the unsold product the rest of the year. According to Terry, this situation was addressed differently by the commercial building program and the fire prevention program. There was interest in looking at whether the rule text in Comm 14 and the commercial building code should match, and whether to remove the rule text from the commercial building code. Joe Hertel cited a school gym that is used temporarily for a sleepover; and Bob noted a building inspector could be concerned there about ventilation and heating, although the inspector on hand would likely be a fire inspector. It was noted that the building code also has criteria under IBC section 3103 for temporary buildings and structures, which are erected for a period of less than 180 days. The IBC Commentary for IBC section 107 indicates the section 107 provisions are for structures that have a limited service life – and states section 107 should not be confused with the scope of IBC section 3103, which regulates temporary structures larger than 120 square feet in area. Section 3103 indicates that “temporary” refers to the structure being erected, not the use of the structure. If a structure is erected for 365 days a year, but is used on a seasonal basis for less than 180 days, section 3103 does not apply, because such structures are considered permanent. Joe cited a tent that is used temporarily to house a popcorn cooker, which can be allowed under some circumstances, through the discretion of the authority having jurisdiction – although some fire departments may not be aware that they have such discretion, and some local ordinances may preclude such uses by being more restrictive than Comm 14 and NFPA 1. Purpose - For the “purpose” entry on page 6 of the table, Terry asked whether NFPA section 1.2 should be modified to specifically reference protecting firefighters, as is referenced in section 101.01 (13) of the Statutes and NFPA Appendix section A.1.2, and as was referenced in previous versions of Comm 14. Gregg and Tod advised not making the modification. Retroactivity - For the “retroactivity concerns” on page 6, Terry noted that under Comm 14.01 (2) (a), Comm 14 applies retroactively to all existing buildings except where stated otherwise – whereas NFPA 1 and its referenced standards apply retroactively only where the risks warrant it, as referenced in sections 1.3.2.4, 1.3.6 and 10.3.2. Craig commented that the NFPA 1 retroactivity makes sense, compared to the expense of changing an existing building when new code requirements become effective. Gregg commented that such expense is typically related to design and construction requirements, and all of those requirements in NFPA 1 are excluded from Comm 14. Bob noted concern that changing Comm 14 to match the NFPA 1 text would result in previous versions of NFPA 1 applying to buildings that existed under those versions, which could cause difficulties with using grills on decks and artwork on school walls. Gregg recommended applying NFPA 1 wherever possible, but keeping the Comm 14 retroactivity text because the design and construction requirements in NFPA 1 do not apply. Bob agreed to look at whether further clarification of NFPA 1 sections 1.3.1, 1.3.2.4 and 10.3.2. would be helpful in conjunction with keeping the Comm 14 retroactivity text. Next meeting The next meeting was tentatively scheduled for May 19, 2009, and was projected to primarily focus on the remaining table of unresolved issues from fire departments. Mathew Mertens suggested that Terry identify by color or other reproducible shading, which of the remaining issues are likely to be resolved only through changes in either Comm 14 or in other Comm codes. Wednesday, February 25, 2009, 9 a.m. to 3 p.m., Tommy G. Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, WI Council member attendance:
John Ashley -
Present; Gregg Cleveland – Chair - Present; Tod Doebler -
Present; Marty King - Present; John Periard - Absent; and Jim Stormer
(Todd Blaser, Alternate) - Present. Department of Commerce staff:
Bob DuPont, Terry Nolen and Sam Rockweiler Gregg Cleveland opened the meeting with a discussion of the potential benefits of expanding the chapter Comm 14 Appendix to include the various forms that are used in administering Comm 14. Gregg explained that having a standardized set of forms there could promote efficiency around the state, and could benefit small communities which may not have Internet-based resources for routinely accessing the forms at a Department Web site. The informational notes in Comm 14 that refer to obtaining forms at the Department’s Web site could also be expanded to refer to having the forms in the Appendix, and additional notes could be added for any forms which are not yet referenced in Comm 14. In reviewing the draft progress report for the preceding, December 10, 2008, Council meeting, staff distributed a revision of the first sentence of the third paragraph on page six, which would then read “In discussing the new definition for special amusement buildings that is included in the 2009 NFPA 1, there was interest in looking at whether any of the 2009 changes conflict with the requirements in chapter Comm 34 for amusement rides.” The Council accepted the progress report as so revised. Department update Budgetary cutbacks - Bob DuPont reported that current budget proposals include reducing the funding for the fire prevention program by 1%, which would be $7500 and would be substantially less than the 6% reduction that is proposed for programs which are funded with general purpose revenues. The justification for 1% instead of 6% is that the program is safety related and is funded with program revenues. Gregg asked what the impact of the $7500 cut would be on fire departments. Bob responded that the Department would likely be able to absorb the cut without reducing services to fire departments, and the $7500 savings would then be distributed statewide to all fire departments. Fire sprinklers in residential occupancies - Bob reported that a lawsuit which challenged the Department’s March 2008 expansion of the residential occupancies where fire sprinklers are required has been appealed to the Wisconsin Supreme Court, following defeat of the challenge at the circuit and appeals court levels. Timeline for the 2009 NFPA 1 - Bob reported that the timeline for adopting the 2009 edition of NFPA 1 in Comm 14 is planned to coincide with updating chapters Comm 60 to 66 (the commercial building code) to include the 2009 edition of the International Code Council® suite of building codes. Public Hearings are expected later in 2009; and a July 1, 2010, effective date is expected. Carbon monoxide alarms - Bob reported that a permanent rule for replacing an emergency rule which requires carbon monoxide alarms in certain residential occupancies has been submitted to legislative review, and is expected to become effective later in 2009. Credentials for electrical inspectors - Bob reported that the Department plans to submit the rules which are required under 2007 Wisconsin Act 63, for credentialing electrical inspectors, to the Legislative Council by April 1. The rules are expected to apply to any new electrical service or electrical branch that must have overload protection. DNR fire incident reports for NFIRS - Terry noted that within geographic areas which are under the jurisdiction of the Department of Natural Resources, fire departments generally defer to the DNR as the primary fire department for the incident and reporting purposes – however, the DNR typically files their wild land fire incident reports with their federal counterpart rather than with the National Fire Incident Reporting System, which would be contrary to the reporting requirements in 2007 Wisconsin Act 75, for fires that include destruction of buildings. Marty King commented that the NFIRS interpretation likely is that those fire departments have a duty to report a building fire to NFIRS if the DNR does not, especially where the fire department responds to the fire. Gregg commented that for many of these wild land or forest fires, the DNR is the primary agency, the fire department typically provides mutual aid, and NFIRS is designed to accommodate reports only from the primary agency. Bob agreed to address the issue with the corresponding staff in the DNR. Staff vehicles - Bob explained that in 2008, four of the Department’s five fire prevention coordinators drove their personally assigned, state-owned vehicles fewer miles than the minimum which the Department of Administration prescribes for having a personally assigned vehicle. Continuing to have these vehicles costs, in total, about $5000 more per year than not having them, and returning them to the DOA pool fleet would result in distributing the $5000 savings statewide to fire departments, which would average about $5.80 per department. Bob asked whether the Council would prefer to have that distribution or to have the more responsive level of service which the coordinators can provide by having personally assigned vehicles. A motion was made by Gregg Cleveland, seconded by Tod Doebler, and passed unanimously, recommending that the Department continue to provide all fire prevention coordinators with personally assigned, state-owned vehicles, rather than distribute the subsequent savings to fire departments which would occur from not providing the vehicles. Internet-based self-certification - Bob reported that the June fire chiefs’ conference could include demonstration of an Internet-based process for municipalities and fire chiefs to transmit their self-certification for fire dues entitlements. The process is expected to include password-protected individual accounts that are accessible 24/7 by both municipal clerks and fire chiefs, and could completely replace transmitting paper-based forms. Marty suggested having the process eliminate duplication by automatically blocking the sending of paper-based forms to any municipality that has used the Internet-based transmittal. It was noted that many municipal clerks and fire departments are currently required to report electronically to other state and federal agencies. Gregg suggested alerting municipalities to any future cut-off date for paper-based transmittals. DHS requirements for fire department inspections, and written statements about emergency plans and fire safety, for nursing homes and community-based residential facilities Bill Lauzon distributed and summarized (1) a table showing contact information for the staff at the Department of Health Services who are assigned, by county, to review construction plans and to perform inspections for nursing homes and community-based residential facilities; (2) a draft report of input from the two DHS Bureaus that regulate nursing homes and community-based residential facilities, for resolving the Council’s questions and concerns about review of emergency plans, fire department inspections, and fire protection services; and (3) samples of written statements which DHS has accepted from fire departments for documenting the adequacy of emergency plans and fire safety for nursing homes. The input from the DHS Bureau for CBRFs clarified that under their rules which become effective on April 1st, fire departments are not required to review emergency plans, and an annual fire inspection must be conducted by either the local fire authority or a certified fire inspector. CBRFs are required to provide information to fire departments about areas of refuge and emergency plans, but a response is not required from the fire department. As referenced in the input from the DHS Bureau for nursing homes, Bill emphasized that DHS will accept whatever level of documentation a fire department is comfortable in issuing after reviewing an emergency plan for a nursing home or performing a fire inspection – and DHS does not intend to question the adequacy of a fire department’s performance. DHS engineers review the emergency plans to ensure they include the eight elements in section 19.7.2.2 of the 2000 edition of NFPA 101, and will accept any method that fire departments use to evaluate the plans. Bill noted DHS likely would have concern where no documentation exists from a fire department, or if a nursing home fails to follow up on a concern by a fire department. Gregg asked who the authority having jurisdiction (AHJ) is for these facilities, and Bill explained it is whoever has adopted the rules – namely, DHS or the federal agency which extends federal funding, or the local building inspector for local building codes, or the local fire department for local fire ordinances. Terry asked where the functional responsibility lies, and Bill explained it is with the licensed facility, rather than the fire department, to ensure compliance with chapter DHS 83 or 132. For example, if a fire department does not review an emergency plan, the facility would need to have an independent, third party perform the service. Terry noted that Comm 14 likewise addresses preparation and review of emergency plans for these and other facilities, through application of NFPA 1 section 10.9. According to Terry, NFPA requires review and approval of those plans where required by 10.9.1, and all revisions must be submitted for review. The 2009 changes to section 10.9 drop the NFPA 1600 plan requirements and allow the AHJ to decide whether revisions to a plan must be submitted for review. For the semiannual fire department inspections that the DHS rules require for nursing homes, Bill explained that DHS will not look for the inspections to be precisely 6 months apart, and will instead accept a tolerance of plus or minus 30 days. Staff training will also address the need for this flexibility. Terry noted that Comm 14 does not require this. Bill noted that the facility could need to have an independent, third party perform the service. Marty commented that difficulties with staffing resources could arise in looking at whether past fire inspections were performed at the prescribed intervals, and Bill noted that if a DHS citation is issued for not having a required inspection, a fine is enforced against the facility. Bill noted that since all areas of the state are covered by an established fire department, no nursing homes are affected by the requirement in section HFS 132.82 (3) (c) 3. to have a fire protection service contract with a municipality. Bill explained he will be DHS’s statewide contact for these topics at nursing homes and CBRFs, to simplify local fire department resolution of issues. He can be contacted by e-mail at bill.lauzon@wisconsin.gov or by telephone at 414-550-5864 if questions or concerns arise about corresponding directives from DHS staff or other DHS building requirements for these facilities. Marty recommended that if a DHS issue arises which involves the fire service, the Department of Commerce can help resolve it. Gregg recommended that Commerce and DHS coordinate their functions and rules relating to emergency plans and fire inspections for these facilities. There was agreement to add an informational note to Comm 14 referencing the DHS requirement for nursing home operators to have emergency plans that are reviewed by fire departments or other fire and safety experts. There also was agreement to add an informational note under the required inspections in section Comm 14.01 (11) (b), stating that DHS rules may require additional fire inspections for nursing homes. It was noted that one goal of the Council is to promote cooperation on fire safety between the DHS licensed facilities and the fire service. Adult family homes Sam Rockweiler distributed and explained a draft table summarizing how the Department’s construction and fire prevention codes apply to adult care in one- or two-family dwellings, in adult family homes, and in community-based residential facilities, for both new and existing buildings. Due to statutory provisions, Comm 14 does not apply to one- or two-family dwellings as addressed in sections 101.60 to 101.66 of the statutes, and to adult family homes as defined in section 50.01 (1) of the statutes – and consequently fire department inspections are not required there. Gregg, Terry and Todd Blaser agreed the page-at-a-glance table should be helpful to fire inspectors. Child-care facilities Sam distributed and explained an update of input from the Department of Children and Families (DCF) for resolving the Council’s questions and concerns about fire department inspections for child-care facilities. The input includes having links on the Department of Commerce Web site to (1) a directory, listed by county, of child-care facilities that are licensed by DCF, where fire departments can look for existing licensed facilities; and (2) a directory, listed by county, of the DCF regional licensing offices, where substantial deficiencies can be reported that are found during fire inspections of licensed facilities. Sam explained this licensure by DCF is required where 4 or more children are in care that receives state or federal funding, and certification by a county is required where 3 or fewer children are in such care. Going forward, fire departments should receive a copy of the DCF letter of license transmittal whenever a provider receives a license to operate a child care center, so fire departments will be informed of newly licensed facilities. DCF is expanding their optional owner’s report form and their instructional materials for DCF staff and owners, to include references to retaining and reviewing maintenance records for fire alarm systems and fire sprinkler systems. DCF is also expanding their commentary manual to explain that fire departments generally conduct fire inspections at least once in each non-overlapping 6-month period per calendar year – unless a different frequency is established in a first class city, or by a local ordinance, or by a Department special order – and to explain that these inspections are not performed for one- or two-family dwellings which function as (1) a foster home or a treatment foster home, for 4 or fewer children; or (2) a group home, a residential care center for children and youth, or a public or private day care center, for 8 or fewer children. DCF has also informed their licensing staff and the certification staff in Chippewa, St. Croix, and Wood counties that having fire inspections precisely 6 months apart is not required. Sam reported that any requests from child care providers for a fire inspection which is not consistent with the inspections required under Comm 14 can be forwarded to Anne Carmody at 608-267-9761 or at anne.carmody@wi.gov. Q&A for design and construction In reference to the draft Q&A that was sent to the Council in advance of the meeting, Sam recounted how uncertainties and concerns about which requirements in NFPA 1 are design and construction requirements have arisen since adoption of NFPA 1 and the International Code Council building code suite in 2001. Sam explained that the draft Q&A attempts to provide a broad framework and guidance for fire inspectors to use in determining whether any particular requirement in NFPA 1 is a design and construction requirement and is therefore not included as part of Comm 14. The framework consists of a generalized, big-picture description of the sequence by which a commercial building is built and then used, through applying the building code requirements (such as chapters Comm 60 to 66, or chapter Comm 16) during the design and construction stage, and then applying Comm 14 during the use and operation stage. But almost inevitably during the use and operation stage, desires of how to use or operate the building evolve or change, and physical modifications of the building are then needed to align it with the new use or operation. The role of fire inspectors in this sequence provides a key mechanism for maintaining this alignment – and can result in a wide variety of circumstances for determining whether specific NFPA 1 requirements do or do not apply. Sam invited input on how the draft could be refined to be more helpful to fire inspectors. Gregg suggested adding several examples illustrating the application of NFPA 1 to specific buildings, and he noted that earlier versions of the commercial building code were helpful to fire inspectors by including an FP in the margin, for identifying the requirements which fire inspectors were responsible for enforcing. Bob noted that by law fire inspectors are only required to look for compliance with fire prevention requirements, but can look for compliance with other requirements. Terry commented that fire inspectors readily understand that they can check for compliance with requirements in Comm 60 to 66 or any other law or code as it relates to section 101.14 of the Statutes, “for the purpose of ascertaining and causing to be corrected any condition liable to cause fire, or any violation of any law or order relating to the fire hazard or the prevention of fire” – and some aspects of a building are clearly within the scope of the building code or within the scope of the fire code, but there are other aspects which are not clearly within one code or the other. For example, movable furniture is clearly addressed by Comm 14, and objects that are physically attached to a building are addressed by Comm 60 to 66, but deciding which code to apply to an interior finish can be more difficult. Terry added that “use” may have different meanings in the two codes, which can increase the uncertainty in deciding which code to apply. Marty noted that changing how part of a building is used can have repercussions on other parts of the building, such as how converting a room to a day-care facility can increase the needed egress through the building. Gregg noted that some gymnasiums occasionally become assembly occupancies, which Marty said can be permitted as a mixed use and Bob indicated can also be permitted as a temporary use. Greg noted many of the design and construction problems are caused by the way the building code is applied to a building versus the overall affect the use has on the building. He said the Department is not always using the most restrictive rule. He noted that because all the design and construction elements have been turned off in NFPA 1, there are no fire code triggers left for those elements. Matthew Mertens cited a building with 4-story ducts that were constructed in accordance with the building code but without cleanouts, and the need for cleanouts then became obvious during a fire inspection. Bob said that could be an inadequacy in the building code, which could be resolved by revising the building code. Bob added that the fire service has several avenues for providing additional input in updating the building code. Greg asked if the Department could develop a list of NFPA 1 rules it feels are design and construction requirements. Terry noted that the Department did that in 2002 when the Department jointly developed with NFPA an enrolled publication of the 2000 edition of NFPA 1 and the 2002 edition Comm 14 – which showed by strike-throughs, deletion of all the design and construction requirements in the 2000 edition of NFPA 1. Gregg asked the Council members to send Terry or Sam any examples they have for illustrating the application of NFPA 1 to specific buildings. Summary of 2009 changes to NFPA 1 In reference to the updated tabular summary of the 2009 changes to the 2006 edition of NFPA 1, that was sent to the Council in advance of the meeting, Sam explained that the new third column shows the corresponding readily apparent changes which are needed in Comm 14. In reviewing the summary, Craig asked how the change in NFPA 1 section 10.9.1 would impact schools. It was noted that buildings and grounds personnel for schools should be able to readily develop the emergency plans which are newly required by section 10.9.1 for educational occupancies. Gregg explained that NFPA 1600 provides non-mandatory guidance for developing the plans, which is summarized in the NFPA 1 Appendix. Terry noted that the change in section 10.9.2.4.2, and a similar change in 10.9.2.5, give the AHJ authority to decide whether revisions to a plan, and floor plans, must be submitted for review. There may be interest in clarifying whether the AHJ likewise has authority under section 10.9.2.3 to decide when any other emergency plan must be submitted for their review. Bob emphasized that if the 2009 changes include design and construction features which should be added to the commercial building code, the Council can recommend making those additions. Tod Doebler noted chapter 40 has been expanded to include more of the fire prevention portions of several NFPA standards that are referenced for dust control – and section 40.3.2 applies the housekeeping requirements retroactively. Terry commented that NFPA 1 typically does not apply retroactively except where risks are believed to warrant that application, whereas Comm 14 applies retroactively except where stated otherwise – which is a model-code concept that the Council may want to revisit. In looking at the changes to chapter 42 for liquefied gases, and to chapter 53 for mechanical refrigeration, it was noted that any design and construction requirements in those chapters are deactivated by section Comm 14.01 (2) (a) 2., because this section generally deactivates all design and construction requirements in NFPA 1. Bob noted that the Department is updating the mechanical refrigeration code (chapter Comm 45) and could expand that code to include any corresponding design and construction requirements in NFPA 1 which are appropriate. Terry asked whether the 2009 International Fire Code will be reviewed and who would be responsible to doing so. Bob stated that the IFC will be reviewed by the two fire specialty councils associated with the building code. Unresolved issues from fire departments In reference to the table of unresolved fire department issues that was developed by Terry and sent to the Council in advance of the meeting, there was agreement for Terry to (1) add a new column, or different font, for identifying any issues which may need to be resolved through changes either in Comm 14 or in other Comm codes, such as Comm 60 to 66; and (2) indentify any issues that have been resolved through the Web-posted Q&A which clarifies the authority having jurisdiction and the governing authority. Next meeting The next meeting was tentatively scheduled for March 17, 2009, and was projected to primarily focus on Terry’s list of unresolved issues from fire departments. Mathew Mertens suggested considering whether to add NFPA 1 to the standards that are adopted in Comm 61, with a provision to apply whichever design and construction requirements are the most restrictive – and Bob indicated the building design community could respond differently to that consideration now than when it was proposed in conjunction with adopting the ICC suite of building codes in 2001.
Wednesday,
December 10, 2008, 9:00 a.m. to 3:00 p.m., Tommy G.
Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison,
WI Council member attendance:
John Ashley -
Present; Gregg Cleveland – Chair - Present; Tod Doebler -
Present; Marty King - Present; John Periard - Absent; and Jim Stormer
(Todd Blaser, Alternate) - Absent. Department of Commerce staff:
Bob DuPont, Terry Nolen and Sam Rockweiler Guests: Anne Carmody,
Department of
Children and Families; Bill Lauzon, PE, Department of Health Services;
and Lynn Wallace, Department of Health Services. Gregg Cleveland opened the
meeting with a
review of the agenda, and the Council accepted the draft progress
report for the preceding, October 22, 2008, Council meeting.
Department update
Comm 14 changes
- Bob
DuPont reported that the changes for chapter Comm 14 which are needed
for fire incident reporting and mobile kitchens, as discussed at the
Council’s October meeting, are expected to advance to a
public
Hearing in February 2009. The changes for fire incident reporting will
update the current Comm 14 requirements to be consistent with the
record keeping requirements in 2007 Wisconsin Act 75. The Act 75
requirements will supersede the differing Comm 14 requirements until
the Comm 14 changes become effective later in 2009.
Christmas trees
in assembly occupancies
- Bob noted the Department’s Web site for the Fire Prevention
Program includes an October 30th letter from the Secretary to all fire
chiefs, explaining that NFPA 1 section 10.14.2 allows them, as the
Authority Having Jurisdiction, to permit natural-cut Christmas trees
where they determine that adequate safeguards are provided. Concerns
were expressed that the letter only addresses assembly occupancies and
not the other occupancies where Christmas trees are prohibited by NFPA
1 table 10.14.1. Gregg reported that data is
being gathered
by a Wisconsin State Fire Chiefs Association (WSFCA) survey, for
consideration during next year’s use of the trees. It was
noted
schools and nursing homes are choosing to not use natural-cut trees
based on insurance and liability concerns. There is concern for how
much liability municipalities take on if an AHJ allows something that
is outside the fire code. The fire service does not understand how the
Department derived its interpretation on the topic, and wants more
explanation from the Department, such as what support the Department
would provide if a corresponding lawsuit is filed against a
municipality. Bob stated the Department will trust the judgment of an
AHJ. Gregg emphasized that the explanation should address how fire
chiefs have become authorized to allow variation from the fire code
– and if a fire occurs as a result of that permission, what
should a municipality do if the insurance company seeks to recover
damages from them. Bob explained that NFPA 1
section 10.14.2
allows limited quantities of combustible vegetation, and is followed by
other sections that specify safeguards to apply where the vegetation is
used. Bob stated the Department could codify the AHJ discretional areas
if the WSFCA wants. If further safeguards need to be codified, they
could be added to Comm 14. Gregg recommended not changing Comm 14 in
that manner, and Bob noted further explanation and adequate safeguards,
including examples, could be posted as a Q&A on the Fire
Prevention
Program Web site. Gregg commented that the underlying issue is that a transition has occurred – from a previous process where the Department established the rules, to a new process where local governmental units can allow varying from the rules – and this new authority has not been clearly explained and communicated to the local units. In addition, there may be some concern that the Department has capitulated to pressure for using the trees in assembly occupancies. Bob suggested that the
Q&A which staff
are developing for clarifying the role of AHJs will help resolve the
issue. Gregg said the main question is whether the Department will
support a fire department if something goes wrong. Bob said it would be
difficult for the Department to issue a general statement promising to
support fire departments 100 percent of the time. Gregg recommended the
Department issue a statement that it has consulted with the fire
service, and then developed best practices which can be used to
minimize risk. John Ashley commented that such a statement could be
helpful, but it would not resolve the insurance issue. Gregg agreed the
statement would not resolve the insurance issue entirely, but a fire
department’s liability could be significantly lessened if a
fire
chief who is testifying in court is able to display the
Department’s best practices and then explain how the fire
department followed them. John questioned whether the Department would
accept being exposed to the remaining portion of the liability. Bob noted that the Secretary’s letter was issued after finding that the legislature was moving toward suspending the entire set of rules for natural-cut Christmas trees, and fire chiefs have developed some best practices for the trees. Marty King commented that a
primary concern
is not having enough control over whether a church uses the trees
correctly, and churches typically are staffed with seasonal volunteers
who are not adequately aware of both the fire danger and the needed
safeguards.
A motion was made by
Marty King and
seconded by John Ashley that the Department issue a Q&A which
(1)
explains how fire departments have become authorized to allow Christmas
trees in assembly occupancies, (2) shows why fire departments are not
violating Comm 14 by allowing the trees, and (3) describes best
practices that should be used with the trees.
Terry Nolen noted the Council and the Department have known about this code problem since 2005, and he indicated the National Fire Protection Association has taken an informal position that NFPA 1 section 10.14.2 is not intended to include trees. According to Terry, NFPA has further stated that the AHJ authority for discretion is found in NFPA 1 section 1.4 titled Equivalencies, Alternatives, and Modifications. Terry suggested if the Department wants to interpret NFPA 1 section 10.14.2 differently, it should utilize the text in section Comm 14.01 (2) (c) which states that any Departmental interpretation of the requirements in Comm 14 supersedes any differing interpretation by an issuer of an incorporated standard. Marty noted the Q&A could cite the general criteria in NFPA 1 chapter 1 that addresses equivalencies and alternatives. Gregg recommended that the Q&A include a reference to the superseding aspect and an explanation of the chain of authority. Terry questioned whether the
15 municipalities that have adopted the 2006 International
Fire Code®
as an alternative to NFPA 1 will have similar AHJ discretionary options
for allowing the trees, because the 2006 IFC does not contain text
which is similar to NFPA 1 section 10.14.2. Gregg and Marty agreed that
having or not having those options under the IFC is entirely a local
issue because any municipality which chose to adopt the 2006 IFC did so
after being informed that the Department would not assist in
determining whether any such proposed adoption would be equivalent to
Comm 14 and NFPA 1 – and therefore the Council should not
spend
time on it. Terry questioned how any IFC-ordinance conflict with
section Comm 14.001 (2) (a) would be resolved. Bob noted that under
section 101.02 (7) (b) of the statutes, any person affected by any
local order that is in conflict with an order of the Department may
petition the Department for a hearing on the ground that such local
order is unreasonable and in conflict with the order of the Department.
The motion passed
unanimously.
Wisconsin
Burning
- Bob reported that the 2005 edition of the Wisconsin Burning report
has been posted on the Fire Prevention Program Web site, and presents a
detailed overview of fire incidents in Wisconsin.
Budgetary
cutbacks - Bob
reported that the Governor’s Office has directed the
Department
of Administration to help other State agencies identify aids and grants
that are non-essential and therefore can be postponed until after
budget deficits are resolved. In response to DOA’s proposed
list
of such aids and grants, Department of Commerce staff have proposed
identifying the two-percent fire department dues payments as being
essential, safety related aids.
November 1,
2008, edition of Comm 14
- Sam Rockweiler distributed the November 1, 2008, edition of Comm 14
and explained that the only change from the previous edition is
updating the chapter Comm 10 title in the Note under section Comm 14.01
(2).
February 1,
2009, edition of Comm 10
- Sam distributed the February 1, 2009, edition of Comm 10, for
flammable, combustible and hazardous liquids, and explained that this
effective date is delayed for 2 months after November 1 to help small
business adjust to the new rules. Sam emphasized that under section
Comm 14.01 (2) (b) 4., where differences occur between the requirements
of chapter Comm 14 and chapter Comm 10, the requirements of Comm 10
will prevail unless otherwise excluded by Comm 10. For example, the new
Comm 10 applies a newer version of NFPA 30 to flammable and combustible
liquids in aboveground tanks and other containers of 110 gallons or
more, than is applied in Comm 14.
2009 NFPA 1
- Bob distributed the 2009 edition of NFPA 1, for the Council to begin
reviewing for adoption in Comm 14.
Web site
Q&As, and Authority Having Jurisdiction
Q&A Web
site for the Fire Prevention Program
- In reference to the Department Web site for posting Q&As for
the
Fire Prevention Program, which became operational after the
Council’s discussion of it in October, Marty asked whether
notices for it could be distributed through Gregg’s
LISTSERV®
e-mail list for fire chiefs, and Tod Doebler asked about distributing
notices through his LISTSERV list for fire inspectors. Bob explained
that any party which has subscribed to the Safety and Buildings
Division LISTSERV will get a notice each time a new Q&A is
posted.
Gregg and Tod agreed to subscribe their LISTSERVs to the Safety and
Buildings LISTSERV.
Q&A for
Authority Having Jurisdiction
- In reference to the Q&A for Authority Having Jurisdiction,
which
was sent to the Council in draft form in advance of the meeting, a
motion was made by John Ashley and seconded by Marty King to accept the
draft as written.
Terry asked whether there was any concern for the second sentence in
the Answer, which describes the “governing
authority” as
being the Department – since that term is not directly
included
in Comm 14. Marty noted it is included indirectly through adoption of
NFPA 1, because NFPA 1 does include it. Sam noted that NFPA 1 and Comm
14 together are the Wisconsin Fire Prevention Code. Bob said the term
could be added to the definitions in Comm 14 and modified there if
needed. The motion passed unanimously.
Q&A for
design and construction
- Gregg recommended developing a Q&A for explaining which
requirements are for design and construction, and therefore are within
the scope of the Commercial Building Code – versus
requirements
that are for use, operation and maintenance, and therefore are within
the scope of Comm 14.
A motion was made by
Marty King and
seconded by Tod Doebler that the Department develop a Q&A for
design and construction, with input from the Council, and through
whatever process is deemed best due to the interplay between Comm 14
and the Commercial Building Code over this term. According to Marty, this term,
and
consequently the applicability of the two codes, is often
misinterpreted. Therefore, even if the Council does not entirely agree
with the final draft, publishing it would still be helpful.
The motion passed
unanimously.
Carbon monoxide
alarms
Bob reported that about ninety
percent of
the time, a required location for a carbon monoxide alarm is the same
as for a smoke alarm; therefore combination smoke and carbon monoxide
alarms can be used in those locations. Also, support is building for
extending the statutory requirement for their installation in
commercial buildings to apply also to both new and existing one- and
two-family dwellings. For credentialing and training for inspectors of
the alarms, Bob noted that the least intensive level which the Division
has used in other programs has consisted of mailing reference materials
to applicants, who then return a signed statement that they have read
the materials, and the Division then certifies those applicants. A
higher level of training could primarily consist of a Web-based system.
Continuing-education modules that address the alarms could be developed
for building inspectors who are required to obtain continuing-education
credits for renewing a credential. More details are expected to be
available by the next Council meeting, after upcoming meetings with
representatives from the carbon monoxide alarm industry. Terry questioned whether fire
inspectors
should only inspect alarms in residential common areas, rather than
also within dwelling units, because fire departments have raised
concerns about being required to inspect within occupied dwelling
units. Bob noted that the statutes require maintenance inspections only
for alarms in the common areas of apartment-type buildings –
just
as for smoke alarms. However, inspectors can inspect a unit within such
buildings at the request of the owner or occupant of the unit to be
inspected. It was noted that the Department of Health Services (DHS)
has rules for access to CBRF dwelling areas. In addition to ongoing
maintenance inspections by fire departments, initial inspections by
building inspectors are expected to occur during new construction
– and the Department and DHS are expected to have
corresponding
requirements for ongoing inspections of sealed-combustion appliances.
Marty suggested extending the training and credentialing to staff from
DHS. Bob noted that DHS is required to develop rules for their
inspections.
NFPA 1, 2009
In reference to the NFPA
summary of changes
from the 2006 to the 2009 edition of NFPA 1, which was sent to the
Council in advance of the meeting, Gregg asked whether any of the
changes could affect the current Comm 14 modifications of the 2006
edition of NFPA 1. Bob said staff could review the summary and identify
any of those changes for the next Council meeting. In discussing the new definition for
special amusement buildings that is included in the 2009 NFPA 1, there
was interest in looking at whether any of the 2009 changes conflict
with the requirements in chapter Comm 34 for amusement rides. For
this review, and for looking
at whether any of the changes conflict with requirements in other Comm
codes, staff will pursue getting an electronic-based version of the
summary that can be expanded to include a column for showing any such
conflicts. Similarly, some of the 2009 changes may address topics that
are addressed in rules by other State agencies, such as the changes in
sections 10.9.1, 10.9.2.2 and 10.9.2.4.2 for emergency plans for
health-care and child-care facilities. There was agreement to retain
the global note in Comm 14 referring to other Department codes and
state agencies that may have additional requirements which may apply to
public buildings and places of employment. It was noted that the 2009
NFPA 1 has been realigned to meet the current NFPA code format style. Bob emphasized that the
Department
generally leans toward applying model code requirements except where
that application would be too problematic. Marty suggested including an
informational Note in the Comm 14 Appendix in conjunction with adopting
the 2009 NFPA 1, for alerting readers to the best practices for
Christmas trees, that are expected to be posted on the Fire Prevention
Program Web site.
Fire department
inspections, and
written statements about evacuation plans and fire safety for licensed
health-care and child-care facilities
Overview
- Bob explained
that the Department can facilitate Council discussions with the
Department of Health Services (DHS) and the Department of Children and
Families (DCF) for the services which fire departments provide to the
health-care and child-care facilities licensed by those two
Departments. The discussions could address fire department complaints
about DHS requiring fire inspections no more than 6 months apart, and
questions about the authority of DHS or DCF to require fire departments
to provide inspections and planning services for evacuation and fire
safety. Concerns were raised as to the lack of standardized
terminology, such as for assistance, signed certificates,
certifications, continuing contracts, disaster vs. evacuation vs. fire
safety vs. emergency plans, and fire protection services. It was noted
that a nursing home must contract with a private inspection services to
provide the required services if a local fire department refuses to. Marty recommended that fire
departments not
sign any forms or letters accepting responsibility or liability for the
licensed facilities. Gregg questioned the extent of a current
memorandum of understanding between Commerce and DHS for health-care
facilities. Bob explained that it includes having DHS review
construction plans for non-health care components of health care
facilities, such as parking ramps, when reviewing overall construction
plans for these facilities. Gregg asked what the process is for
resolving any differences between Wisconsin’s Commercial
Building
Code and applicable NFPA construction codes, such as the NFPA 101 Life
Safety Code, and Bob said the more-restrictive requirement is applied
if there is a difference. Bob noted Department staff audit the DHS plan
review program for compliance to Commerce codes. Bob added that a
separate memorandum of understanding could be developed if desired, to
address fire inspection conflicts, and statements about evacuation
plans and fire safety. Marty emphasized that (1) fire departments want
timely rather than urgent scheduling for fire inspections, and (2) they
are being advised by legal staff to not certify the adequacy of an
evacuation plan or the fire safety of a facility.
Nursing homes
- Tod
Doebler explained that several fire departments are reporting they are
being contacted by nursing homes which have received a citation from a
nursing home inspector for not having a fire department’s
“certification . . . as to the fire safety of the facility
and to
the adequacy of a written fire plan for orderly evacuation of
residents,” as required in section HFS 132.82 (3) (c) 2. Tod
noted that fire departments are refusing to provide that certification.
He asked what is meant by “certification” in HFS
132.82 (3)
(c) 2., and where the DHS authority originates from for requiring the
certification. Lynn Wallace responded that
this code
requirement was promulgated through legislative review and has existed
for at least 20 years, but DHS is now enforcing it more vigorously
because of heightened emphasis on emergency preparedness, relating in
part to recent flooding and other extreme-weather related incidents.
Marty commented that the requirement is an unfunded mandate which local
governments and fire departments have been unaware of; and he noted
that fire chiefs are deputies of the Department of Commerce and subject
to its authority, but are not subject to DHS authority. Bill Lauzon read a statement
from a Port
Washington fire inspector which generally described a nursing
home’s evacuation plan and fire safety as “adequate
safeguards are in place,” and which was accepted by a nursing
home inspector. Bill said the nursing home section in DHS could issue
guidelines on what can be accepted as a
“certification” of
the fire safety of a facility and the adequacy of an evacuation plan.
The fire service raised concerns as to nursing homes throughout
Wisconsin appearing to be treated differently – and the fire
service goal is equal application statewide. Tod questioned whether
compliance with standard NFPA 1600, as referenced in NFPA 1, would be
needed. Marty asked whether stating that the facility’s fire
safety plan is in compliance with model codes would suffice, because
fire departments prefer to rely on model code benchmarks. Bill
suggested looking for whether a fire safety plan includes the elements
that are required in section 19.7.2 of the 2000 edition of NFPA 101.
Terry noted the same elements are found in NFPA 1600, as is referenced
in NFPA 1 section 10.9.2. Lynn said the DHS nursing home section could
be asked to develop a draft guidance document that the Council could
comment on. Marty noted that a second
issue of concern
is what is meant by the requirement in section HFS 132.82 (3) (c) 1.
for “semiannual” fire inspections, and Sam noted
that
section Comm 14.01 (11) (b) 3. requires conducting fire inspections
“at least once in each non-overlapping 6-month period per
calendar year.” Lynn indicated the HFS requirement should be
met
by complying with the Comm 14 requirement. Marty added that a nursing
home typically contacts his department and wrongly assumes they are
familiar with the HFS requirements – and his department
likewise
does not know which DHS inspector is involved with the facility. Bill
agreed to provide a chart showing which nursing homes are inspected by
which DHS inspector. Terry noted HFS 132.82 (3) (c)
3. requires
a nursing home to have a contract for fire protection services if the
home is located in a city, village or township that does not have an
official, established fire department, and requires keeping a
certification of the existence of that contract on file in the
facility. Terry noted HFS 132.82 (3) (c) appears to require the
administrator of those facilities to arrange for semiannual fire
department inspections, and certifications of evacuation plans and fire
safety, as applicable, and he questioned whether that is an accurate
reading of the code.
Community-based
residential facilities
- Marty indicated that the optional DHS inspection form which was sent
to the Council in advance of the meeting should be useful for the
annual fire department inspections that are required in section HFS
83.42 (6) (a) 1. for CBRFs with 9 or more residents. It was noted that
HFS 83.42 (6) (a) 2. refers to “comments and
recommendations” from the fire department, rather than a
“certification,” about the adequacy of written
plans for
evacuation of residents in the case of fire, and about the adequacy of
the fire safety of the CBRF. Tod raised liability exposure concerns
about fire departments being required to comment or making
recommendations on the requirements in HFS 83.42 (3) for CBRF emergency
plans and in subsection (4) for emergency planning for certain
residents. It was also noted that HFS 83.42 (6) (b) requires DHS to
annually inspect CBRFs for 8 or fewer residents to determine compliance
with fire safety requirements and the adequacy of written emergency
plans.
Outcome for
health-care facilities
- Lynn indicated that chapter DHS 124 does not have any language
requiring local fire departments to do fire inspections or approve
evacuation or life safety plans, for hospitals. Bill agreed to pursue
having DHS draft a letter for the Council to review that will (1)
clarify what can be accepted as a “certification”
under HFS
132.82 (3) (c) 2., and whether to use a standard specification, such as
section 19.7.2 in the 2000 edition of NFPA 101 or NFPA 1 section 10.9,
as a benchmark; (2) clarify whether the
“semiannual”
frequency in HFS 132.82 (3) (c) 1. is met by the inspection frequency
in Comm 14.01 (11) (b) 3.; (3) clarify the optional use of the CBRF
inspection forms; (4) include a chart of DHS inspectors that shows
their e-mail and mailing addresses, telephone numbers and assigned
inspection areas; and (5) clarify the requirements for a nursing home
that is located in a city, village or township which does not have an
official, established fire department.
Child-care
facilities -
Anne Carmody explained that the administrative codes for the various
types of licensed child-care facilities are being updated in
conjunction with the Division of Children and Family Services becoming
the Department of Children and Families (DCF). Chapter HFS 45, for
family child care centers, has become DCF 250; HFS 46, for group child
care centers, has become DCF 251; and HFS 55, for day camps for
children, has become DCF 252. According to Anne, these three codes do
not require any inspections by fire departments. Similarly, HFS 52, for
residential care
centers for children and youth, has become DCF 52; HFS 57, for group
foster homes for children, has become DCF 57; and HFS 59, for shelter
care facilities, has become DCF 59. Anne noted that of these three
codes, only DCF 52 requires inspections by fire departments. Section
DCF 52.55 (3) requires an annual fire inspection; DCF 52.55 (1)
requires developing an evacuation plan in consultation with the fire
department; and, for the initial license application, DCF 52.62 (2) (c)
11. requires a fire inspection report showing “approval of
the
facility for fire safety.” Terry noted that NFPA 1 section
10.9
requires emergency plans for residential board and care facilities and
day-care centers unless otherwise exempted by sections Comm 14.01 (1)
(b) and (c) 5. and 6. It was noted that some
child-care providers
in Marshfield, Cornell and Richmond are contacting fire departments
about licensure trouble from not complying with a DCF requirement to
have two fire department inspections every year within 6 months
–
which is different from the requirement in Comm 14.01 (11) (b) 3. to
conduct fire inspections at least once in each non-overlapping 6-month
period per calendar year. Anne noted that DCF generally looks for a
recent fire department inspection report when re-licensing a child-care
facility in conjunction with a change of ownership – and she
agreed to look into and clarify for DCF staff that they are not
authorized to require child-care providers to have two fire department
inspections every year within 6 months. Anne said this clarification
and similar guidance for other topics can be posted on a Web site DCF
has for providing assistance to field staff. Terry noted that in some cases
a fire
department may not be aware of a child-care facility and consequently
has not inspected it. Anne agreed to send Sam hyperlinks to DCF Web
sites that show new, pending and existing, licensed child-care
facilities – for posting on the Fire Prevention Program Web
site. Anne questioned how DCF staff
could
determine if a fire protection system is operable or has been
maintained. Terry recommended adding a note to DCF’s
inspection
forms for alerting DCF inspectors to check for fire protection
maintenance records from qualified maintenance personnel, for sprinkler
systems and other fire protection components, such as fire alarms.
Unresolved
issues from fire departments
In reference to the table of
unresolved
fire department issues that was developed by Terry and sent to the
Council in advance of the meeting, Gregg asked whether Terry could
identify which issues are the most important. Terry explained that the
table is a running list of unresolved issues which fire departments
have posed to the Department’s Fire Prevention Coordinators
since
adoption of the 2000 edition of NFPA 1 in 2001, and he suggested
subdividing the issues into major categories. Bob suggested reviewing
the issues simultaneously with NFPA’s summary of changes from
the
2006 to the 2009 edition of NFPA 1. Gregg asked whether any of the
issues are currently causing major problems. According to Terry,
several of the issues could be resolved through developing a
Q&A
for design and construction, and the Q&A that will be posted
for
clarifying the AHJ and governing authority should similarly resolve
several of the issues. Terry said another topic that could be clarified
which could resolve several issues is “temporary
use,”
which he believes the Council interprets as having a significantly
different application and meaning in Comm 14 than in the Commercial
Building Code. Bob suggested identifying any other global issues whose
clarification could resolve subsequent issues, and he asked how the
entries in the columns for “Not addressed” and
“Addressed” were determined. Terry explained he
added these
two columns at Gregg’s request, and Council discussions can
now
determine when the “Not addressed” entries can be
changed
to “Addressed.”
Next meeting
The next meeting was
tentatively scheduled
for the last Wednesday in February 2009, and was projected to primarily
focus on Terry’s list of unresolved issues from fire
departments. Wednesday, October 22, 2008, 9 a.m. to 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council member
attendance: John Ashley- Present; Gregg
Cleveland, Chair - P; Marty King
- P; Tod Doebler - P; John Periard
- Absent; Jim Stormer (Todd Blaser, Alternate)
- P. Update on Comm 10, Flammable, Combustible, and Hazardous Liquids Sam Rockweiler reported that the legislative review period for repealing and recreating Comm 10, as administered by the Environmental and Regulatory Services Division, ended on September 16. The rules were adopted later that month, and are expected to be published in the end-of-November issue of the Wisconsin Administrative Register. The rules will then have a two-month delayed effective date of February 1, 2009, which will allow small businesses and others to adjust to the new rules. To help with that adjustment, the department is partnering with the Wisconsin Petroleum Equipment Contractors Association to conduct a series of training sessions in January and February at several regional locations throughout the state. Further details for the training sessions will be posted on the department’s Web site as they become finalized. The rules are currently posted on the Web site, through links to the ERS Division. Sam also reported that a Scope Statement was published in the Register on October 14 for updating Comm 10 to comply with the requirements issued in August 2007 by the United States Environmental Protection Agency, in response to the federal Energy Policy Act of 2005, for training three levels of operators of underground storage tank (UST) systems. The three levels generally equate to class A for general managers, class B for station supervisors, and class C for employees at the cash register. Mike Fehrenbach explained that the changes in Comm 10 are expected to closely match the EPA criteria and the corresponding rules that all other states, including the four adjacent states, likewise must adopt by August 8, 2009. Wisconsin is currently ahead of most states in EPA’s Region V except Minnesota. Maine has substantially begun developing their rules and corresponding Web-based program materials, which may be helpful to the department and avoid reinventing the same material. The department likely will provide oversight and tracking of the training and corresponding testing, rather than provide the training and testing. Documentation that an operator has complied with the requirements may be addressed through the current annual operating permits for the tank systems, rather than through any newly created credential issued under Comm 5, Licenses, Certifications, and Registrations Code. According to Mike, about 4000 underground storage tank facilities in Wisconsin will be affected. Mike said he was unsure about the actual number of UST owners. It was noted that there may be a test-out option. It was unclear whether the test would be a general application test or site-specific application test. No continuing educational requirements are anticipated. Code revisions may be needed in Comm 2, Fee Code, Comm 5, and Comm 10 to recognize the operator training provisions. Marty King commented that the department’s Local Program Operators may be interested in conducting or hosting some of the training. John Ashley noted some school districts have multiple facilities with underground storage tanks, and Mike explained that the upper two levels of operators can oversee multiple sites. Mike emphasized that the primary goals are to make compliance as easy and least costly as possible, and to have reciprocity with the adjacent states. Safety and Buildings Division Update Active code-development projects - Bob DuPont reported that the division currently has 24 active code-development projects, many of which are in response to legislative action during the legislature’s last session. The projects include changes to Comm 41, Boiler and Pressure Vessels Code, which are expected to become effective on December 1. Changes to Comm 16, Electrical Code, are in legislative review, and include criteria relating to arc-fault circuit interrupters, and tamper-resistant receptacles in dwelling units. Opposition to the arc-fault interrupters and tamper-resistant receptacles has arisen, and a compromise may result. A public hearing draft for updating Comm 60 to 66, Commercial Building Code, to include the 2009 edition of the building code suite from the International Code Council may be completed by July 1, 2009. Carbon monoxide (CO) alarms - Terry Nolen commented that the recently adopted emergency rules for carbon monoxide alarms may be unclear about whether the alarms must be interconnected in multifamily dwellings in order to provide a warning in all units, rather than provide a warning only in the unit where the detection occurs. Bob explained that the rule matches the corresponding legislation, 2007 Wisconsin Act 205, in requiring a warning only in the unit where the detection occurs, and in requiring the alarms to be maintained in accordance with the manufacturer’s instructions. Bob distributed a draft of a carbon monoxide brochure the department plans to finalize and then provide at the annual fall conference for fire inspectors. The brochure will also be posted on the department’s Web site, and copies should be available in bulk quantities. Bob asked the council members to review and provide feedback on the brochure. Marty asked whether the brochure will be distributed to building inspectors. Bob said, "Yes," and that plan-review entities will also receive a copy. Gregg commented that the included excerpt from the corresponding legislation seems unclear in excluding an introductory phrase, and in addressing dwelling units which are not part of a multiunit building. Bob explained that under section 101.149(2)(b) of the legislation, the owner of a building with a single dwelling unit need not install more than one CO alarm in the unit, which is an exception to the multiple locations required for a unit in multiple-unit buildings. There was agreement that this section should be more clearly conveyed as being an exception. Marty noted that the alarm requirements may be extended by further legislation within the next few years to apply to one- and two-family dwellings. School drills - Bob distributed an updated draft of the department’s current form for reporting school drills for fires and other emergencies. The update is intended to incorporate the requirements in 2007 Wisconsin Act 79 for reporting drills relating to tornadoes and other hazards; and to accommodate the additional emergency egress drill that is required by section 20.2.3.2.2(3) of the 2006 edition of the National Fire Protection Association’s NFPA 1, during the first 30 days of operation for educational occupancies which are not open on a year-round basis. It was noted that an additional line should be added to the form to record the additional fire drill for these occupancies. Terry noted the instructions on the back side of the form state that fire officials must be invited to be part of the drills, and he questioned why the instructions do not instead reflect the actual code language, and whether that invitation must occur with each drill. Marty noted that whenever his fire department is invited, they participate, and they want to be notified of each drill so that they don’t respond to the drill’s fire alarm as a false alarm. There was agreement that the text from NFPA 1 section 10.6.1 which is reprinted later in the form’s instructions is more appropriate in stating that the fire drills must be designed in cooperation with the local authorities. There was agreement to revise the mandated invitation to instead reflect consistency with the text in 10.6.1, and to add another line to the fire drill section on the front side of the form. John emphasized that training is also needed for the drills, and for lockdowns. It was noted that an Alliance for Fire Safety newsletter which contained a fire drill message was recently sent to all Wisconsin schools. Marty explained his department uses a different report form for lockdowns, because lockdowns keep the occupants in, instead of getting them out, as in an egress drill. Bob agreed to have the form revised accordingly, and to post it on the department’s Web site within the next week. Proposed changes to Comm 14 In referencing the proposed rule changes that were sent to the council in advance of the meeting, Sam explained that SECTION 1 revises the scope of the fire-reporting requirements so that they apply to all fire responses which involve a building, rather than applying to all fire responses, which is needed to be consistent with the corresponding legislation in 2007 Wisconsin Act 75. Terry noted that the National Fire Incident Reporting System (NFIRS) has a series of descriptive phrases with assigned code numbers, which are used to describe fire incidents, and many of these phrases and common definitions were created by the NFPA and published in NFPA 901, Standard Classifications for Incident Reporting and Fire Protection Data. Gregg and Terry questioned how “building” is defined for the purposes of SECTION 1, and the definition in NFPA 1 section 3.3.27 was noted as differing from the definition in the NFPA 901 standard by referring to a “use or occupancy” rather than referring only to an “occupancy.” The council agreed that the NFPA 1 definition is adequate for the purpose of complying with Act 75. In discussing the SECTION 2 criteria for reporting fire data, Marty commented that the reported building-age data is not likely to be subsequently extractable from NFIRS, because the age data is not entered in one of the standard electronic-based NFIRS modules. The age data typically is entered instead as part of a narrative in a special NFIRS module E. Sam asked whether the proposed rules should be refined to inform fire departments on how to enter the age data in a uniform, extractable manner in module E, and the council recommended against the refinement. Marty explained that fire departments could be trained on how to enter the age data in a more extractable manner. Terry emphasized that the main, initial goal is to get all 862 fire departments participating in the data entry. John asked why either assessed values or estimated replacement costs can be reported. Bob explained that replacement-cost data is often used where only partial property loss occurs, and an assessed value is typically used where a total loss occurs. Bob noted that recent United States Fire Administration efforts have been directed at making the NIFRS data accessible to fire departments rather than just state-level staff. Sam noted council concerns had arisen about the included text from section 101.141(3) of the statutes that authorizes the department to review, correct, or update any report filed by a fire department. Terry explained that historically the department has corrected a submitted paper-based NFIRS report only where needed to enable electronic-based acceptance of the report. Under the proposed rules, all fire departments will file the reports electronically with NFIRS, rather than submit paper-based reports to the department for entry into NFIRS. Bob noted that the department’s arrangement with NFIRS is to review, rather than revise, reported data. The council noted their concerns related to legal ownership, court proceedings, and open-records responsibilities for the reports, and recommended refining the proposed rules to state that “Department” in this section means the chief of the corresponding city, village or town fire department, who is constituted a deputy of the Department of Commerce. In discussing the criteria in SECTION 3 for a once-per-calendar-year inspection frequency for eligible seasonal or periodic occupancies, Terry noted that limiting a seasonal or periodic occupancy to a maximum of 6 consecutive months could result in 5 months of occupancy, then 1 month off, and then 2 to 6 more months of occupancy, during a calendar year. The council agreed seasonal and periodic occupancies should instead not extend beyond 6 months in any calendar year in order to qualify for the once-per-calendar-year inspection frequency. The changes in SECTION 4 for inspection reports under Comm 14.01(11)(b)7., and for availability of records under Comm 14.01(11)(e) were noted as being needed for consistency with section 19.21(4)(b) of the statutes, which requires keeping these records for at least 7 years. SECTION 4 was accepted by the council as drafted. In discussing SECTION 5, Gregg recommended adding a requirement to retain the usage records for mobile kitchens on the premises of each kitchen, and the council accepted the draft SECTION with that addition. Based on the council’s acceptance of the draft rules, Bob indicated the division would proceed with advancing them to the public hearing stage. Web site Q&As, and seasonal and periodic occupancies In reference to the Q&A for seasonal and periodic occupancies that are eligible for a once-per-calendar-year inspection frequency, which was sent to the council in draft form in advance of the meeting, the council agreed the length of the occupancy should not extend beyond 6 months in any given calendar year, rather than beyond 6 consecutive months, in order to match the draft rules discussed earlier. The council accepted the draft Q&A with that change. Sam distributed a draft format for a department Web site for posting the Q&A for seasonal and periodic occupancies, and for posting additional Q&As that could be developed for addressing other topics. The council accepted the draft format, and welcomed the prospect of using the Web site as a medium for distributing resolved issues in the fire prevention program to fire departments and the general public. Terry recommended having a quick link for the Q&A Web site near the top of the department’s Web site for the fire prevention program. Review of 2009 NFPA 1, and credentialing of fire inspectors Gregg asked for an update of the timeline for reviewing the 2009 edition of NFPA 1, and Bob said the council’s review could start at their next meeting, since the published copies are expected to become available within the next week or so. It was noted that the corresponding 2009 ICC building code suite should be available by January 2009. Bob suggested that prior to beginning the review, the council may want to consider whether the department should begin credentialing fire inspectors, for performing the carbon monoxide (CO) alarm inspections that are mandated in section 101.149(7) of the statutes, as created by 2007 Wisconsin Act 205. Bob explained that the department could issue the credential upon receipt of proof of an inspector attending a course approved by the department. Marty questioned whether adjacent or other states have enacted requirements for CO alarms, and whether those requirements include credentialing inspectors. Terry asked what Act 205 intends by having a building inspector “certified” by the department. Bob said “certified” typically infers a higher level of knowledge than simply being “registered.” It was noted that having fire inspectors perform the CO inspections for existing buildings as part of their regular fire inspection duties and inspection frequency cycles would be more practical than having a special inspection conducted by a building inspector certified by the department. Bob noted the inspections are required to start during the fire inspections in calendar year 2011, and the department wants fire departments to have enough time to become ready for the inspections. Marty and Gregg suggested that training for the inspections could be included as a one- or two-hour session in a monthly, quarterly, or annual fire inspector meeting or conference. Bob noted the training could also address smoke detectors because of the combination alarms that detect both carbon monoxide and smoke. Marty recommended not having too much flexibility in how the inspections are performed, and that the department develop the training courses. Gregg suggested the department train the trainers, and that renewals be available through online transmittals. Bob noted that trainers of continuing education courses for other programs administered by the division typically are only required to inform thedivision of the attendees at a course. Terry questioned whether Act 205’s reference to the inspections being performed by “the department, or a building inspector certified by the department” means fire chiefs, as deputies of the department, can perform the inspections without becoming certified. Bob explained that advocates of the act wanted the inspections to be performed by knowledgeable inspectors. Terry questioned whether currently certified building inspectors would need further CO credentials and CO training, and Bob noted inspectors of new construction will need to be knowledgeable about the alarms. Gregg recommended the department approve or develop the curriculum for the training courses, and that all inspectors be required to attend, without any grandfathering. Terry noted any department-certified building inspector who is inspecting for proper CO installation and maintenance should be required to attend the same CO training and carry the same credentials that all fire inspectors will be required to do, without any grandfathering. The council agreed to table the CO training and certification discussion until their next meeting in December. Q&A for authority having jurisdiction Bob explained that staff are attempting to develop a Q&A for clarifying what is meant by the authority having jurisdiction (AHJ). One option may be to explain that the fire chief is the AHJ, and the department is the governing authority for Comm 14, while local governments are the governing authority for any locally adopted ordinances and additions to Comm 14. Terry suggested that following the NFPA track could consist of explaining that the department is the governing authority and the department’s deputies are the AHJ. Gregg suggested that the entity which adopts the NFPA requirements, such as the department, is the AHJ. Marty argued that local units, which perform the inspections, are the AHJ, and the department is the governing authority. Marty explained that this relationship also applies to the state-owned facilities which local units inspect through agreements for also providing fire protection services. Gregg preferred that option, provided it is established through an official statement from the department. Marty recommended establishing it through a code interpretation rather than a code requirement. Staff agreed to develop a draft Q&A with that interpretation, for the council to review. Local use of the fee schedule in Comm 2 Terry asked whether local officials can collect the fees that are specified in Comm 2, as referenced in section Comm 14.01(5). Bob noted Comm 2.001 states that the fees established in Comm 2 are to be paid either to the Safety and Buildings Division or to the Environmental and Regulatory Division, in the department. Marty said any local unit that wants to collect fees which are similar to the Comm 2 fees could adopt them through a local ordinance. There was interest in changing Comm 14.01(5) to be an informational note about the Comm 2 fees, which could be located under the informational note in Comm 14.01(3) that addresses the criteria in Comm 3, Petition for Variance Procedures Code, for obtaining a variance from the department. Christmas trees in assembly occupancies It was noted that the preceding criteria in Comm 14 for natural-cut Christmas trees have been replaced by the current rules in section 10.14 of the 2006 NFPA 1. Terry noted that according to the NFPA staff he has communicated with, section 10.14.2 by itself does not authorize local AHJ discretion to allow natural trees in the occupancies which are listed in NFPA 1 Table 10.14.1 as not permitted to have trees (assembly, board and care, detention and correctional, dormitories, educational, and hotels). According to that NFPA staff, section 10.14.2 deals with just combustible vegetation, not trees. (The explanatory text for section 10.14.2 in the 2006 NFPA 1 Uniform Fire Code Handbook cites examples of common combustible vegetation as including hay or straw, tree cuttings, flowers, leaves, and other decorative materials based on the particular season or holiday. The NFPA 1 handbook further states adequate safeguards might include sprinkler protection, limited quantities, moisture content, and placement.) Terry noted that the department has authority under Comm 14.01(2)(c) to issue an interpretation superseding any differing interpretation by an issuer of an adopted code or standard. NFPA staff have suggested NFPA 1 section 1.4, which addresses equivalencies, alternatives, and modifications, as being the appropriate section for dealing with AHJ discretion. Marty noted the preceding Wisconsin criteria had allowed natural cut Christmas trees in assembly occupancies, without any local approval, and were based on research by the Forest Products Laboratory in the 1960s. Marty noted that more recently, a 100-year-old church in Waukesha which was valued at $2.5 Million was destroyed by a fire that began with Christmas trees and boughs igniting. Bob indicated section Comm 14.01(2)(f) could be interpreted as enabling local officials to allow natural cut Christmas trees in assembly occupancies on a temporary-use basis. Marty and Gregg disagreed with that interpretation, by arguing that the references in this section to how a building is “used” are instead referring to the type of “occupancy” which the building has. According to Marty, disallowing natural cut Christmas trees in assembly occupancies is becoming less and less of an issue because insurance companies are increasingly either refusing to provide corresponding insurance or are charging substantially higher premiums where the trees are allowed. Gregg suggested that reinstating the preceding Comm 14 criteria as an emergency rule would be preferable to seeing legislation enacted which would allow the trees in assembly occupancies, without any local approval. Terry suggested removing or updating the information about Christmas trees which is currently posted on the department’s Web site and which refers to the preceding Comm 14 criteria. Next meeting - The next meeting was tentatively scheduled for the second week in December, and was projected to focus on credentialing inspectors of carbon monoxide alarms; Terry’s list of remaining unresolved staff issues; the 2009 edition of NFPA 1; and AHJ review of emergency plans, as specified in NFPA 1 section 10.9 and as prompted by the Department of Health Services under HFS 132.82(3). Staff from DHS are expected to participate in discussion of the emergency plans.
Wednesday,
August 6, 2008, 9 a.m. to 2:30
p.m., Thompson Commerce
Center, Room 3B, 201 West Washington Avenue, Madison,
Wisconsin
Thursday,
May 22, 2008, 9 a.m. to 2:30
p.m.; Thompson Center; Room 3B, 201
West Washington Avenue, Madison, Wisconsin Department
of Commerce Staff: Bob DuPont, Joe Hertel, Terry
Nolen, Sam Rockweiler. Thursday, March 22, 2007, 9 a.m. to 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: John Ashley - Present; Gregg Cleveland, Chair - P; Marty King - P; Dave Lind - P; John Periard - Absent; Jim Stormer (Todd Blaser, Alternate) - P Visitors: Tod Doebler - Menomonee Falls Fire Department; Dan Gengler - National Fire Sprinkler Association Department of
Commerce Staff: Bob DuPont, Joe Hertel, Terry
Nolen, Sam Rockweiler
Tuesday,
March 7,
2006, 9 a.m. to 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West
Washington Avenue, Madison, Wisconsin
Wednesday,
February 1, 2006,
9 a.m. to 2:30 p.m., Tommy G. Thompson Commerce Center, Room
3B, 201 West Washington Avenue, Madison, Wisconsin Tuesday, December 13, 2005, 9 a.m. - 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: John Ashley-Present; Gregg Cleveland, Chair-P; Marty King (Tod Doebler, Alternate)-P; Dave Lind-P; John Periard-Absent; Jim Stormer (Todd Blaser, Alternate)-P Guests:Ed Erickson-Marshfield Fire Department Department of Commerce Staff: Bob DuPont, Joe Hertel, Terry Nolen, Sam Rockweiler Gregg Cleveland opened the meeting
with a review of the
draft progress report
for the preceding, November 15th Council meeting. In
reference to
his recommendation on page 7 to apply any NFPA 1 design and
construction requirements that are not addressed in
Wisconsin’s
Commercial Building Code, and in reference to the corresponding
discussion on page 8 for the Note proposed in Comm 14.10, Dave Lind
noted his recommendation had also included applying any NFPA 101 design
and construction requirements which are not addressed in the
WCBC. Dave explained that his statement on page 4 about the
number of references in the International Building Code to the
International Fire Code was based on a count produced by NFPA staff.
Terry Nolen commented that (1) the first sentence in the last paragraph
on page 2, relating to AHJ duties and responsibilities, should also
have included reference to the authority having jurisdiction and the
governing authority; and (2) the second paragraph on page 3 relating to
doing a full comparison of the two model code suites should have
included reference to the Proposal C, the 2001 agreement between the
Department of Commerce and the Wisconsin Fire Service.
Department
updates
Alternate use of the IFC: Bob Dupont reported the Department is considering whether to discontinue the current option in Comm 14 that allows municipalities to adopt IFC requirements in lieu of NFPA 1. Gregg emphasized that the Council remains opposed to continuing the option. Mandating fire sprinklers in student housing: Proposed Assembly Bill 544, which would expand the range of new and existing student housing that must be protected with fire sprinklers, was reported as being passed by the Wisconsin Senate, with an eight-year period to achieve compliance in existing buildings. Fire sprinklers in all new R-2 occupancies: Bob reported that the Department’s Building Code Fire Protection Systems Advisory Council has recommended not modifying the 2006 IBC requirement to provide fire sprinklers in all new R-2 occupancies. Bob explained that the Wisconsin Builders Association has responded with a written opinion from their legal counsel stating that the Department is prevented from adopting that requirement because that requirement would be more restrictive than the thresholds in the Wisconsin Statutes for providing sprinklers in multifamily dwellings. According to Bob, the Department disagrees with that opinion, and plans to discuss the topic further with its Commercial Building Code Council and Multifamily Dwelling Code Council at a January 2006 meeting. Corresponding cost data and insurance rate comparisons are being compiled for that discussion. Bob said the Statutes do not prohibit the Department from adopting more restrictive sprinkler thresholds. He added that the Department has previously relied on its general authority to make buildings safe, through administrative codes, in adopting requirements for safety glazing and for smoke detection equipment that also are more restrictive than corresponding statutory criteria. Terry suggested that if a corresponding Department legal opinion is generated, it should also address preexisting local sprinkler ordinances which are more restrictive than the State-level statutory thresholds.
December
9th updated draft rules for repealing and recreating Comm 14:Sam
Rockweiler led discussion of the updated draft rules and corresponding
summary for repealing and recreating Comm 14, which were e-mailed to
the Council on December 9th. John asked whether Department interpretations are issued by different Department staff than the staff that provide routine explanations. Bob responded that explanations typically come from plan reviewers and inspectors, and issuance of formal interpretations has ranged from the bureau-director level, to the Division Administrator, to the Department Secretary. Dave recommended narrowly focusing each building or fire code Q&A, or other written interpretation, on a specific topic or subcategory, and posting that information together in one location on a Commerce Web site, with a corresponding link on each of the Web sites for individual programs in the Safety and Buildings Division. Terry agreed with deleting the reference in Comm 14.01 (2) (b) 4. to having Comm 61 to 65 prevail over any differences in Comm 14. However, difficulty still remains in determining which NFPA requirements are considered as addressing design and construction, and which are considered as addressing use, operation and maintenance. John questioned whether building owners should consider hiring private-sector inspectors to audit buildings in order to address the building owners’ responsibility to maintain their building and premises in compliance with Comm 14. There was recognition that this compliance does not relieve the owner from complying with the other administrative rules established by the Department or other state agencies. Dave generally agreed that such audits can be helpful, and he recommended that they focus on risk analysis. According to Dave, some fire departments are performing home inspections upon request, and are then making suggestions rather than looking for and citing code violations. Dave recommended expanding the list
of occupancies
in Comm 14.01 (10) (b) 5. that are eligible for a
once-per-calendar-year inspection frequency, to address seasonal
occupancies, and to require inspection of those occupancies during an
occupancy period. There was recognition that the purpose of a
fire prevention inspection has been established, but the terms fire
prevention inspection, fire inspection or inspection have not been
defined for purposes of applying the inspection-frequency
language. Bob noted the inspection frequency in subdivision 5
should also apply to first-class cities in subdivision 4, and where the
local ordinances for annual inspection in subdivision 6 are
adopted. Dave noted that the proposed frequency in
subdivision 6
would allow nearly 2 years between inspections, and there was agreement
that no more than 12 months should occur between those
inspections. There also was agreement that the frequency in
subdivision 6 should be recognized in subdivision 3 as being an
exception to the inspection frequency required in subdivision 3. Dave questioned whether the criteria in Comm 14.65 (2) for layout of mixing plants would be considered design and construction requirements. According to Bob, these criteria likely repeat corresponding requirements in the 2006 IBC, and if so, they will be deleted. Staff will likewise review the remaining criteria in 14.65 to determine whether further deletions are appropriate. Dave questioned whether the preliminary text in Comm 14.001 for the IFC should be an informational note instead, and should identify the IFC sections, rather than chapters, that must be adopted locally if the IFC is chosen in lieu of NFPA 1. Bob responded that refinement of this text has been withheld, pending the outcome of internal reconsideration of the IFC option. NFPA summary of changes in the 2006 NFPA 1/UFC: Bob asked whether the previously distributed NFPA summary of changes in the 2006 NFPA 1 illuminated any new requirements that could create difficulties. Dave explained that where an assembly occupancy load exceeds 250, an additional crowd manager is needed for each additional quantity of 250, whereas the previous threshold was 1000. John indicated that this change likely would not create difficulties. Dave also explained that the 2003 NFPA 1 newly required a notification explaining where emergency exits are located, prior to the start of a performance, and the 2006 NFPA 1 better coordinates that requirement with the crowd-manager requirements. There was reference to further description of crowd-management guidelines, factors, and techniques, in the Society of Fire Protection Engineers’ Handbook of Fire Protection Engineering, Section 3, Chapter 13. Gregg asked whether “authority having jurisdiction” and “deputy of the Department” would have the same meaning under the proposed revision of Comm 14. Sam Rockweiler explained that the two terms would not always have the same meaning: for example, on State-owned property, the State, rather than a local official who is a deputy of the Department under section 101.14 (2) (a) of the Statutes, would be the authority having jurisdiction. There was reference to the use of “the AHJ designated by the governing authority” in NFPA 1 section 1.6. Gregg questioned whether placards would be newly required under NFPA 66.2.5.2.1 for identifying hazardous liquids in tanks. Tod Doebler noted these placards are not currently required under Comm 10. Dave asked whether the NFPA 1 requirements for retail sales of fireworks would be included in the revised Comm 14. Bob said they would, except where they address design and construction. Staff list of issues that remain to be addressed by the Council: Terry distributed an updated staff list of color-coded issues that remain to be addressed by the Council. Terry explained that many of the issues were not addressed in the 2000 NFPA 1, as currently adopted in Comm 14, but are reasonably addressed in the 2006 NFPA 1 and the 2000 IBC, particularly for spray booths, and interior and exterior storage of combustibles. However, the main continuing difficulty relates to determining whether an NFPA 1 requirement addresses design and construction rather than use, operation and maintenance. Dave recommended not trying to resolve this difficulty by developing a definition of design and construction, and a definition of use, operation and maintenance. Terry recommended further discussion in order to eliminate conflict, confusion and uncertainties about whether the fire or building codes would apply. An example cited was barns that are converted to seasonal storage for boats or cars which are not owned by the barn owner. Terry commented that the most important topic to consider on the staff list of issues is whether to reinsert an informational note into the Commercial Building Code for explaining that building inspectors and fire inspectors share enforcement of that Code. Gregg commented that the preceding edition of the Code included a similar note, along with an Appendix list of code sections that were particularly related to fire inspections, and both the note and the list were very helpful. Dave agreed, and said the note gave fire inspectors a higher level of credibility. Terry indicated that by not having the note and corresponding list of code sections, local deputies and fire inspectors are less aware of what to look for in inspections. There was discussion that a corresponding list of code sections should be developed for training purposes and reinserted into the Commercial Building Code and Fire Code. Gregg noted interesting identifying examples of design and construction requirements in NFPA 1. Dave said that if he receives a copy, he would compare the 2006 IBC to the 2006 NFPA 1 and 101, to identify design and construction requirements which are in NFPA 1 and 101 but not in the IBC. Next meeting: The next meeting date was scheduled for February 1, at the same location and for the same time period (9 a.m. - 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin), and was projected to include (1) discussion of an updated draft of revised Comm 14 and (2) discussion of remaining unresolved issues, including the National Fire Incident Reporting System. Monday, November 15, 2005, 9 a.m. to 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council member attendance: John
Ashley Present;
Gregg Cleveland (Chair) P; Marty King P; Dave Lind P; John Periard
Absent; Jim Stormer (Todd Blaser – Alternate) P
Draft
progress report for the preceding meeting
In reference to the
report’s description of draft revisions to
Comm 7 and 9 for explosives and fireworks, Gregg asked whether the
corresponding chapter 65 in the 2006 edition of NFPA 1/Uniform Fire
Code would be included in the Comm 14 adoption of the 2006 NFPA
1. Bob said it would, and that a few Wisconsin modifications
may
be made to chapter 65, such as clarifying in a Note that any associated
fire inspections by fire inspectors would not be a substitute for the
corresponding licensing and permitting requirements which are
administered by the Department’s Mine Safety Section. Gregg commented that the report should have addressed discussion about a local jurisdiction’s duty to correct; properly citing code sections in correction notices and orders; issuing reports to owners where no violations are found; enforcement referral options, as a department deputy, where no local fire prevention ordinance has been adopted; and discussion about developing a definition for “use, operation and maintenance.” Terry Nolen noted that discussion of the fire inspection frequencies in Comm 14.47 (2) (c) and (d) was not addressed as well. A motion was made by Dave Lind,
seconded by Todd Blazer, and passed
unanimously, to accept the October 18th progress report, as amended
through the November 15th discussion. Dave commented that the fire service coalition has never wavered in preferring NFPA 1 over the IFC, and that needs of the many should outweigh needs of the few - but the minority of municipalities which have adopted the IFC are causing disruption across the State, such as for school districts that span multiple municipalities having different fire codes. According to Dave, some fire inspectors in the 15 municipalities that have received a special order under Comm 14.004 (1) (b) to use the IFC are not applying the IFC in accordance with the conditions and limitations of the special order. The IFC special order contains the same restrictive parameters found in Comm 14, including Subchapter III, and some of those municipalities are applying NFPA 1 in lieu of the IFC. Some of the 15 municipalities are misapplying their IFC ordinance by extending it retroactively for design and construction requirements, and misapplying it by conflicting with the required uniformity for multifamily-dwelling occupancies. Others are applying the IFC incorrectly in part because the Department is not providing administrative and educational assistance with that Code, as the Department is providing with NFPA 1. Dave added that building owners generally do not want to oppose a fire inspector’s misapplication of code requirements, but some owners now realize that they are being treated differently than the other eighty percent of the State’s population. Reference was made to the Department’s official code interpretation [dated May 27, 2003] relating to a municipality’s simultaneous use of the IFC and NFPA 1. Bob commented that the proposed revisions to Comm 14 would replace applying the IFC through a Department special order, with simply applying the IFC through a local ordinance, and this ordinance could include applying portions of NFPA 1, as modifications of the IFC. Dave indicated such ordinances should instead apply any desired IFC elements as modifications of NFPA 1. Many municipalities desire the more restrictive, regulatory layered effect, to achieve a policy of the safest rule, rather than being restricted to the State’s minimum codes. According to Dave, the International Building Code contains 38 [actually 65] references to the IFC, and the National Fire Protection Association has addressed each of those references, in NFPA 1. Gregg agreed that municipalities can
adopt what
they want without having a State code acknowledge that
ability.
He questioned why Comm 14 is singling out promotion of the IFC, and he
commented that no other Department code allows this kind of alternative
option. Gregg inferred that this alternative fire code
promotion
is intended to advance an agenda of moving toward adopting the IFC, in
place of NFPA 1, in Comm 14. Dave asked why a Department Fire
Prevention
Coordinator is handling the project rather than the Department of
Public Instruction, and Bob explained that the Statutes require
submitting the reports to the Department of Commerce. Dave
noted
concern that fire departments could be portrayed as being
delinquent. Terry referenced the corresponding handouts from
the
May 5 Council meeting and a preceding Department brochure on the topic,
which could be updated and reissued. Dave recommended
expanding
the dialog between Sue and DPI, and encouraging local school districts
to contact their fire departments accordingly. Bob said he
would
pursue the topic further with staff and report back to the Council, and
implementation of the outcome is targeted for the beginning of the next
school year. Consistent with the earlier
discussion, Gregg
recommended revising the proposed audit-appeal process in Comm 14.01
(11) (f) to reflect completion of the process by August 1 each year, in
order to be consistent with section 101.573 (3) (a) of the
statutes. Bob asked whether the draft text should be expanded
to
refer to the appeals board holding a hearing for an appeal.
Sam
commented that an appeal could be based on either oral or written
testimony; and the rule could be clarified to reflect that an appellant
could request a hearing, in order to present oral testimony.
Gregg recommended clarifying the included listing of board-member
representation, to reflect full representation from each of the listed
categories. There was agreement that the included deadline
for
the board to complete its action on an appeal should be revised to
allow extension of that deadline, through mutual consent of the
appellant and the board.
Tuesday,
October 18, 2005, 9 a.m. to 2:30 p.m., Thompson
Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin
Fire
Audit Appeal Process
Comm 7, Comm 9
and NFPA 495
A question was raised in citing violations relative to explosives whether the citation should reference Comm 14.65, NFPA 1 or NFPA 495 and the proper format. Staff will research the matter and report back.
Unresolved Issues
Miscellaneous
Updates:
Comm 14 Draft
The next meeting
was reaffirmed for Tuesday, November 15 and a subsequent meeting
scheduled for Tuesday, December 13. Monday, September 12, 2005, 9 a.m. - 2:30 p.m., Thompson Commerce Center, Room 3C, 201 West Washington Avenue, Madison, Wisconsin Council member attendance: John Ashley Present; Gregg Cleveland - Chair P; Marty King P; Dave Lind P; John Periard Absent; Jim Stormer A. Guests: Tod Doebler - Menomonee Falls Fire Department Department of Commerce Staff: Bob DuPont, Joe Hertel, Terry Nolen, Sam Rockweiler; Jim Smith. Gregg Cleveland opened the meeting
with a review
of the agenda and a round of introductions. In reviewing the
draft progress report for the preceding, August 8th Council meeting,
Terry Nolen and Dave Lind agreed that the recommendation on page 5 to
expand the Wisconsin Enrolled Commercial Building Code to include any
design and construction requirements from the International Fire Code
which are applied directly or indirectly through Comm 61 to 65, should
have also included putting these requirements into the Wisconsin
Enrolled Fire Prevention Code. According to Terry, the
recommendation was originally made due to the fact that the Department
Secretary had decided to stay with the adopted International Code
Council (ICC) codes and their included references to the IFC for design
and construction. The Council accepted the progress report,
based
on Terry and Dave’s agreement. Monday, August 8, 2005, 9 a.m. - 2:30 p.m., Thompson Commerce CenterRoom 3C, 201 West Washington Avenue, Madison Wisconsin Council member Attendance: Gregg Cleveland - Chair (Dave Lind - Alternate Present; Ken Cole Excused; Marty King (Tod Doebler - Alternate P; John Periard Absent; Jim Stormer Absent. Guests: Dave Bloom - Town of Madison Fire Department Department of Commerce Staff: Ron Acker; Bob DuPont; Joe Hertel; Terry Nolen; Sam Rockweiler; Jim Smith. Dave Lind opened the meeting with a review of the agenda. In reviewing the draft progress report for the preceding, June 16th Council meeting, Terry Nolen noted that not all of his comments relating to fireworks safety were included in the report, and he requested that the correction be included in the next progress report for publication and archive purposes. Terry emphasized that the Department and any deputy has the authority to ascertain and cause to be corrected any condition liable to cause fire, or any violation of any law or order relating to the fire hazard or to the prevention of fire. Terry noted that the State Fire Prevention Code, Comm 14, has adopted the 2000 NFPA 1 Fire Prevention Code. NFPA 1, in Chapter 16-10, deals with the sale, handling, and storage of consumer fireworks. Terry said that the ERS Division management and its legal counsel had earlier ruled that this NFPA 1 rule, after deletion of the permit text there, is not in conflict with section 167.10 of the Statutes. Terry said that the Wisconsin Fireworks Law originated in 1929, and that the current law very clear for those who routinely work with it. Public misunderstanding stems from the lack of adequate fireworks safety information reaching the public, inconsistent enforcement by state and local authorities, and misinformation coming from the fireworks industry and temporary fireworks stands.
The Council accepted the draft progress report for the June 16th meeting, after agreeing that the fireworks-safety discussion at that meeting also included a reference to prior assurance from the Department that the criteria which remains in 2000 NFPA 1 section 16-10 after deletion of the permit text there does not conflict with section 167.10 of the Statutes.
Department
updates Notifications for the Comm 7, 9, 40,
and 45 Councils Ron Acker distributed and discussed an August Scope Statement for updating Comm 7 and 9, and explained that the previous update for Comm 9 did not include input from an advisory Council. Dave asked whether the update of Comm 9 would address fireworks sales and permitting, and Bob responding that this topic would be included in the Comm 14 review of NFPA 1. Dave emphasized that tightening the requirements for shooters of fireworks is needed due to incompetence and accidents, and there are corresponding restraint-of-trade concerns. Training for upcoming audits Timely resolution of any appeals may be needed due to the annual, statutory June 30 deadline for allocating the funding from the 2-percent dues. Dave suggested holding any contested funding in abeyance to avoid the restrictions from the June 30 deadline. Terry indicated this abeyance would not be an option for a funding denial that is being appealed, because under section 101.575 (1) (am) of the Statutes, the Department must still pay the dues for that calendar year to the municipality, and must issue a notice of noncompliance to the chief of the fire department, the governing body, and the highest elected official of the municipality. If, after one year or by the time of the next audit of the fire department, whichever is later, it cannot be demonstrated to the Department that the statutory requirements have been met, then the municipality would be ineligible to receive fire dues for that year and any subsequent years until the statutory conditions have been satisfied. Dave asked whether a fire department that fails an audit one year will then be moved to the top of the list for field auditing by a Fire Prevention Coordinator in the following year.Bob and Terry responded yes, and explained that implementation of the substantial-compliance process from 2003 Act 219 should avoid having an unwieldy number of fire departments assigned to that priority auditing. Terry commented that the new substantial-compliance audit process will likely result in no appeals rising to the appeals board. However, the difficulty for the Fire Prevention Coordinators may be in finding out the details behind a local self-certification of noncompliance, and then helping to rectify the problems before August 1 of the second year. Bob noted that the Fire Prevention Coordinators could visit those noncomplying fire departments sooner than before the next scheduled annual Department audit. Terry emphasized that those fire departments needing assistance should contact their Fire Prevention Coordinator, and Bob added that any self-certification of noncompliance should be followed up with a Departmental offer to help. According to Terry, for some fire departments, the funding from the 2-percent dues is too little to justify much effort by those departments and municipalities to comply. Dave Lind questioned whether the upcoming 2-percent-audit presentation at the fall conference for fire inspectors could be expanded to include common questions and answers. Dave also questioned whether there would be any corresponding communication with the municipalities. Terry responded that a list of frequently asked questions and resulting Department answers had been compiled from the audit training, and could be made available for the presentation. Bob noted that the Department has posted corresponding information on a 2-percent-audit Web page, and a related mailing will be sent to municipal associations in the near future. Dave suggested recording all the Department presentations on a compact disc that could be included in the conference packet for each inspector, and he recommended discussing further plans for the fall conference at the next Council meeting. Timeline for adopting the 2006 NFPA
1/UFC Dave recommended that if NFPA 1 regulates a design and construction topic for the purpose of prescribing the minimum requirements necessary to establish a reasonable level of fire safety and property protection from the hazards created by fire and explosion - and if that topic is not addressed in the International Building Code, as adopted in Comm 61 to 65, then there should be consideration of whether to apply the NFPA 1 criteria in Wisconsin. Bob responded that the forum for that consideration should be in the discussions for updating Comm 61 to 65 rather than the discussions for updating Comm 14, and those discussions for Comm 61 to 65 should focus on the 2006 version of the IBC. There was discussion that Building Code references should be made to NFPA 1 instead of the International Fire Code. It was noted that the Fire Code Council previously passed a motion to eliminate the option in Comm 14 to locally adopt the IFC in lieu of applying NFPA 1. There also was discussion that the most restrictive fire-hazard design and construction rule in either NFPA 1 or the IFC should apply. Dave recommended that any design and construction requirements from the IFC which are applied directly or indirectly through Comm 61 to 65 should be included in the Wisconsin Enrolled Commercial Building Code. Bob reported that the Department Secretary has decided to stay with the adopted International Code Council (ICC) codes and their included references to the IFC for design and construction. Dave recommended that any local governmental units which want to apply the IFC instead of NFPA 1 for use, operation, and maintenance should do so through a local ordinance rather than through an option specified in Comm 14. Comm 14 would then be a uniform fire code, by including only NFPA 1. Terry commented that under section 101.14 of the Statutes, the Department should be providing local fire departments with all the tools which are needed – including training, manuals, and other materials and services – to perform the activities that the Department expects from local units. According to Terry, too much confusion is occurring when determining whether any particular NFPA 1 rule relates to design and construction and is therefore superseded by Comm 61 to 65 – or whether the rule relates instead to use, operation, and maintenance, which is addressed by Comm 14. Terry noted that Comm 14.003 (1) (a) 2. and (2) (d) are the current rules causing most of the conflicts with fire code users. Bob asked whether eliminating the most restrictive reference in Comm 14.003 (2) (a) would help eliminate some of the Building and Fire Code conflicts. There was discussion that this would be a step in the right direction. Bob agreed the Department should attempt to provide further guidance on this topic. Jim Smith questioned whether keeping the approved construction documents at the site, in a controlled-access location, would help. Dave agreed it would, and said those documents should also include any State-level letter of approval specifying the conditions which are part of any conditional approval of a plan or variance. There was agreement that for local-level requirements which are imposed in addition to State-level requirements, the local governmental unit is the Authority Having Jurisdiction, as this phrase is used in NFPA 1. There was interest in having the Department develop further guidance on the AHJ topic, especially from the perspective of how this phrase would affect or be utilized by a Department deputy, certified agent, or authorized representative of the Department.
Requirements
that would be applied by 2003 NFPA 1/UFC
There was agreement that an unfunded mandate would result if Comm 14 is changed to no longer delete the local permits which are required in NFPA 1. Bob asked whether any of the new requirements in NFPA 1 chapter 65 would create problems. It was noted that the conflict about design and construction versus use, operation, and maintenance would be a factor in this topic. Dave questioned whether the criteria in sections 65.11.4 (1) and (2), which address the buildings or structures where fireworks can be sold, would be interpreted as design and construction requirements. Bob noted that the criteria could instead be interpreted as allowing this use in a building or structure which already exists and complies with these sections. There were questions on how Comm 61 to 65 and NFPA 1 chapter 65 would apply to permanent buildings versus temporary use of buildings. Jim Smith explained that the current criteria in Comm 61 to 65 allows local latitude for temporary uses, such as for seasonal fireworks sales. Dave asked whether these NFPA criteria would be lost if they are more restrictive than corresponding criteria in Comm 61 to 65, and Bob said they would, but the 2006 IBC should be reviewed before the next Council meeting to verify whether anything would be lost. There was interest in similarly reviewing the criteria for exits in section 65.11.8.3, and in clarifying how a permanent or temporary, hazardous use would be classified. Dave recommended reviewing all of sections 65.11.4 to 65.11.10.3.7.3. If the 2006 IBC adopts and applies all of NFPA 1124, then the IBC likely will not be dissimilar to those sections. Dave asked whether Comm 7 and 9 would then continue to be needed. Ron Acker said Comm 9 could be reduced to a small number of requirements for administration, recordkeeping, and reporting; but Comm 7 has additional technical requirements beyond NFPA 495. Ron referred to a comparison he had done between Comm 7, Comm 9, NFPA 495, and NFPA 1124; and he said that Comm 8 is basically a training chapter for mines, pits, and quarries. Bob noted that Comm 9 could be merged with Comm 7. Remaining chapters of 2003 NFPA 1 Dave recommended keeping all of chapters 2 and 3. Dave commented that section 4.5.1.2 may be too broad in allowing the Authority Having Jurisdiction to create and impose requirements which are not included in NFPA 1. Terry said the rule would be limited by the purpose, scope, and application sections of Comm 14 and NFPA 1. The burden would be on the AHJ to demonstrate that the added requirements are essential for the safety of the occupants, protection of the structure, or protection of the contents. Terry said that based upon the original intent of the NFPA 1:4.5.1.2. code rule proposal [NFPA Report on Proposals] the Department’s field staff did not object to this rule. There was agreement that chapter 4 should be adopted. In reviewing the performance-based design criteria in chapter 5, Dave said the review requirements in sections 5.1.4 and 5.1.5 would not be a problem if the Department performs the reviews. Bob said those sections are deactivated by the code-application criteria in Comm 14.003 (1) (b). Dave suggested modifying Comm 14.003 if needed to retain any desired criteria in chapter 5, such as those in section 5.4.2.1.1 for an occupancy-specific fire design scenario. Bob agreed that chapter 5 should be reviewed in more detail. Dave suggested adding an informational note for alerting readers that Comm 61 to 65 supersedes all of the design and construction requirements which are included in the reference under section 10.1.2 to complying with NFPA 101, Life Safety Code There was agreement to retain all of the fire-drill requirements in section 10.6. There was tentative agreement that the signage requirements in section 10.13 would not conflict with Comm 61 to 65 and should be retained. There was agreement that the criteria in section 10.14 for vacant buildings should be retained, and that these criteria do not conflict with the criteria in section 66.0413 of the Statutes, for unsafe buildings. Terry commented that Fire Code users commonly confuse vacant buildings with dilapidated or unsafe buildings. Terry said that NFPA 1 treats each category as a separate aspect of a building’s fire safety condition and status. There was agreement that the criteria in section 10.15.2 for allowing limited quantities of combustible vegetation should provide adequate latitude for using Christmas trees in churches and similar occupancies. After brief discussion of permanent wiring that is abandoned in place, temporary wiring, and elevator upgrades which include new firefighter elevator recall service, there was agreement to retain all of the remaining criteria in chapter 10, and all of the criteria in chapter 11.
Next
meetings
Terry requested further clarification on the decision by the Department Secretary to stay with the referenced IFC for fire-hazard design and construction instead of referencing the NFPA 1 Uniform Fire Code. Terry questioned why the IFC is being retained, if NFPA 1 is equivalent for fire-hazard design and construction. Bob said some of the reasons are that the designers, builders, and architects are now accustomed to using the ICC codes, and the code sections and numbers correlate better. Terry stated the same could be said for the correlation of the NFPA model code suite code sections and numbers. Terry said by referencing the NFPA 1 Uniform Fire Code instead of the IFC, many of the current conflicts could be avoided. Todd Doebler commented that just as the Department has made efforts to assist designers by not applying the design and construction requirements in NFPA 1, Departmental efforts should also be directed to assisting fire inspectors by minimizing modifications of NFPA 1. Bob said he is ready to advance the remaining 2003 NFPA 1 requirements to public Hearings, without further review. There was agreement that the next Council meeting should include further review of (1) subchapters IV and V of Comm 14, (2) chapter 65 of NFPA 1 for design and construction equivalence and maintenance of existing buildings constructed under the preceding Commercial Building Code - Comm 50 to 64; (3) subchapters I and II of Comm 14, and chapter 1 of NFPA 1; and (4) subchapter III of Comm 14, for any modifications or additions to definitions, and review of missing 1999 code items. Prior to the meeting, the Council should receive a summary of what has been reviewed in subchapters IV and V of Comm 14 to date - and what has been identified as needed, such as review and clarification of (1) inspection frequencies and exceptions; (2) the corresponding special orders from the Department, and their process and limitations; (3) the enforcement process and fire inspection reports to owners; and (4) the audit appeals board and its representation and procedures. Bob suggested that the requirement to request special orders be replaced with a codified process which includes more community involvement and local governmental action. Dave raised concerns with this concept and referenced a similar situation in his fire district where a local public hearing produced undesirable results. The next meeting was reaffirmed for September 12, at the same location and time period as the August 8 meeting.
Thursday,
June 16, 2005, 9 a.m. - 2:30 p.m., Thompson Commerce
Center, Room 3C, 201 West Washington Avenue, Madison, Wisconsin Department updatesSurplus State computers As a follow-up to the corresponding discussion at the May 5 meeting, Bob DuPont reported that concerns had arisen over giving surplus state computers to fire departments for use with the National Fire Incident Reporting System. Some of the departments may be nonprofit organizations, and giving those departments the computers could be considered by other nonprofits as unequal preferential treatment. Giving the computers to municipalities that are associated with the corresponding fire departments might resolve the concern. Terry Nolen reported that an updated tally of his district shows the number of fire departments which do not have computers has declined substantially. Notifications for the Comm 7, 9, 10, 40, and 45 Councils and Committees As a follow-up to the corresponding discussion at the May 5 meeting, Bob reported that notifications of the applicable pending changes to Comm 14 would be sent to the members of the Comm 7, 9, 40, and 45 Councils and to the nominating organizations for those members, prior to the next meeting of the Comm 14 Council. Sam Rockweiler explained that the notification to the Comm 10 Committee would likely be in conjunction with a committee meeting which is expected to occur after an upcoming public hearing for changes to Comm 10. Gregg suggested including a 45-day response deadline in the notifications. Bob agreed and indicated that any significant concerns in the responses would be discussed with the Comm 14 Council. Terry recommended emphasizing in the notifications that any responses should focus on concerns related to fire and explosion, because that is the focus of Comm 14 and the NFPA 1 Fire Prevention Code which is adopted therein. The purpose of Comm 14 is to protect the public, employees, firefighters, and property from the hazards of fire and explosion by establishing minimum standards for the use, operation, maintenance, and inspection of buildings, structures, and premises. The purpose of NFPA 1 has been to prescribe minimum requirements necessary to establish a reasonable level of fire safety and property protection from the hazards created by fire and explosion. In the 2003 NFPA 1/UFC, this purpose was expanded to also address life safety and dangerous conditions. Dave Lind suggested getting a commitment from the Comm 10 Committee to review the corresponding portions of the 2006 edition of NFPA 1. Sam Rockweiler explained that having that commitment instead from the Department may be more appropriate. Emergency access windows Joe Hertel distributed pages B-26 to B-28 and B-154 from the Wisconsin Enrolled Commercial Building Code, which specify where emergency access openings are required. Joe reported that concerns have arisen about whether these openings will become blocked by furniture or similar items, and a fire inspector has suggested creating warning labels for these openings. These labels could be similar to the labels that have been created for fire doors, and there may be interest in funding the labels from the 2% dues. Dave and Gregg noted that placing the labels within private dwellings could be enforced only at the time of construction, because any subsequent inspection access into those dwellings is specifically not authorized by the statutes. Consequently, the labels may not remain in place, particularly as occupants change or when windows are upgraded or replaced. Dave indicated that using 2% dues for funding the labels would not fall within any of the uses authorized by the statutes. Dave suggested that the openings be earmarked during plan review instead. May 2005 Legislative Audit Bureau Report for the Multifamily Dwelling Program Bob reported that the LAB audit occurred because the statutes require it on a periodic basis, and he explained that the audit focused on plan reviews for multifamily dwellings. The report recommended that the Department implement better internal mechanisms for refunding half of the plan review fee whenever a review is not completed within 15 days of submitting the plans. Bob explained that the code text which requires the refund was adopted prior to implementing the current process of scheduling appointments for plan reviews, and this code text may need to be revised to better reflect the appointment process. Gregg indicated his primary concerns with the audit are that it did not address any fire safety issues and that it was slanted in favor of economics and developers, instead of focusing on a dilution of national standards which has occurred in the corresponding code requirements. Bob commented that the statutes do not preclude the Department from adopting sprinkler thresholds which are consistent with national standards but are more restrictive than the thresholds in the statutes. Gregg suggested that the Council inform the LAB co-chairs in writing that (1) where a national-level code is adopted, it should not be weakened, especially for economic reasons; and (2) the statutory prohibition against more-restrictive local sprinkler ordinances should be repealed. The Council agreed that Gregg should write the letter and send it with his signature. Gregg noted there have also been efforts to relax fire department access requirements, in conjunction with addressing stormwater issues. For further demonstrating the effectiveness of sprinklers, Bob suggested scheduling a fire-sprinkler demonstration trailer at a joint meeting of the Commercial Building Code Council and the Multifamily Dwelling Code Council, and at a meeting of a corresponding legislative committee. Bob emphasized the effectiveness of using water that is already supplied to a building, to fight a fire in the building - and he noted that the support from the fire service for the effectiveness of fire sprinklers was instrumental in the recent enactment of legislation requiring sprinklers in all newly constructed University of Wisconsin dormitories. Terry questioned whether the issue of standard limitations on sprinkler thresholds will become outdated, because the statutes do not preclude the Department from adopting sprinkler thresholds that are consistent with national standards. Bob responded that if the public wants sprinkler protection in more buildings, builders will provide it. Fireworks Safety Joe distributed excerpts from section 101.14 and chapter 167 of the statutes, along with an NFPA Web site notice that discusses a national movement toward prohibiting consumer fireworks. Joe also distributed an April 2004 letter from the Department that summarized the local-only permit process in chapter 167, and the Department’s corresponding authority under section 101.14 and chapter 167. Dave said state-level enforcement should be increased, particularly in only allowing consumer sales that comply with the statutorily recognized exceptions to the permit process, such as sparklers. Joe said the Department does not have any authority under chapter 167 of the statutes to enforce restrictions on sales of fireworks. Terry replied that the Department and any deputy have authority under section 101.14 (1) (b) of the statutes to ascertain and cause to be corrected any condition that is liable to cause fire, or any violation of any law or order relating to the fire hazard or to the prevention of fire. Bob commented that reviewing the topic would be timely, in conjunction with updating Comm 14 to include the 2006 edition of NFPA 1. Bob explained that this updating includes looking at a broad range of fire-safety issues, not just fireworks; and the Department may be able to regulate sales of fireworks by using its fire-prevention authority in chapter 101 of the statutes, to adopt the corresponding NFPA 1 requirements in Comm 14. Dave suggested that a written notice from the Attorney General’s office could assist local efforts in promoting fireworks safety. Terry said that the Wisconsin Department of Justice had issued a 2005 summary overview of the Wisconsin laws for fireworks. Terry also referenced a similar overview document released in 2002 by the Wisconsin Legislative Council. Terry noted that other state fire marshal offices commonly issue fireworks informational sheets and press releases, and Bob suggested that the notice could be sent to the Wisconsin Insurance Alliance, the Wisconsin Towns Association, the League of Wisconsin Municipalities, and the Wisconsin Alliance of Cities. Terry said that 2003 Wisconsin Act 298 has been helpful to municipalities because it has relieved them from any civil liability associated with issuing a permit to purchase or use fireworks. Terry noted that Wisconsin legislation for fireworks originated in 1929, and the current law is confusing and not very clear. He added that fireworks-safety information and corresponding enforcement has been applied inconsistently by state and local authorities in the past; and he referenced a scope statement that the Department previously issued for beginning a review of the topic and to address the inconsistencies. Dave recommended that the requirements which are imposed on professional shooters of commercial fireworks should be similarly applied to sales of those products. Bob said that targeting sales of fireworks is difficult due to the interstate aspects of the market. Gregg asked for the basis of previous notices from the Department of Justice that any consumer fireworks which are propelled after being ignited are illegal. Terry said that interpretation had been issued by an employee who is no longer with DOJ; and that the current interpretation is that fireworks are prohibited except where a permit is issued for their use, or except for the products which are statutorily listed as exempt from permitting. Dave said the current permitting process is so loose that it is ineffective. Terry indicated the current requirements are widely misunderstood - and discussion, education, and dissemination of information on the Wisconsin laws for fireworks is needed to establish reasonable levels of understanding and protection under sections 101.14 and 167.10 of the statutes. Gregg noted there is consensus that something needs to be done, and that there is some enforcement authority under section 101.14. Dave emphasized that the applicable rules should be stiffened in time for the 2006 fireworks season, such as by at least adopting the corresponding requirements in the 2000 edition of NFPA 1. Joe asked who would enforce the stiffened rules. Dave commented the biggest loophole is in the permitting process, and therefore buyers should have to demonstrate compliance with the requirements for professional shooters in NFPA 1123. Dave added that the scope of Comm 14 should be broadened for fireworks, to apply to more than public buildings and places of employment - similar to how it is currently being broadened for flammable, combustible, and hazardous liquids. Bob suggested considering whether to prohibit the sale of fireworks, except for the exempted products, to anyone who is not appropriately licensed by the Department. Dave recommended specifically informing the Department’s advisory councils for Comm 7 and 9 that the Department is considering tightening the requirements for sale and display of fireworks, along with licensing of sellers or buyers. Terry circulated the following fireworks documents: (1) Special Committee staff brief Review of Wisconsin Fireworks Law, as authored by the Wisconsin Legislative Council; (2) Fireworks in Wisconsin, 2005, as authored by the Wisconsin Department of Justice; (3) 2003 Wisconsin Act 298; and (4) 1999 Comm 14 Scope Statement, for fireworks storage, handling, and use. Requirements that would be newly applied by 2003 NFPA 1/UFC Bob distributed a tabular listing of the topics that are newly addressed in 2003 NFPA 1. The table also listed the 2003 chapters where the topics are addressed, and it included cross-references to any chapters in the 2000 edition of the International Fire Code (IFC) that have similar requirements. According to Bob, much of the new criteria has been previously applied in other states – through other model fire codes – and the criteria generally are recognized as the best ways to address the various topics. Bob explained that incorporating this specificity in Comm 14 should provide uniform guidance at the local level, which should reduce blindsiding from unexpected requirements and the consequent negotiations that can then be needed to achieve compliance with those requirements. Use of such standards that are applied broadly across the country also allows more bidders to compete on individual projects. Ken Cole commented that the current prevailing political philosophy is that more government regulation is not necessarily better. Gregg countered that governmental intervention is appropriate where private markets do not adequately address or protect the public interest and fire safety. 2003 NFPA 1 Chapter 15 - Planned Building Groups Gregg noted that the distributed table includes NFPA 1 chapter 15, and section 15.2 references NFPA Standard 1141, which specifies maximum grades for fire department access roads. However, the Commercial Building Code does not address those grades. Consequently, according to Gregg, the Department should prescribe that wherever requirements in Comm 14 differ from the Commercial Building Code, the most restrictive requirement applies. Bob questioned whether establishing that prescription would mean the Department would then have to inform code users of when to look at which code to use. Gregg said no and that instead the users would have the responsibility to look at both codes. According to Bob, that event could result in a counter proposal to replace NFPA 1 with the IFC, in Comm 14. Gregg said a corresponding overlap group consisting of building code users and Fire code users was intended to be established after NFPA 1 and the International Building Code (IBC) were adopted, but that group has not yet been formed. Dave commented that NFPA 1 chapter 15 does not appear to have other conflicts with the Commercial Building Code. Bob noted that except for multifamily dwellings, local jurisdictions can adopt more restrictive requirements. Dave asked whether the Department would be the Authority Having Jurisdiction (AHJ), as that phrase is used in NFPA 1, after the Department adopts the updated edition of NFPA 1. Bob answered that the AHJ is construed to initially be the local jurisdiction. Terry commented that the AHJ phrase has been defined differently by Department staff through the years, and further clarification or code definition is needed. Terry noted that difficulties and conflicts continue to arise (1) from ongoing uncertainties in determining which requirements are for design and construction, and therefore governed by the building code, rather than for use or operation or maintenance, and therefore governed by the fire code; (2) from ongoing uncertainties about which code official is primarily responsible for making or accepting that determination; and (3) from the fact that many local fire chiefs and inspectors do not have copies of the IBC, IFC, International Mechanical Code, or International Fuel Gas Code - which are all adopted in the Commercial Building Code. Bob said the Department currently leaves to local levels the determination of which code to apply, unless a local jurisdiction asks to be an agent of the Department. Bob agreed that administration and enforcement should be discussed further as review of the new NFPA 1 requirements continues. Dave emphasized that recognition is needed for the role that fire inspectors should have during construction. Bob agreed and explained that the Department is looking at whether the permit and inspection process in the Department’s one- and two-family dwelling program should be similarly applied to commercial buildings. There may be economic justifications to do so, such as having an associated potential to reduce property-insurance rates; and this process could be implemented without imposing unfunded mandates on local jurisdictions, such as implementing it through contracts with private-sector, independent inspection entities. That contracting could enable the Department to direct its resources more toward training and oversight. And, additional efforts for certifying more commercial building inspectors could result in further interest in creating certifications for fire inspectors. 2003 NFPA 1 Chapter 17 - Wildland Urban Interface Terry commented the Department of Natural Resources typically cites sections 26.11 to 26.13 of the statutes for Wisconsin’s corresponding criteria for forest-fire concerns in a wildland-urban interface, such as when a new development at the fringe of a city will interface with a wildland area. Dave explained that chapter 17 would provide guidance to fire departments when they exercise their authority under section 101.14 (1) (b) of the statutes to address fire prevention concerns in these interface areas. There was agreement that some of the requirements in chapter 17 could apply within these areas to premises which do not contain a public building or place of employment, and which are therefore beyond the current scope of Comm 14. Sam Rockweiler suggested considering whether an informational note should be added to Comm 14 that would alert the code’s users of these or any other requirements in NFPA 1 which are beyond the scope of Comm 14, but which could be within the scope of local enforcement if adopted by local ordinance. 2003 NFPA 1 Chapter 18 - Fire Department Access and Water Supply Bob suggested that the Commercial Building Code Council review this chapter, for determining whether the included requirements could replace some or all of the corresponding current requirements in Comm 62.0500. Terry questioned whether this replacement would result in the chapter 18 requirements applying retroactively to existing developments. Although section 18.2.2.1 applies its access-road requirements only to new construction, Comm 14.003 (1) (a) applies every requirement of Comm 14 retroactively unless specifically stated otherwise in the code - and the supremacy provision in Comm 14.003 (1) (c) would cause the code text in paragraph (a) to prevail over the adopted-standard text in 18.2.2.1, and thereby apply the access-road requirements retroactively. Consequently, Comm 14 would need to specifically state that the chapter 18 access-road requirements do not apply retroactively. 2003 NFPA 1 Chapter 22 - Automobile Wrecking Yards There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any requirements in chapters Comm 61 to 65, and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapter 31 - Wood Products There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any requirements in chapters Comm 61 to 65 and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapter 52 - Stationary Lead-Acid Battery Systems There was discussion that (1) the included requirements do not conflict with any requirements in chapters Comm 61 to 65, and (2) the included requirements should not be burdensome. Bob commented that the signage requirements may conflict with Comm 61 to 65 or the National Electrical Code, and therefore may need further consideration. 2003 NFPA 1 Chapter 60 - Hazardous Materials There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any requirements in chapters Comm 61 to 65, and (2) the included requirements should not be burdensome. Dave noted NFPA 1 Appendix section A-60.3.2 clearly indicates that the NFPA building code’s classification system for hazardous occupancies is generally equivalent to the IBC’s corresponding classification system. 2003 NFPA 1 Chapter 63 - Compressed Gases and Cryogenic Fluids There was consensus to accept the chapter because (1) the included requirements do not have any apparent conflicts with any corresponding Commerce codes, and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapter 64 - Corrosive Solids and Liquids There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any corresponding Commerce codes, and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapter 67 - Flammable Solids There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any corresponding Commerce codes, and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapter 68 - Highly Toxic and Toxic Solids and Liquids There was consensus to accept this chapter because (1) the included requirements do not have any apparent conflicts with any corresponding Commerce codes, and (2) the included requirements should not be burdensome. 2003 NFPA 1 Chapters 71 to 73 - Pyrophoric, Unstable, and Water-Reactive Solids and Liquids Dave noted that Comm 61.03 (13) (a) 6. applies various use and operation requirements of the IFC that are a contingency of design and construction-related requirements. Dave indicated concern that similar use and operation requirements of NFPA 1 which are a contingency of design and construction-related requirements could be lost if the building code does not address the corresponding design and construction-related requirements. There was interest in archiving the consideration of these requirements so that in the future, the code of the day can generally be reconstructed. Bob suggested adding a note to Comm 61 to 65 that would reference the requirements in Comm 14 for pyrophoric materials. Remaining new requirements in NFPA 1 Bob explained that April 2006 is the targeted date for public hearings on adopting the updated edition of NFPA 1, and that edition is expected to be the 2006 version. The expected effective date is July 1, 2007. A tabular summary of what has been reviewed and what remains to be reviewed could be helpful for proceeding with the remaining new requirements in the 2003 version and the subsequent new requirements in the 2006 version. Terry asked whether adoption of the 2006 version will include repeal of Comm 7, 9, 40, and 45. Bob indicated this inclusion could delay timely adoption of the 2006 version. Dave and Gregg recommended including the repeal but not delaying the July 1, 2007, effective date. Miscellaneous updatesNotices to Comm 7, 9, 40, and 45 Councils As a follow-up to the earlier discussion and the corresponding discussion at the May 5 meeting, Bob said the notices to these Councils could ask the members whether they would have concerns with repealing those codes in conjunction with moving the included requirements to Comm 14 and the Commercial Building Code. Fire Inspection Report form Joe distributed the Department’s Fire Inspection Report form and asked whether the form should be expanded to four pages to include a second copy for the owner. Owners could then use their second copy to record their corrections of any cited violations, and that copy could then be sent back to the fire department as a report of compliance. There was consensus to not expand the form in this manner, because the current copy to the owner can instead be photocopied and used for this purpose. Relocatable power taps In a follow-up to the corresponding discussion at the May 5 meeting, Joe distributed a newly reissued, formal code Interpretation, which updates the previous Interpretation to be consistent with the current version of Standard 1363 from Underwriters Laboratories. Next meetings The next meetings were scheduled for August 8 and September 12, in Conference Room 3C, for the same time period as the June 16 meeting. Bob indicated that in the interim, the Commercial Building Code Council may consider whether to adopt code text for making the most restrictive requirement apply wherever any differences occur between the requirements of the Commercial Building Code and Comm 14. Terry asked which Code Council would review the references in the Commercial Building Code to design and construction requirements in the IFC. Bob explained those reviews will be assigned, as applicable, to the Department’s councils for fire protection systems, fire safety, multifamily dwellings, and commercial buildings. Bob noted those reviews could include consideration of whether the references to the IFC should instead be to corresponding requirements in NFPA 1, for fire inspection purposes. Thursday, May 5, 2005, 9 a.m. - 2:30 p.m., Thompson Commerce Center , Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: Gregg Cleveland, Chair Present; Ken Cole P; Marty King Exc; Dave Lind P; John Periad (Michelle Feldman – Alternate) P; Jim Stormer (Todd Blaser – Alternate) P Guests: Dave Bloom Town of Madison Fire Department; Tod Doebler Menomonee Falls Fire Department Commerce Staff: Sue Birren, Bob DuPont, Joe Hertel,
Terry Nolen, Luann Robb, Sam Rockweiler, Jim Smith
Portable tanks over 110 gallons Note (3) explains which of the corresponding inspections under Comm 10 must be conducted by individuals who are certified as tank inspectors under Comm 5. Sam indicated that an additional Note may be helpful to explain how Comm 48 also regulates containers which have a capacity of under 275 gallons and which are used for storing gasoline or any other petroleum product having a flash point of less than 100°F. Terry recommended expanding the Note to include a reference to section 101.14 (2) of the Statutes, to reflect the duty of fire chiefs to provide fire inspections in public buildings and places of employment. Ken Cole questioned whether concerns would arise about the extent of the Notes being proposed in Comm 14, and he asked whether the Notes convey any authority or contain requirements. Sam explained that informational Notes in a code are appropriate if they are helpful, but they cannot impose any requirements. Ken asked for clarification of the interaction between Comm 10 and Comm 14. The response was that Comm 10 is aimed more at environmental regulatory issues while Comm 14 is focused on fire safety issues. Gregg Cleveland commented that combining Comm 10 and Comm 14 into one code may be desirable as a long-term goal. Sam commented that the informational Notes – in combination with the draft changes to Comm 10 and 14 which were developed in response to discussions at the Council’s meeting on January 25, and which were discussed at the subsequent meeting on March 8 – are expected to resolve the Council’s concerns that were reflected in the corresponding motion at the January 25th meeting. There was agreement that with this resolution, relaying those concerns to the Department’s Comm 10 advisory committee, as requested in the January 25th motion, would no longer be needed.
Relocatable power taps
Fire drills and fire alarms in schools
Dave Lind noted that an existing building which is changed to include a school occupancy must comply with the change-of-use requirements in Wisconsin’s Commercial Building Code - chapters Comm 61 to 65. Jim Smith agreed, but noted that revisions to the Code in 2002 included elimination of a requirement to provide a fire alarm system under certain conditions for fewer than 50 occupants [see IBC Section 907.2.3]. Sue questioned whether the 50-occupant threshold includes all of a building’s occupants, or only the occupants of the portion of the building that includes the school. And wherever a fire alarm system is not provided, Sue emphasized that there is a need for guidance on how to conduct a fire drill. Ken commented that most of the private, choice schools start with less than 50 students, and some of these schools hope to expand beyond 50. Ken added there is a growing trend toward locating these schools in multi-use buildings. Gregg questioned whether the topic would be addressed by the Department’s advisory council for alterations and changes of occupancies. Terry commented that the problem is compounded by several other factors as well: the statutory definition of a school or an educational occupancy is different than the definitions in the Commercial Building Code and the Fire Prevention Code; and there are differences between the fire-drill requirements in section 118.07 of the Statutes and the requirements for emergency egress and relocation drills in NFPA 1 (or the requirements for emergency-evacuation drills in the IFC, where it is adopted locally). Terry circulated an excerpt of various requirements relating to fire drills, from chapters 115 and 118 of the Wisconsin Statutes, from NFPA 1, and from the International Building Code and International Fire Code. He also circulated an informational notice the Department published in 2003 to alert owners and managers of new requirements for emergency egress and relocation drills in NFPA 1 for other occupancies besides schools. Luann reported that the Department’s Fire Drills Report form for schools is being revised, and she distributed copies of the current form. Ken commented that the Wisconsin Department of Public Instruction issues a license to schools which receive State funding, and that the private, choice schools are only permitted in the Milwaukee school district. There was interest in asking the DPI to enclose a notice with the license that is issued to each of these schools, for informing them that the Commercial Building Code and the Fire Prevention Code have additional requirements that may apply to the school, including the requirements that apply to mixed-use buildings. There also was interest in asking the DPI to notify the corresponding fire department when these new school licenses are issued. Bob and Sue agreed to contact the DPI accordingly.
Records for fire incidents, and surplus State
computers
Bob noted the Department has about 80 surplus computers, which could be given to local fire departments who do not have computers, for electronically reporting fire incidents or annual summaries. Additional surplus computers may be available from other Departments. According to Gregg, the fire chiefs believe all fire departments should participate in electronic data entry for NFIRS, and distributing the surplus computers through the Fire Prevention Coordinators would be good. Gregg suggested that the Department request written assurance from each prospective recipient that they do not have a computer, and the Fire Prevention Coordinators could look for the computers during the 2 percent-dues audits. Dave Lind questioned whether the recipients would need to purchase software and modems. Bob indicated those purchases could be fundable by the 2 percent-dues monies; and for volunteer fire departments, the computers could be located within a home. Terry commented that the Coordinators support statistical reporting as a fundamental basis for identifying problem areas. Future limited resources could then be focused on those identified problem areas. He noted that reporting of fire incidents has been a longstanding problem, and agreed that 101.141 of the Statutes does not require NFIRS reporting. As currently codified in Comm 14.47 (3), each fire chief must submit written fire-incident reports to the Department no later than April 1, for the previous year. The reports must contain at least the information specified in subsection (5), which only lists the time, date, and location of fires and number of firefighters responding to each fire. Terry noted that several longstanding, fundamental issues need to be overcome. These include the unfunded mandate in Comm 14 to annually submit the reports to the Department, the lack of a corresponding statutory mandate to submit the reports, an inability of average volunteer fire departments to keep up with the complicated NFIRS reporting system, a high turnover rate in the fire-department reporting staff, and the corresponding training needs of new staff replacements. Bob indicated a preference for having Department staff serve as a help desk for NFIRS rather than perform the corresponding data entry, in part because local staff will not be encouraged to fully participate if they expect Department staff will do the data entry. Dave agreed that broad participation in NFIRS is in the best interest of the fire service. Dave questioned whether the Department should ask fire departments who are not participating why they are not. Gregg said they may respond by asking why they should participate, and he noted the Department has not issued a corresponding annual report of the fire incidents since 1993. Gregg suggested revising that report to be more of a summary – similar to the annual summary of woodland fires that is published by the Department of Natural Resources - which would be more helpful with local elected officials. Bob suggested that the fire departments who are not participating may be more likely to submit a condensed, annual summary to the Department. Ken Cole suggested the Department move more toward providing materials free through online resources, but charging for all paper-based versions. Dave recommended that the Department establish a date after which only electronic-based reporting will be accepted. Bob said electronic reporting could be mandated in the 2007 edition of Comm 14, and take effect in 2008. Dave noted the fire inspectors could support electronic reporting, but only the fire chiefs can decide to do it. Gregg agreed with establishing a cutoff date for paper-based reporting, and agreed that the Council and the fire chiefs would need to support moving to only using electronic-based reporting.
Continued review of Subchapter III of Comm 14
Terry commented that the current text in Comm 14.16 deletes the corresponding requirements in 2000 NFPA 1 section 16-4 for fireworks manufacturing and section 16-8 for explosives, and instead refers the reader to Comm 9 and 7, where the NFPA 1 requirements are then applied again - which causes the reader to come full circle to the same requirements that were initially deleted. Bob noted that Comm 9 and 7 have not yet been fully reviewed for consistency with the revised Commercial Building Code that became effective in 2002. Terry added that some of the requirements in Comm 9 have been superceded by federal regulations which have taken effect since 2001. There was recognition that the NFPA 1124 standard for manufacture, transportation, storage, and retail sale of fireworks is referenced in both the 2000 and 2003 editions of NFPA 1. Bob suggested deleting the Notes under Comm 14.16 that refer to Comm 9 and 7, because a general Note under Comm 14.003 (6) includes the same reference. Joe Hertel recommended reviewing any corresponding new requirements in the 2003 edition of NFPA 1 before adopting them. Bob said the Department could notify the Comm 9 and 7 Council members and their nominators that the Comm 14 Council is recommending applying the 2003 NFPA 1 chapter 65 requirements for fireworks and explosives, in addition to the requirements in Comm 9 and 7. The notification could include corresponding excerpts from chapter 65, and could give the recipients a one-month period to respond with any concerns. Terry recommended emphasizing in the notification that any responses to the Comm 14 recommendations should focus only on concerns related to the minimum requirements necessary to establish a reasonable level of fire and life safety and property protection from the hazards created by fire, explosion, and dangerous conditions - because that is the focus of NFPA 1. There was recognition that 2003 NFPA section 65.11.2 contains requirements for retail sales of consumer fireworks, as extracted from the 2003 edition of NFPA 1124, and that those requirements extend beyond what was required in the 2000 edition of NFPA 1, which referenced the 1998 edition of NFPA 1124. There was interest in reviewing where section 167.10 of the Statutes supercedes the 2003 NFPA 1 requirements for these sales. Comm 14.17 - flammable and combustible liquids Comm 14.21 - liquefied petroleum gases and liquefied natural
gases Comm 14.23 - mechanical refrigeration Comm 14.27 - manufactured-home and recreational-vehicle sites Comm 14.28 - refueling Comm 14.29 - fire hose threads and fittings Comm 14.30 - service stations and repair garages Terry raised concern with whether a design or construction requirement in NFPA 1 chapter 30 or 66 should be disregarded if Comm 61 to 65 is silent on the topic, and Bob responded that it should be disregarded unless a Wisconsin modification specifically applies the requirement. Terry recommended that the Council discuss this topic further as it relates to the minimum requirements necessary to establish a reasonable level of fire and life safety and property protection from the hazards created by fire, explosion, and dangerous conditions. Comm 14.31 (1) - maintenance of membrane structures Comm 14.31 (2) - vehicle parking near tents Comm 14.31 (3) - flammable and combustible liquids near tents Comm 14.31 (4) and (5) - abatement of special hazards, and
combustible materials near tents Comm 14.31 (6) - smoking and open flame in tents Comm 14.31 (7) - maintenance of outdoor grandstands
Next meeting Tuesday, April 5, 2005, a.m. to 2:30 p.m., Thompson Commerce Center, Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council member attendance: Gregg Cleveland, Chair (Dave Lind, Alternate) Present; Ken Cole P; Marty King P; Dave Lind (Tod Doebler, Alternate) P; John Periad (Michelle Feldman, Alternate) P; Jim Stormer (Todd Blaser, Alternate) P Department of Commerce staff: Darrell Christy, James Daniels, Bob DuPont, Joe Hertel, Dan Meneguin, Terry Nolen, LeRoy Nordmeyer, Sam Rockweiler, Sheldon Schall; Bill Shane, Jim Smith. Dave Lind opened the meeting with a round of introductions. In reviewing the progress report from the preceding, March 8 meeting, Bob DuPont commented that the reference on page 3 to a Department advisory group for inspecting one- and two-family dwellings should have explained that the group’s purpose was to assist in developing contracts which independent inspection agencies will execute with the Department in conjunction with performing inspections in municipalities that choose to not perform the inspections. Terry Nolen commented that past progress reports had addressed several unresolved issues which are still pending; and he indicated that the reports should contain enough detail to reflect the status or resolution of each issue brought before the Council. Terry explained that progress reports serve as a valuable archive tool for establishing the original purpose and intent of a council’s decision on an issue. A motion was made by Ken Cole, seconded by Tod Doebler, and passed unanimously, to accept the progress report from the March 8, 2005, meeting, as revised to reflect Bob’s comment about the advisory group for inspecting one- and two-family dwellings.
Intermediate
bulk containers and portable tanks over 110 gallons
Terry commented that the 2000 NFPA 1 Chapter 17 requirements which apply to these vessels are specifically excluded from Comm 14; a note in Comm 14 then directs the reader to see Comm 10 for requirements for flammable and combustible liquids; and Comm 10 then applies the same NFPA 30 requirements that are excluded from Comm 14. Terry indicated this creates frustration with fire inspectors because it causes them to come full circle to the same NFPA 30 requirements they were originally informed not to use. According to Terry, another problem is that the text for flammable and combustible liquids that has been proposed for adding to Comm 14 is limited to tanks and containers under 110 gallons. Many intermediate bulk containers and tanks that are used for distribution and industrial processes fall between 110 and 660 gallons. The fire inspector will be the code enforcement person most likely to come into contact with these vessels during the required twice-a-year fire inspections. What the fire inspectors want is a single code book that prescribes the minimum requirements for a reasonable level of fire safety and property protection from the hazards created by fire and explosion. A single code book would assist them in performing their day-to-day field inspections. Sheldon commented that NFPA sometimes refers to these vessels as intermediate bulk containers and sometimes as portable tanks - and NFPA is having difficulty in addressing them, partly because they are sometimes used for liquids that are not fire hazards. Consequently, according to Sheldon, a variety of acceptable industry practices have developed over time for using these vessels with those liquids, which fire inspectors may not be familiar with and may not view as being acceptable, particularly when these vessels are used for liquids that are fire hazards. Bob and Sam Rockweiler suggested adding an informational note to Comm 14 that would summarize the corresponding fire-safety requirements in Comm 10. Dave recommended also adding an informational note to Comm 14 that would alert readers to which of the corresponding inspections under Comm 10 must be conducted by individuals who are certified as tank inspectors under Comm 5. Dave added that during the current updating of Comm 10, consideration should be given to whether its requirements are consistent with the requirements for flammable and combustible liquids in chapter 66 of the 2003 edition of NFPA 1/UFC. Bill Shane commented that corresponding training is very important for fire inspectors and local program operators, and the suggested informational notes in Comm 14 would be helpful. Ken Cole commented that the clarifications should not be a problem, but he would want to know if the regulatory requirements are proposed to be changed. Joe Hertel asked how many Wisconsin modifications of NFPA 30 are included in the proposed Comm 10 changes. Sheldon estimated they number between 12 and 24, and mostly relate to environmental issues. Sheldon explained that a 2005 effective date is desired for the update of Comm 10. Terry asked what cycle is expected for future updates of Comm 10, and Sheldon said it should match the update cycle for the requirements for flammable and combustible liquids in NFPA 30, which is every three years. Sheldon added that the 2006 edition of NFPA 1/UFC could be considered in relation to Comm 10 when it becomes available as well. Terry indicated there is a problem with code harmony and uniform application, because the update cycles for Wisconsin’s codes for commercial buildings, fire prevention, and flammable and combustible liquids, and the adopted NFPA codes and referenced NFPA standards, currently are not synchronized with each other.
Relocatable
power taps
Terry explained that the present problem with the power taps is that the corresponding requirements in Comm 14 and the NFPA 1 and IFC code commentaries are no longer consistent with the UL guidelines. According to Terry, the explanatory language for temporary use that was added in the revised draft would still be unclear to most fire inspectors, and should be clarified in order to resolve ongoing arguments about permanent versus temporary use. Dave said training on the topic is needed, such as at the Fall fire inspectors’ conference, and further efforts at keeping the Fire Prevention Coordinators informed for consultation purposes, along with posting a clear-enough notice on the Department’s Web site, should occur soon. Joe agreed to further clarify the notice, and Dave asked that the next revision be sent to the Council with the next progress report. Status
of other unresolved topics from previous meetings Ken asked why the appeals board will be needed, since the audits will now be looking for substantial compliance rather than the absolute compliance that was previously looked for. Dave explained that the fire service is concerned that in the future the audits could move again toward looking for absolute compliance. Bob recommended that this topic be discussed further when the Council’s review of Comm 14 advances to the subchapter which addresses the fire department dues program.
Defining
what constitutes a fire inspection
Benchmarks
for substantial compliance
Comm
14 problematic issues
Comm
14 rules for the National Fire Incident Reporting System
Inspection
of seasonal occupancies, and special-order requirements
Dave indicated the fire service wants Comm 14 to identify and list all of the criteria that are needed for obtaining a special order, such as the risk analysis which is currently required by Comm 14. Bob said he would also like to see this codified but in such a way that the fire departments would not need to continue asking Commerce for a written special order. For example, a fire department could meet the stated code criteria, and record and maintain that in their fire department records, which would avoid requesting and granting a special order. According to Terry, this portion of Comm 14, and the included list of occupancies that can be inspected once per year, has been reviewed for possible additions or deletions in every code cycle since being created in the 1992 edition. Terry indicated that for the purposes of this portion of Comm 14 and NFPA 1, vacant buildings are distinctly different from buildings which are not open for business when a fire inspector is there.
Stop-use
rules for local Department deputies
Comm
61 to 65 compliance orders from Fire Prevention Coordinators
Review of Subchapter III of Comm 14
Comm
14.04 (1)
There was agreement that the requirements in Comm 14.04 - for self-closing devices on egress doors, and for maintaining unobstructed egress - are adequately addressed in 2003 NFPA 1 sections 3.3.173, 4.4.3, 12.8.3.5, 12.9.4.4, 14.4, 14.5.4, 63.2.14.1.3, A.12.9.4.4, A.14.4.1, and A.14.5.4.1.
Comm
14.05
Comm
14.06 (1)
Comm
14.06 (2)
Comm
14.06 (3)
Comm
14.06 (4)
Comm
14.06 (5)
Comm
14.06 (6)
Comm
14.07 (1) (a)
Comm
14.07 (1) (b)
Comm
14.07 (2)
Comm
14.07 (3) (a) and (b)
Comm
14.07 (3) (c)
Comm
14.07 (4) (a), (b), and (c)
Comm
14.07 (5)
Comm
14.07 (6) (a) and (b)
Comm
14.07 (6) (c)
Comm
14.08
Next
meetings
Tuesday, March 8, 2005, 9 a.m. to 2:30 p.m., Thompson Commerce Center , Room 3B, 201 West Washington Avenue, Madison, Wisconsin Council member attendance: Gregg Cleveland - Chair (Keith Anderson - Alternate) Present; Ken Cole P; Marty King (Rick Gale - Alternate); Dave Lind P; John Periad (Michelle Feldman - Alternate) P; Jim Stormer (Todd Blaser - Alternate) P Department of Commerce staff: Bob DuPont; Joe Hertel; Dan Meneguin; Terry Nolen; Sam Rockweiler
Dave Lind asked to expand the agenda to include discussion of the Department’s participation in the Spring Fire Inspector’s conference. Dave explained that public education will be a focus of the conference, and although only one of the Department’s Fire Prevention Coordinators is scheduled to participate, the other four Coordinators also provide oversight for public-education efforts. Bob DuPont responded that the Coordinator who is participating has the district in which the conference will be held, and Joe Hertel added that the agenda topics for the conference do not relate strongly enough to the Department’s activities to justify having all five Coordinators participate. Dave asked whether the Inspector’s Fall conference will likewise have only one Coordinator participating, and Bob responded that a need may arise for more than one to attend. Dave asked to also expand the agenda to include discussion of the statutory authority for fire chiefs to cause correction of fire hazards. According to Dave, the statute is sometimes being interpreted to mean that a fire department must conduct a follow-up, verification inspection after issuing an order to correct a fire hazard or violation relating to fire prevention. Bob responded that to achieve substantial compliance in the fire-dues audits, local fire departments must perform various initial inspections, but the departments can decide whether any follow-up, verification inspection is needed prior to the next statutorily-prescribed inspection. Terry Nolen added that during performance of the fire-dues audits, the Fire Coordinators generally look at whether local orders from fire departments include adequate direction for correcting hazards and violations. Dave commented that defining what constitutes an inspection has not been done for many years, but should be, such as clarifying whether participation in a public-education effort at a school should count as one of the statutorily-prescribed inspections. Bob responded that the Department currently relies on the corresponding judgement of local fire departments, as based on the range of cooperation they may expect or encounter from individual property owners. There was interest in looking at how the model fire codes define inspection. Dave said a concrete, overly restrictive definition is not desired, but a level playing field is. As an example, Dave questioned whether substantial compliance is achieved if an inspector repeatedly visits a building that is not open, and each time the inspector leaves a note asking for a telephone call to schedule an inspection, but the call never results. Dave asked to also expand the agenda to include discussion of whether the transfer to the Program Development Bureau will result in changes to the Fire Prevention Section. Bob responded that he is committed to improving the Fire Prevention program - and he commented that the program is a model for other programs in the Safety and Buildings Division, in part because the ratio of 5 field staff to about 850 local units is one of the highest ratios of any S&B program. According to Bob, the model is particularly effective when field and local staff have adequate input in the program, as a partnership with the Department - otherwise, local units may choose to drop out of the program. In comparison, Bob referenced an advisory group the Division has assembled for improving cooperation from small municipalities that have opted out of inspecting one- and two-family dwellings. Terry asked whether ongoing topics that were not included on the agenda would be addressed, such as developing an appeals process for the fire-dues audits, and creating stop-use rules in Comm 3 or 14. Bob responded that development of stop-use rules in Comm 3 is under way for Departmental staff, but development of similar rules in Comm 14 for local staff awaits resolution of whether the Fire Prevention Section and administration of Comm 14 will transfer to the Department of Justice - in part because that Department has a different definition of which individuals are authorized to be Department deputies. Terry asked if development of the stop-use rules in Comm 14 would be revisited if the transfer to Justice does not occur. Bob responded that it would, during the update of Comm 14 which is expected to replace the 2000 version of the incorporated NFPA 1 with the 2006 version. Ken Cole noted concern for the extent of the foregoing discussion, since the corresponding topics were not announced in the official public notice for the meeting, and he recommended that such discussion be instead scheduled on an agenda of a future meeting. A motion was made by Ken Cole and seconded by Rick Gale, to accept the progress report from the January 15, 2005, meeting. Terry commented that the portion addressing the National Fire Incident Reporting System should have included a comment that field staff are concerned about moving from a four-part reporting system to a single reporting system. The motion passed with no opposition, and with an understanding that the field staff’s concern for moving from a four-part NIFIRS reporting system to a single reporting system would be reflected in the progress report for the March 8 meeting.
Governor’s
Budget Bill Bob
reported that the Governor’s proposed budget bill includes
the Department’s response to the Governor’s request
for a ten-percent reduction in funding and in positions. That response
includes reducing the number of positions in the Fire Prevention
Section from 7.6 to 6.6, which should parallel the efficiency gains
that are expected from implementing the substantial-compliance
methodology in the fire-dues program. Bob added that the funding which
is saved by eliminating the position will revert to the local level
rather than lapse into the State’s general fund. Dave asked
for the rationale in eliminating the position. Bob responded that
because Wisconsin’s average per capita earnings rate is low
compared to other States, Wisconsin’s per capita ratio for
cost of government versus average earnings is relatively high. Reducing
the number of positions should reduce the cost of government, which
should then reduce the high ratio. Bob added that if the Fire
Prevention Section transfers to the Department of Justice, the number
of authorized positions is expected to remain at 7.6, to facilitate the
corresponding start-up activities in that Department - and a position
elsewhere in Safety and Buildings would be eliminated instead School-hallway storage As a follow-up to the corresponding discussion at the January 25 meeting, Joe reported that the Department’s position is to not pursue a code change for storage of combustibles in egress hallways for schools. Joe commented that enabling the storage by providing a smoke-detection-and-alarm system should be a cost-effective option. Bob agreed that if a school chooses to begin or to continue the storage, some construction requirements may be triggered. In response to a clarification request from Terry, Joe explained that this option, or the option to provide fire sprinklers, could include providing smoke detectors or fire sprinklers only in the hallway rather than throughout the building. Bob explained that the Commercial Building Code would treat either option as an alteration, and therefore not require retrofitting the entire building. Relocatable power taps In a follow-up to the corresponding discussion at the January 25 meeting, Joe distributed and discussed a draft informational notice for clarifying acceptable uses of relocatable power taps, as based on current guidelines from Underwriters Laboratories Inc. Joe explained that UL generally does not rescind a listing for a product if the product’s benchmark standard changes, but a product recall could occur if a potential for significant problems develops. Terry commented that UL interprets the guidelines to mean relocatable power taps cannot be used in place of any required wiring, or where tools would be needed for removal. Joe explained that the power taps have no history of causing fire hazards, and the UL guidelines do not prescribe a limit on the length of time that the taps can be used. Terry suggested expanding the draft to include reference to how NFPA 1 and the International Fire Code addresses temporary usage. Joe noted the UL guidelines permit usage with certain, prescribed light-duty equipment “and other equipment,” but although “other equipment” is not defined, it is not expected to include heavy-duty items such as washing machines and refrigerators. Joe agreed to expand the draft to address short-term versus long-term use, and to clarify that they are not intended for equipment which draws a heavy load, and to further clarify how the taps are not a substitute for fixed wiring. Web posting of the Wisconsin Enrolled Commercial Building Code As a follow-up to the corresponding discussion at the January 25 meeting, Bob distributed and discussed a printout of a Safety and Buildings Web site showing directions on how to access a free, online version of the WECBC, at the International Code Council Web site. According to Bob, a more robust online version may become available at a prescribed cost, but that cost has not been determined yet. Bob noted there may be about a two-month delay before the online version includes a link to the changes in the Wisconsin Commercial Building Code that became effective on January 1, 2005. Bob added that the compact disc version of the WECBC cannot be updated to include the January 1 changes, which further motivates the Department to keep its rules current with the ICC model codes and to minimize modifications to those codes. Transfer of rules from Comm 10 to Comm 14, and new rules for Comm 14 As a follow-up to the corresponding discussion at the January 25 meeting, Sam Rockweiler summarized the draft rules and analysis that were transmitted to the Committee on the preceding Friday and Monday, for clarifying the requirements which are transferring from Comm 10 to Comm 14. As described in the analysis, Sam noted that the draft change for Comm 14.002 would expand the scope of Comm 14 to include nearly all of the tanks and other containers which are being excluded from Comm 10 and which involve storage, transfer, or dispensing of flammable, combustible, or hazardous liquids. Tanks that are being excluded from Comm 10 because they are regulated under ACTP 32 or 33 would not be included in this expanded scope of Comm 14. Sam explained that although Comm 14.002 (1) currently applies Comm 14 only to public buildings and places of employment, the expanded scope for the included tanks and containers would extend beyond that limit, because Comm 10 likewise now extends beyond that limit. However, the expanded scope would not extend to Indian reservation land, or to facilities that are either leased to the federal government or exempted by federal statutes or treaties. The expanded scope would also apply retroactively to any of these tanks and other containers that exist on the effective date of the rule change, because Comm 14 otherwise now applies retroactively to existing conditions. Sam explained that the draft changes for Comm 14.47 (2) would clarify that Comm 14 does not restrict the statutory authority of Department deputies, including local fire chiefs, to investigate and cause correction of any condition - anywhere, not just at public buildings or places of employment - which is either liable to cause fire, or will endanger or hinder fire fighters in case of fire. Sam explained that the draft Note for Comm 10.210 (2) would clarify how Comm 61 to 65 addresses existing, unchanging public buildings and places of employment - in addition to addressing new construction for public buildings and places of employment. Terry commented that the draft
rules and analysis are helpful, by addressing scope, application,
design and construction conflicts, the Commercial Building Code, and
retroactivity. There was agreement that the draft rules and analysis
adequately address and clarify the evolving interface between Comm 10
and Comm 14, and the corresponding fire prevention requirements and
statutory authority. Construction/use-and-maintenance enforcement coordination Bob explained that the current framework of having one suite of model codes address design, construction, and maintenance of commercial buildings - along with having a different model code address fire prevention in those buildings - came about late in the process of adopting those model codes, which tended to segregate building inspectors and fire prevention inspectors into those two areas. According to Bob, current efforts are focusing on reintegrating fire inspection and building inspection activities. For example, fire inspectors should be able to go as far into the commercial building code as they are comfortable with and knowledgeable about, and the Department understands that fire departments may routinely prefer to contact the Fire Prevention Coordinators for assistance - rather than the Division’s Building Inspectors, who have extensively scheduled work lists. Keith Anderson commented that a substantial number of new local building inspectors are not familiar with how the Fire Prevention Coordinators were helpful with inspections prior to the segregation Bob described. Dave agreed that fire inspectors have an established comfort level in working with the Coordinators rather than the Division’s Building Inspectors, and he noted that the reference to reintegrating fire inspection and building inspection activities fits well with the recognition earlier in the meeting that the fire prevention program is a model for other programs in the Safety and Buildings Division. Inspection of seasonal occupancies Keith questioned how inspection of seasonal occupancies should be addressed in relation to the two-percent dues audits, because the buildings are frequently closed. Bob explained that an exterior-only inspection could count as one of the two required annual inspections. Terry commented that although local fire departments have an option to obtain a special order to conduct less frequent inspections, such as for these occupancies, that option generally is not utilized. Bob noted that Comm 14.47 (2) (d) 2. m. allows reduced inspections for vacant buildings, and there was interest in addressing seasonal occupancies in a similar manner. Terry commented that similar concerns occur with large buildings which are constructed to conceal items from aerial surveillance photography, and warrants may be needed to gain access to those buiildings. Dave recommended changing Comm 14 for seasonal occupancies, to require one interior inspection per season of occupancy. There was agreement this change should be created as Comm 14.47 (2) (d) 2. s., with an understanding that exterior inspections can also be conducted where desired. Review of Subchapter III of Comm 14 Bob explained that as Comm 14 is updated to incorporate the 2003 and 2006 versions of NFPA 1/UFC, the Department does not want to inadvertently leave some things behind. Dave commented that the update should move more toward how Comm 16 incorporates the NFPA National Electrical Code. Dave and Terry noted that at previous Council meetings, several documents had been distributed which could be helpful as references during the update: (1) a tabular listing and narrative, by John Anderson, for comparing the content of the current Comm 14 with the content of the preceding version of Comm 14; (2) a Microsoft Powerpoint printout by Terry on fire code history; and (3) an overview by Dave of relevant Wisconsin statutes, Comm codes, and NFPA 1/UFC. Ken asked what the overall objective of the update is, and Bob responded that it is to move toward adopting the next version of NFPA 1. Ken asked whether that includes looking at what changes may be needed for the next version, and Bob said yes. Ken asked whether parts of that version could be deleted, and Bob said yes, such as if a requirement is overkill and has a benefit which is not worth the cost. Ken commented that one objective should be to minimize modifications of NFPA 1, and Keith agreed. Terry commented that discussions at previous meetings had dealt with definition issues, such as whether long-standing definitions in model codes for fire hazard and eminent danger differ from how those two terms are addressed in Wisconsin’s statutes. Bob recommended applying the definitions in Comm 14 to the entire code, rather than only to the modifications of NFPA 1, in subchapter III.
Comm
14.03 (2)
Comm
14.03 (1)
Comm
14.03 (3)
Comm
14.03 (4)
Comm
14.03 (5)
Comm
14.03 (6)
Comm
14.03 (7)
Comm
14.03 (8) through (10)
Comm
14.03 (11)
Comm
14.03 (12)
Comm
14.03 (13)
Comm
14.03 (14)
Comm
14.03 (15)
Comm
14.03 (16)
Next
meetings: The
next three meetings were scheduled for April 5 in Conference Room 3B,
May 5 in Conference Room 3B, and June 7 in Conference Room 3C; for the
same time period as the March 8 meeting. Tuesday, January 25, 2005, 9 a.m. to 3 p.m., Thompson Commerce Center, Room 3C, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: Gregg Cleveland, Chair, Present; Ken Cole, P; Marty King, P; Dave Lind, P; John Periad, Absent; Jim Stormer (Todd Blaser, Alternate), P. Guests: Dave Bloom, Town of Madison Fire Department; Tod Doebler, Menomonee Falls Fire Department; Rick Gale, West Allis Fire Department. Department of Commerce Staff:: Bob DuPont, Joe Hertel, Duane Hubeler, Dan Meneguin, Terry Nolen, Sam Rockweiler. Gregg Cleveland opened the meeting with a review of the agenda and a round of introductions.
Progress
reports from preceding meetings
Transfer
of rules from Comm 10 to Comm 14, and new rules for Comm 14
Duane explained that the draft rule changes also include some newly proposed requirements for Comm 14, such as criteria for defueling of aircraft. Duane noted those criteria were developed because of concern that the topic is not adequately addressed in NFPA 410, and the criteria reflect input from Midwest Express, Mitchell Field Airport, and the Waukesha Fire Department. In reference to the included revision of section Comm 14.17, Duane explained it would undelete some of the criteria in chapter 17 of NFPA 1 that were deleted when NFPA 1 was adopted in 2002, but any of that criteria which fits better within the scope of Comm 10 will be placed in Comm 10 instead of Comm 14. Gregg noted concern that the draft rule changes would increase complexity by making additional references to other codes, whereas the rule changes should instead decrease complexity. Gregg also indicated concern for whether the scope of Comm 10 is being narrowed to address only public buildings and places of employment, and concern that the rules which are being transferred to Comm 14 would then have the narrower scope in Comm 14 of applying only to public buildings and places of employment. Bob DuPont explained that Comm 10 has a tradition of applying to all premises, including one- and two-family dwellings, whereas Comm 14 has traditionally been applied only to public buildings and places of employment. However, the rules that are transferring from Comm 10 to Comm 14 could carry their current Comm 10 scope with them. Bob added that moving the rules to Comm 14 would have an added benefit of putting them under the direct purview of the Comm 14 Council. An alternative of transferring some of the rules to the one- and two-family dwelling code would be less desirable because that code does not have the retroactive application that Comm 14 has. Duane referred to proposed new criteria in Comm 10.115 (2) (a) that would more clearly address the authority which fire inspectors have for fire prevention and for response to fire hazards. Dave Lind commented that the new criteria in Comm 10.115 (2) (a) should also be included in Comm 14, and likewise be applied there to more than just public buildings and places of employment, and Marty agreed. Dave referred to the motion from the preceding meeting to adopt the 2003 edition of NFPA 1/ UFC, and recommended comparing the corresponding criteria there to the proposed criteria for Comm 10 and 14. Gregg questioned whether the proposed rules would address conflicts with construction requirements. Duane responded that since 1991, Comm 10 has referred to the Wisconsin Commercial Building Code, Comm 61 to 65, for design and construction of public buildings and places of employment, and he explained that draft section Comm 10.210 (2) would substitute the applicable provisions of Comm 61 to 65 for NFPA 101, 220, and 221. Dave questioned whether Comm 61 to 65 applies only to new construction, and Sam Rockweiler responded that Comm 61.03 (12) requires existing buildings to be maintained to conform with the building code requirements which applied when the building was constructed. Dave suggested adding an informational note under Comm 10.210 (2) about the Comm 61.03 (12) requirements. Terry Nolen commented that (1) the broad application of Comm 10 since 1931 has been to regulate flammable and combustible liquid commodities rather than a building in which they are contained; (2) the Working Draft does not clearly show which parts would be new requirements; (3) the Comm 14 Council may want to consider whether its purview should include the fire prevention criteria that will remain in Comm 10, such as regulation of containers during shipping; and (4) unclear references to secondary standards can cause dilemmas when determining which standards should apply. Gregg asked whether adopting the 2003 edition of NFPA 1/UFC now would be better than adopting circuitous references now. Bob responded that adopting the 2003 edition of NFPA 1 will take substantial time, and the interim adoption of the proposed rules can happen significantly sooner. Rick Gale noted concern for a lengthy period for adopting 2003 NFPA 1, and concern for the costs to local officials of purchasing a variety of codes rather than purchasing one code or one set of codes. Joe Hertel emphasized the benefits of carefully reviewing national standards before adopting them, and cited as an example the difficulties that were avoided in Wisconsin by not adopting recently developed NFPA requirements for arc-fault circuit interrupters until after the marketplace had adapted to the new requirements. Dave noted interest in adopting the interim proposed rules sooner rather than later. A motion was made by Dave Lind and tabled, to have Department staff relay the concerns expressed about the proposed rules to the Comm 10 advisory committee, and to then present that committee’s response back to the Council.
Fire
chief representative on Dwelling Code Council
Stop-work/stop-use rules, and
potential transfer of Comm 14 to Justice Bob reported that discussions with the Department of Justice are continuing on whether administration of Comm 14 will be transferred to the State Fire Marshal’s Office. Gregg recommended that development of the stop-work, stop-use rule text should proceed rather than be held up pending the outcome of the discussions with DOJ. Bob agreed Commerce would consider developing stop-work, stop-use rules for local officials, that would apply to all the requirements in Comm 14, rather than only the rules which are transferring from Comm 10 to Comm 14. Terry asked for further discussion of the impacts on staff if (1) Comm 14 transfers to DOJ or (2) stop-work, stop-use rules are implemented. Hallway
lockers in schools
Relocatable
power taps
Portable
heaters
Training
issues
NIFIRS
reporting Dave recommended listing the minimum computer-system requirements in the transmittal, and enclosing a copy of Comm 14. Terry said field staff support statistical reporting and want to see its outcome, but the lack of a statutory mandate to submit the reports may be a topic the Council wants to address. Gregg noted he had not received the Department’s Wisconsin Burning publication for the past several years, which previously summarized the submitted reports. Bob cited problems with the nonstatistical nature of the previous reporting, which led to discontinuing the Burning publication. Dave suggested polling fire departments on whether they have the needed computer equipment, and Dan said that had already been done. Gregg agreed to distribute a summary from Dan to fire chiefs for their input, and to then report back before the finalized materials are sent to the fire chiefs and municipalities. Terry indicated this process would be similar to the audit process, and building consensus through it would be more helpful than the piecemeal approach in the past that was ineffective.
Fire-dues
audits
Gregg reported that at a December 2004 meeting with Senator Ron Brown, the Department’s Deputy Secretary, and the Safety and Buildings Administrator, there was discussion of whether to convert the fire-dues audit program to a block-grant program. According to Gregg, Senator Brown would not support the conversion, the Deputy Secretary said the concept would go no further, the Fire and EMS Legislative Liaison Coalition does not want it to go further, and there was agreement that the substantial compliance concept is instead the best approach to achieve an appropriate blend of enforcement and funding.
Previous
motion to adopt 2003 NFPA 1/UFC
Ken Cole reiterated that the Department has emphasized growing Wisconsin’s economy in part by minimizing regulations wherever appropriate. Gregg commented that substantial costs could have been avoided if the NFPA building code suite had been adopted instead of the ICC suite. Bob said that 80 to 90 percent of building code officials throughout the country previously operated under one of the three model building codes that were the predecessors to the ICC suite. Dave commented that an NFPA mainstay for many years has been its criteria for existing buildings, whereas the ICC criteria for existing buildings, in the International Existing Building Code, have been published for only about three years. Bob noted that the scope of Comm 14 is limited to requirements for use and maintenance, and if design and construction ideas arise during updating of Comm 14, they can be referred to the Commercial Building Code Council and the Multifamily Dwelling Code Council. Gregg asked if the Department is not going to proceed with the motion’s recommendation to apply the most restrictive requirement wherever any conflicts occur between NFPA 1 and Comm 61 to 65. Bob responded that the Department is not going to proceed with applying that concept in a blanket manner, but individual design and construction requirements in NFPA 1 may be considered in relation to updating Comm 61 to 65. Dave recommended that the Alteration and Change of Occupancy Council closely review NFPA 1, which deals extensively with existing buildings. Bob said that the Comm 14 Council would be kept updated with relevant items from the Department’s other advisory groups, such as the Commercial Building Code Council. Rick Gale asked whether joint meetings with the other councils have been or would be considered. Bob responded that joint meetings could be helpful if the councils begin moving in divergent directions. Dave commented that conflicts can be expected as the Alteration and Change of Occupancy Council begins looking at the IEBC and NFPA 1. Coordination of construction
inspections and use and maintenance inspections Gregg said a key question is whether the Department’s Fire Prevention Coordinators can issue orders to enforce compliance with Comm 61 to 65. Terry commented that in the past the Coordinators could address basic, general enforcement for Comm 61 to 65, but the Department is moving more toward having the Coordinators enforce only Comm 14. Dan explained that the Integrated Services Bureau is clarifying staff roles through a team that studied overlaps between Safety and Buildings programs. Gregg said the Fire Coordinators should be able to work freely within Comm 61 to 65, which could include making referrals to other staff, such as referring electrical problems to electrical staff. According to Dave, a significant change occurred in 2001, when the Fire Coordinators were no longer authorized to receive formal training for Comm 61 to 65 - and that training had improved their capability to assist fire departments as a first stop in obtaining compliance with Comm 61 to 65. Bob noted that the Department’s commercial building inspectors receive assigned-work lists for inspecting construction projects, and must also assist local building inspectors - but in the commercial buildings program, the Department does not have district staff who are primarily assigned to assist local staff, as does exist in the plumbing program and in the private sewage program. Terry commented that prior to the change in 2001, the Fire Prevention Coordinators provided that assistance. A motion was made by Gregg Cleveland, seconded by Dave Lind, and passed with no dissenting votes, to revert back to the pre-2001 practice of having the Department’s Fire Prevention Coordinators able to (1) assist local fire departments in addressing fire prevention aspects of buildings and (2) receive training on the Commercial Building Code. Dave Lind resurrected his previously tabled motion, with a second from Gregg Cleveland, to have Department staff relay the Council’s concerns about the proposed fire prevention rules in the Comm 10 Working Draft, to the Comm 10 advisory committee, and to then present that committee’s response back to the Council. The motion passed, with a dissenting vote from Ken Cole.
Timeline
for updating Comm 14
Next
meeting
Wednesday, October 13, 2004, 9 a.m. to Noon, Thompson Commerce Center, Room 3C, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: Gregg Cleveland, Chair, Present; Ken Cole, P; Marty King P; Dave Lind, P; John Periad (Jennifer Cape, Alternate), P; Jim Stormer (Steve Krause, Alternate), P. Guests: Dave Bloom, Town of Madison Fire Department; Tod Doebler, Menomonee Falls Fire Department; Edwin Erickson Department of Commerce Staff: Debra Bresser, Bob DuPont, Joe Hertel, Dan Meneguin, Terry Nolen, Sam Rockweiler Gregg Cleveland opened the meeting with a round of introductions and a review of the agenda.
Progress reports from
preceding
meetings
A motion was made by Marty King, seconded by Dave Lind, and passed with no dissenting votes, to accept the progress report from the August 26 meeting, as amended by the preceding discussion. A motion was made by Marty King, seconded by Dave Lind, and passed with no dissenting votes, to accept the revised progress report from the May 18 meeting, as transmitted by email on October 5.
Division and Department
updates
Dave Lind suggested additional training for fire inspectors that focuses on electrical issues. Joe agreed the Division could develop the training, and Dave agreed to contact Joe accordingly after discussing the topic further with other members of the fire service. Terry Nolen noted that section
101.14 of the statutes requires the Department to provide training to
fire inspectors, and asked whether any free training is being
developed. Joe responded that free training has been discussed,
including evening training for volunteer fire departments. Joe
circulated a Division handbook that enrolls the NEC requirements with
the electrical requirements from Wisconsin’s Commercial
Building Code - chapters Comm 61 to 65 - and suggested posting the
handbook on the Division’s Web site. Dave suggested also
distributing the handbook at the 2004 fall conference for fire
inspectors.
2003 Wisconsin Act
219
Comm 14 audit procedures
Ken Cole noted an understanding that there was a need for an appeals process under the previous audits, which were based on whether 100 percent compliance was achieved, but questioned whether an appeals process would still be needed under the new concept of “substantial compliance.” Bob explained that a reliance on substantial compliance should result in fewer failures, and that although all Department determinations are subject to a statutory appeal process, a separate, additional appeals process for the fire-dues audits might be helpful. Bob distributed and discussed a draft fire-dues self-certification audit form and corresponding instructions. Bob said the draft audit form and instructions could be referred to the fire-dues task force for their review and advice, and Gregg agreed. Bob explained that the draft audit form incorporates the substantial-compliance concept - and includes a separate section for input from local clerks, which Dave agreed would be helpful. Dave liked the form’s citation of the statute sections that the audited requirements devolve from, but emphasized that fire inspectors need to be reminded that they have other statutory responsibilities as well. Dave also liked the proposed audit-explanation sheet in Gregg’s handout, and indicated an appeals process will still be needed under the substantial-compliance concept because although the auditors will receive detailed guidance, they will still make subjective decisions. For a local unit that certifies on the form that substantial compliance was not achieved, Gregg asked whether a physical audit by the Department should be expected in the following year, and Bob responded yes. Ken recommended continuing to emphasize that 100 percent compliance is still the statutory duty and the goal, but the substantial compliance concept should be helpful. A motion was made by Gregg Cleveland, seconded by Dave Lind, and passed with no dissenting votes, to refer the draft audit materials to the fire-dues task force for its review and response back to the Committee. Terry asked whether the task force would address input or concerns from out-state stakeholder sessions, and Gregg responded the task force should address that as well any concerns from the legislature. Comparison of NFPA 1 2000 to
NFPA 1/UFC 2003 A motion was made by Dave Lind, and seconded by Gregg Cleveland for discussion purposes, to revive a previously tabled motion to adopt the 2003 edition of NFPA 1 in its entirety, except where Wisconsin’s statutory requirements override; and to include in that adoption a clause that for design and construction, if any conflicts occur between NFPA 1 and chapters Comm 61 to 65, the most restrictive requirement shall apply. Ken asked whether passage of the motion would constitute a recommendation from the Committee to the Department Secretary, and Dave responded yes. Ken asked whether the net effect of adopting the 2003 edition would be more regulation. Dave responded he did not believe that adopting the 2003 edition would require schools to do more, and commented that the 2003 edition would be more user-friendly, for both regulators and owners. Gregg estimated that 90 percent of the fire-safety maintenance requirements for schools are contained in the 2003 edition. Ken asked whether the public would be subjected to additional regulation if the motion is implemented, particularly as a result of the clause that would apply the most restrictive requirement, wherever conflicting criteria occur. Gregg responded that the implementation could result in different design and construction outcomes than under the current requirements, but the costs should not increase significantly, and may, in some cases, be less. Dave indicated that some costs could increase and some could decrease. Ken noted the current widespread interest in growing Wisconsin’s economy in part by minimizing regulation, and he stated that adopting additional regulation which is more user-friendly would not make more regulation more acceptable. Marty King commented that the adoption as proposed would make the current regulation more user-friendly, rather than create additional regulation. Gregg commented that clauses for applying the most restrictive requirement in the event that conflicting criteria occur have been utilized for over 100 years. Jennifer Cape asked whether the adoption as proposed would apply retroactively to existing conditions, and Dave responded the retroactive application would be no greater than in other codes. Bob responded that since the adoption would be in Comm 14, which applies to all current and proposed uses, the adoption would apply retroactively to all current uses. Dave commented that NFPA 1 includes provisions which allow the authority having jurisdiction to determine that a compliant building at the time of construction can remain noncompliant with a subsequent code if no hazard occurs. Bob noted that Wisconsin’s construction requirements generally since the 1930’s have applied only to proposed construction, except where the statutes have imposed retroactive requirements, and he explained that alterations sometimes occur to accommodate new use restrictions. Bob commented that adoption of the 2003 edition of NFPA 1 might not have a big impact on the Division, but the broad scope of the motion raises a bigger question of what the relationship should be between the Fire Prevention Code and the Commercial Building Code, particularly where the Building Code would allow an existing building to remain unchanged but the Fire Code would require the building to change. Gregg suggested that the proposed adoption could include an effective-date clause which would result in applying any future retroactive aspects only to buildings constructed after that date. Dave estimated that the 2003 edition of NFPA 1 is in use in about 23 states, and usually in combination with the International Building Code (IBC). According to Dave the 2003 edition allows a building owner or occupant to perform a life-safety evaluation, and if the results indicate the building is safe enough, no new requirements apply. Ken asked whether Department recommendations were available for the motion. Bob responded that there would be concern for the motion’s impact on the relationship between the Building Code and the Fire Code, and although the effective-date clause which Gregg suggested might resolve some of that concern, there would still be concern that a building designer would have to consider design requirements in both codes during the design stage. Dave suggested consolidating the competing/most restrictive criteria into one document, and he noted that a performance-based design option is available in both codes. Terry commented that the Department’s field staff do not share the concern Bob described, and cited an example where the proposed adoption would have prevented a building owner from becoming disadvantaged. The motion passed, with dissenting votes from Jennifer Cape and Ken Cole.
Rules transferring from Comm
10 to
Comm 14
Marty King indicated that a fire inspector would then continue to not be able to apply the design and construction requirements for buildings, in chapter 17 of NFPA 1, for spray-painting within a school. Marty asked whether the IBC includes those requirements, and Terry Nolen responded that if the spray-painting would not be within a spray booth, the entire room would need to comply with the IBC requirements for that use. Terry noted concern for whether moving the rules from Comm 10 to 14 would result in (1) losing a corresponding retroactive effective date, and (2) lessening the applicability of the rules, because Comm 14 applies to public buildings and places of employment, whereas the scope of Comm 10 is broader, such as applying to containers during shipping. Terry suggested retaining the rules in Comm 10 until Comm 14 is modified as outlined in the motion that was adopted by the Council’s preceding action. A motion was made by Dave Lind, seconded by Marty King, and passed with no dissenting votes, to delay the proposed transfer of rules from Comm 10 to Comm 14 until Comm 14 is updated to include adoption of the 2003 edition of NFPA 1, as outlined in the previous motion.
Proposed stop-work and
stop-use rules
Gregg commented that as
deputies of the Department, fire inspectors could apply rules in Comm
3, but having the rules in Comm 14 might be more effective. Bob noted
the scope in proposed section Comm 3.12 could be expanded to be more
universal, as it is in Comm 10, but there could then be concern for how
resulting appeals to local orders would be addressed. According to
Terry, local units that adopt Comm 14 could address those appeals at
the local level, and appeals in local units that do not adopt Comm 14
could be addressed by the Department.
Next meeting
Submitted
by Sam Rockweiler, code consultant to the Council Thursday, August 26, 2004, 9:30 a.m. to noon, Thompson Commerce Center, Room 3C, 201 West Washington Avenue, Madison, Wisconsin Council Member Attendance: Gregg Cleveland, Chair, Present; Ken Cole, P; Marty King, P; Dave Lind, P; John Periad (Jennifer Cape - Alternate), P; Jim Stormer (Todd Blaser - Alternate) Absent. Guests: Dave Bloom - Town of Madison Fire Department; Tod Doebler - Menomonee Falls Fire Department. Department of Commerce Staff: Ron Buchholz, Bob DuPont, Joe Hertel, Dan Meneguin, Terry Nolen, Sam Rockweiler, Kimberly Walker. Sam Rockweiler opened the meeting with a round of introductions, and he distributed and summarized an Advisory Council Manual produced by the Safety and Buildings Division. Dave Lind asked why Terry Nolen was not serving as chairperson, and why a tape recording of the meeting was not being made, as were agreed to at the previous meeting. Ken Cole commented that a tape recording was suggested at the previous meeting, rather than agreed to. Bob DuPont explained that the Council members are appointed by the Department, and that although Department staff attend the Council’s meetings in order to receive the Council’s input, the Division’s policy is that the chairperson must be a member of the Council, and the Council cannot expand its membership to include Department staff. Bob added that since the Council serves an advisory role, the Department will also consider minority viewpoints that occur when consensus is not achieved. A motion was made by Dave Lind, seconded by Marty King, and passed unanimously, to have Gregg Cleveland serve as the Council Chairperson.
Progress reports from
preceding
meetings
Gregg offered to provide recording equipment if the Department could not, and Dave Lind offered to have his staff transcribe recorded tapes and then return the tapes to the Department. Gregg noted that the members who had issues with the previous reports are compiling the issues and will have them at the next meeting. Ken Cole said he had no problems with any of the previous reports. He added that the role of the Council is to provide advice, and he did not see why the level of precision desired by taping would change whether or how that advice is accepted. Gregg said that taping would record the proceedings so that later if representatives of included groups change, the new reps could go back to the recordings to get all of the details. Jennifer Cape suggested that anyone who wanted to could bring their own recorder. Marty King said the Department has a duty to maintain records, and members can submit letters disputing the reports. Ken added that such letters could be attached to the reports. Ron Buchholz noted that the Division’s process of utilizing written progress reports has worked for 30 years, without taping. Dave Lind asked whether a vote to accept a progress report is an endorsement of the contents. Bob responded that acceptance of the report means it is an accurate summary of what happened, but does not necessarily convey agreement with included positions on issues. A motion was made by Ken Cole, seconded by Marty King, and passed unanimously, to accept the progress report from the preceding, June 15 meeting. Ken noted his understanding that any issues with the reports for the two meetings preceding the June 15 meeting would be presented at the next meeting. Dave Lind noted concern for running counter to the reports. A motion was made by Dave Lind and seconded by Jennifer Cape, to table discussion of the progress reports for the two meetings preceding the June 15 meeting. Ken noted desire to amend the motion to reflect that if the Council is not presented at the next meeting with the issues for the reports for the two meetings preceding the June 15 meeting, then those two reports would be accepted. Dave disagreed with the proposed amendment. The motion passed, with a dissenting vote from Ken Cole.
Division and Department
updates
Gregg asked whether a different definition of the term would not be advanced for legislative review until after August 31, and then not be accepted for review there until after the first session day of next year’s legislature. Bob responded that a definition of “substantial compliance” is expected to be advanced to legislative review prior to the August 31 cutoff, and a definition of “administrative expenses” would be advanced later, after it is revised to include more detail, in order to arrive at a definition that is acceptable. Gregg stated the fire service does not want the two definitions split apart and advanced separately. Bob explained that the Department’s rules cannot bind the legislature from passing legislation in the future, and previous lapse legislation has protected some fund sources, but not others, from lapses. Bob added that the Department is looking at whether not lapsing money from the fire dues fund would be precedent-setting for other fund sources, and he said there may be unique aspects of the statutory appropriation for the fire dues fund that enable avoidance of setting such precedence. Bob distributed and discussed pages from the Department’s Web site showing (1) how to subscribe to the Division’s various email distribution groups, such as the Fire Prevention group, for receiving occasional email alerts to news of potential interest; (2) a listing of all of the Division’s Advisory Councils; and (3) how to access online details for the Councils, such as each Council’s function, and their corresponding agendas, meeting summaries, and membership list. Bob distributed and discussed a chart showing a projected schedule of meetings of the Division’s specialty councils and umbrella councils, for developing the next comprehensive update of the Wisconsin Commercial Building Code. Bob explained that (1) the Transitioning Buildings Specialty Council was newly created, to develop more specificity for these buildings than is contained in the current code; (2) the Fire Protection and Fire Safety Specialty Councils were likewise newly created; and (3) the Comm 14 Council is a stand-alone council, rather than a specialty council that provides input to the umbrella councils. Bob reported that the Division’s Electrical Code Council would begin meeting in the fall to review the 2005 edition of the National Electrical Code, and adoption of corresponding updates to Wisconsin’s Electrical Code is expected in mid 2005. Gregg asked for the total cost of the recent redesign of the Department’s Web site, and for the extent of the fire dues money that was used for the redesign. Bob agreed to obtain the data and provide it to Gregg.
Stop-work and stop-use rules
Dave Lind indicated the citations would be a good idea, and asked how state staff could handle the accompanying workload. Bob agreed that handling the workload is a concern. Gregg asked whether a draft of the stop-work and stop-use rules would be considered at the next meeting, and Bob said yes. Marty King asked whether the draft would be distributed prior to the meeting, and Bob said yes.
Final rule draft for
“substantial compliance”
A |